Omron G7 Fault Codes 5
CPF04 - Internal A/D Converter Error
An error has occurred in the A/D converter inside the CPU.
If the control circuit is damaged, replace the inverter.
CPF05 - External A/D Converter Error
An error has occurred in the external A/D converter of the CPU.
If the control circuit is damaged, replace the inverter.
CPF06 - Option Card Error
The Option Card is not properly connected.
If the Option Card or inverter is faulty, replace the Option Card or the inverter.
CPF07 - RAM Error (ASIC Internal RAM Error)
An error occurred in the RAM inside the ASIC.
If the control circuit is damaged, replace the inverter.
CPF08 - Watchdog Timer Error
An error has been detected in the watchdog timer.
If the control circuit is damaged, replace the inverter.
CPF09 - CPU Error (CPU-ASIC Diagnosis Error)
An error occurred between the CPU and ASIC.
If the control circuit is damaged, replace the inverter.
CPF10 - ASIC Version Error
An error was detected in the ASIC version, indicating the inverter’s control circuit is faulty.
Replace the inverter.
CPF20 - Option Card A/D Converter Error
An error was detected in the A/D converter of the communication Option Card.
The Option Card may not be properly inserted. Power off and reinsert the card.
If the Option Card is faulty, replace the Communication Option Card.
CPF21 - Option Card CPU Error
A self-diagnosis error occurred in the Communication Option Card.
Replace the Option Card.
CPF22 - Option Card Model Code Error
An error was detected in the model code of the Communication Option Card.
Ensure the Option Card is the correct model or replace it if necessary.
CPF23 - Option Card DPRAM Error
An error occurred with the DPRAM in the Communication Option Card.
Check the Option Card and replace it if necessary.
OPE01 - kVA Selection Error
The inverter capacity setting is not compatible with the device.
Contact your Yaskawa representative to resolve this error.
OPE02 - Limit Error
The set value is outside the current adjustment range.
Press the ENTER key to display U1-34 (OPE error constant) and correct the faulty setting.
OPE03 - Terminal Error (Multi-Function Input Selection Error)
One of the following errors may have occurred in the multi-function input settings:
The same setting may have been selected for more than one multi-function input.
A stand-alone up/down command may have been selected (they must be used together).
Up/down commands and Accel/Decel Ramp may have been selected simultaneously.
Speed Search 1 and Speed Search 2 may have been selected at the same time.
Up/down commands may have been selected while in PID control mode.
Positive and negative speed commands may not have been set simultaneously.
NO and NC emergency stop commands may have been set simultaneously.
Check for these errors and make the necessary corrections.
OPE05 - Option Card Selection Error
The Option Card was selected as the frequency reference source (b1-01 setting 3), but the Option Card is not connected.
Ensure the Option Card is connected or correct the frequency reference source.
OPE06 - Missing PG Option Card
PG feedback V/f control was selected (A1-02 setting 1), but a PG Speed Control Card is not connected.
Connect the PG Speed Control Card or change the control method settings.
OPE07 - Analog Input Selection Error
The same setting was selected for both analog input selection and PID function.
Check settings H3-09 and H6-01 and adjust them if necessary.
OPE08 - Constant Selection Error
An unnecessary setting was made for the current control method. For example, a function used only for open-loop vector control may have been selected for V/f control.
Press the ENTER key to display U1-34 (OPE error constant) and correct the faulty setting.
OPE09 - PID Control Selection Error
The following settings were made simultaneously:
b5-01 (PID Control Mode Selection) is set to a non-zero value.
b5-15 (PID Sleep Function Operation Level) is set to a non-zero value.
b1-03 (Stopping Method Selection) is set to 2 or 3.
Review and correct these settings.
OPE10 - V/f Data Setting Error
The settings for E1-04, E1-06, E1-07, and E1-09 do not meet the following conditions:
E1-04 (FMAX) ≥ E1-06 (FA) > E1-07 (FB) ≥ E1-09 (FMIN)
Check and correct these settings.
OPE11 - Carrier Frequency/Open Delay Setting Error
One of the following constant setting errors may exist:
C6-05 (Carrier Frequency Gain) > 6, Carrier Frequency Lower Limit (C6-04) > Carrier Frequency Gain (C6-05)
Upper/lower limit error between C6-03 and C6-05.
C6-01 value is 0, and C6-02 value is between 2 and E.
C6-01 value is 1, and C6-02 value is between 7 and E.
Check and correct these settings.
ERR - EEPROM Read/Write Error
A verification error occurred while writing to the EEPROM.
Try turning the power off and on again.
Try resetting the constants.