OL1 (Motor overload): The motor overload protection relay operates due to excessive load as per the motor nameplate's nominal current.

Check:

- Load size or V/f pattern setting

- Set the nominal current of the motor shown on the nameplate with n32.

OL2 (Inverter overload): The inverter overload protection relay operates due to excessive load.

Check:

- Load size or V/f pattern setting

- Check the inverter capacity.

- Overload

- Incorrect V/f pattern setting

- Insufficient acceleration time during acceleration

- Input air temperature exceeding 50°C

- Fan stoppage

- Load size
- V/f pattern setting
- Input air temperature.

- Check the driven machine and correct the cause of the error or increase the fixed n60 value to the maximum value allowed for the machine.

OL3 (Over-torque detection): The inverter output current exceeds the pre-set value at fixed speed n60. When over-torque is detected, the inverter operates according to the pre-set setting of fixed n59.

EF? (External fault): The inverter receives an external fault input from the control circuit terminal. The output is turned OFF, and the motor stops rotating freely.

- EF0: External fault reference via MEMOBUS communication

- EF2: External fault input command from control circuit terminal S2

- EF3: External fault input command from control circuit terminal S3

- EF4: External fault input command from control circuit terminal S4

- EF5: External fault input command from control circuit terminal S5

CPF-00: Initial memory error detected.

CPF-01: ROM error detected.

CPF-04: EEPROM error of the inverter control circuit detected.

CPF-05: A/D converter error detected.

CPF-06: Option card connection error or incompatible option card connected.

CPF-07: Operator control circuit (EEPROM or A/D converter) error.

CE (MEMOBUS communication error): Normal reception of communication data is not possible. Check the communication devices or communication signals.

STP (Emergency stop): The inverter stops according to n04 after receiving the emergency stop alarm signal.

Note: Refer to page 34 for the display/clearing of error history.

Perform a power cycle. If the error persists, replace the inverter.

Insufficient power supply voltage

Control power supply error

Hardware error

Check:

- Power supply voltage
- Are the main circuit power supply cables connected?
- Are terminal screws tightened?
- Control sequence.

Replace the inverter.

Incorrect operation mode selection.

Operation command (n02) not set to Control Circuit Terminal.

Set the operation command (n02) to Control Circuit Terminal.

3-wire sequence effective.

For using a 3-wire sequence, ensure that the S2 control terminal is closed. For using a 2-wire sequence, set the multifunction input (n37) to a value different from the 3-wire sequence.

Motor stops.

Torque does not come out.

Lock prevention level during acceleration is too low.

During acceleration, the output current reaches the set level, the output frequency stops, and the acceleration time increases due to the lock prevention level (n56) being set too low.

Check if the lock prevention level during acceleration (n56) is set to an appropriate value.

Local mode effective. Set the digital operator's LO/RE selection to RE.

Wrong operation method selection.

Example: 4-20mA entered as reference, but SW set as "V."

For analog input, make sure the frequency reference (n03) and SW settings are correct.

Lock prevention level during operation is too low.

During operation, the output current reaches the set level, and the speed decreases due to the lock prevention level (n57) being set too low.

Check if the lock prevention level during operation (n57) is set to an appropriate value.

Load is too heavy.

Due to excessive load, lock prevention is activated, the output frequency stops, and the acceleration time increases.

Extend the set acceleration time (n16). Reduce the load.