Omron G7 Fault Codes 4
UL3 - Insufficient Torque Detected 1
A current below the value set in L6-02 occurred for longer than the time set in L6-03.
Ensure that the settings for L6-02 and L6-03 are appropriate.
Check the mechanical system and resolve the cause of the insufficient torque.
UL4 - Insufficient Torque Detected 2
A current below the value set in L6-05 occurred for longer than the time set in L6-06.
Ensure that the settings for L6-05 and L6-06 are appropriate.
Check the mechanical system and resolve the cause of the insufficient torque.
OS - Overspeed Detected
The motor speed remained above the value set in F1-08 for longer than the time set in F1-09.
The speed reference may be too high. Check the reference circuit and the reference gain.
Ensure that the settings for F1-08 and F1-09 are appropriate.
Adjust the gain to prevent excessive speed increase or decrease.
PGO - PG Connection Lost
No PG (Pulse Generator) signal was received while the inverter was outputting a frequency.
There may be a break in the PG wiring. Repair the cables.
The PG may be connected incorrectly. Correct the wiring.
The PG may not be receiving power properly. Ensure that the PG is powered correctly.
If the motor uses a brake, check for an open circuit.
DEV - Speed Deviation Too Large
The speed deviation exceeded the value set in F1-10 for longer than the time set in F1-11.
The load may be too heavy. Reduce the load.
The acceleration and deceleration times may be too short. Extend these times.
The load may be locked. Check the mechanical system.
Ensure that the settings for F1-10 and F1-11 are appropriate.
If the motor uses a brake, check for an open circuit.
CF - Control Error
During open-loop vector control, the torque limit was exceeded for more than 3 seconds during deceleration.
The motor constants may be incorrect. Check the motor constants and perform autotuning.
An error may have occurred in the speed estimation calculation for open-loop vector control 2.
If a run command was issued before the motor stopped, enter the run command after the motor has fully stopped.
Set the b3-01 (Speed Search Selection) to 1 or 3 (speed search enabled at start).
Refer to additional information regarding open-loop vector control precautions.
FBL - Feedback Loss (PID)
The PID feedback reference was lost (b5-12 = 2), and the PID feedback input dropped below the level set in b5-13, continuing for the time set in b5-14.
Review the necessary settings when PID feedback loss is detected.
EF0 - External Fault (From Communication Card)
An external fault input was received from the Communication Option Card.
Check the Communication Option Card and communication signals.
EF3 - External Fault (Input Terminal S3)
An "external fault" signal was received from the multi-function input terminal.
Reset the external fault inputs using the multi-function inputs.
Eliminate the cause of the external fault.
EF4 - External Fault (Input Terminal S4)
An external fault signal was received from input terminal S4.
Eliminate the cause of the external fault.
EF5 - External Fault (Input Terminal S5)
An external fault signal was received from input terminal S5.
Eliminate the cause of the external fault.
SVE - Zero Servo Error
The rotation position changed during the zero servo operation.
The torque limit may be too small. Increase the limit.
The load torque may be too large. Reduce the load torque.
Check for signal noise.
OPR - Digital Operator Connection Error
A connection was lost while attempting to connect to the Digital Operator during a RUN command.
Check the connection with the Digital Operator.
CE - MEMOBUS Communication Error
After control data was received once, no normal reception was obtained for more than 2 seconds.
Check the communication devices and signals.