Omron V7 fault codes 2
BB (External Baseblock):
Check: NO/NC contact selection, wiring, and PLC signals.
EF (Simultaneous FWD/REV Run Commands):
Check: NO/NC contact selection, wiring, and PLC signals.
STP (Operator Function Stop / Emergency Stop):
Turn OFF: FWD/REV Run Command of control circuit terminals and check wiring and signals.
FAN (Cooling Fan Fault):
Check: the cooling fan, connection, and ensure nothing is obstructing rotation.
CE (MEMOBUS Communications Fault):
Check: communication devices, signals, PLC, transmission cable, and wiring.
FBL (PID Feedback Loss Detection):
Check: the mechanical system and correct the cause, or increase the value of n137.
Option Card Communications Fault:
Check: communication devices, signals, PLC, transmission cable, wiring, and ensure the option card is inserted correctly.
OC (Overcurrent):
Check: for short circuits or grounding at the Inverter output side, excessive load, rapid acceleration/deceleration times, special motor use, starting motor during coasting, and leak current due to long wiring.
GF (Grounding):
Check: the cause and restore operation, ensuring no short-circuit or ground fault occurs at the Inverter output.
SC (Load Short Circuit):
Similar checks and actions as GF.
OV (Main Circuit Overvoltage - Running):
Check: for large regenerative energy, short deceleration time, excessive negative load, and input voltage errors.
UV1 (Main Circuit Low Voltage - Running):
Similar checks and actions as UV, with additional checks while the Inverter output is ON.
UV2 (Control Power Supply Fault):
Replace the Inverter.