Omron J1000 fault codes 2
oL1 Motor Overload fault code for Omron J1000 VFD:
This error indicates that the electrothermal sensor has tripped overload protection. If you encounter this error, the possible causes and solutions are:
Cause: The load is too heavy.
Solution: Reduce the load to avoid overloading the motor.
Cause: The cycle times are too short during acceleration and deceleration.
Solution: Increase the acceleration and deceleration times (C1-01 through C1-04). If the drive is overloaded at low speeds, reduce the load, increase the speed, or use a motor specifically designed to operate with the drive.
Cause: Although a special type of motor is being used, the motor protection selection is set for a general-purpose motor (L1-01 = 1).
Solution: Set L1-01 = "2" to match the motor type.
Cause: Voltage is too high for the V/f characteristics.
Solution: Adjust the user-set V/f patterns (E1-04 through E1-10). Parameters E1-08 and E1-10 may need to be reduced to avoid overloading the motor at low speed.
Cause: The wrong motor-rated current is set to E2-01.
Solution: Check the motor-rated current and enter the value written on the motor nameplate to parameter E2-01.
Cause: Multiple motors are running off the same drive.
Solution: Disable the Motor Protection function (L1-01 = "0") and install a thermal relay to each motor.
Cause: The electrical thermal protection characteristics and motor overload characteristics do not match.
Solution: Check the motor characteristics, correct the value set to L1-01 (Motor Protection Function), or install an external thermal relay.
Cause: The electrical thermal relay is operating at the wrong level.
Solution: Check the current rating listed on the motor nameplate and check the value set for the motor-rated current (E02-01).
Cause: Motor overheated by overexcitation operation.
Solution: Prevent excessive overexcitation operation or apply proper cooling to the motor. Reduce the excitation deceleration gain (n3-13) and set L3-04 (Stall Prevention during Deceleration) to a value other than 4.
Cause: Output current fluctuation due to input phase loss.
Solution: Check the power supply for phase loss.
By following these solutions, you can address the potential causes of the oL1 Motor Overload fault and hopefully resolve the issue. It is important to note that this fault code may have other potential causes, and it is best to refer to the manual for your specific VFD for more information on troubleshooting and addressing this error.
OL2 fault on an Omron J1000 VFD:
oL2 Drive Overload
The thermal sensor of the drive triggered overload protection.
Cause: Load is too heavy.
Solution: Reduce the load.
Cause: Cycle times are too short during acceleration and deceleration.
Solution: Increase the settings for the acceleration and deceleration times (C1-01 through C1-04).
Cause: Voltage is too high for the V/f characteristics.
Solution: Adjust the preset V/f pattern (E1-04 through E1-10). Be careful not to lower E1-08 and E1-10 excessively because this reduces load tolerance at low speeds.
Cause: Drive capacity is too small.
Solution: Replace the drive with a larger model.
Cause: Overload occurred when operating at low speeds.
Solution: Reduce the load when operating at low speeds, replace the drive with a model that is one frame size larger, or lower the carrier frequency (C6-02).
Cause: Excessive torque compensation.
Solution: Reduce the torque compensation gain (C4-01) until there is no speed loss but less current.
Cause: Output current fluctuation due to input phase loss.
Solution: Check the power supply for phase loss.
oL3 fault on an Omron J1000 VFD:
oL3 Overtorque Detection 1:
The current has exceeded the value set for torque detection (L6-02) for longer than the allowable time (L6-03).
Cause: Parameter settings are not appropriate for the type of load.
Solution: Check the settings of parameters L6-02 and L6-03.
Cause: There is a fault on the machine side (e.g., the machine is locked up).
Solution: Check the status of the load. Remove the cause of the fault.
oPr fault on an Omron J1000 VFD:
oPr External Digital Operator Connection Fault:
The external operator has been disconnected from the drive.
Note: An oPr fault will occur when both of the following conditions are true:
• Output is interrupted when the operator is disconnected (o2-06 = 1)
• The run command is assigned to the operator (b1-02 = 0 and LOCAL has been selected)
Cause: External operator is not properly connected to the drive.
Solution: Check the connection between the operator and the drive. Replace the cable if damaged. Turn off the drive input power and disconnect the operator. Next, reconnect the operator and turn the drive input power back on.
ov Overvoltage fault on an Omron J1000 VFD:
This fault (ov) indicates that the voltage in the DC bus has exceeded the overvoltage detection level. This can be caused by various factors such as short deceleration time, excessive braking load, surge voltage, ground fault, excessive regeneration, high input power voltage, damaged dynamic braking transistor, or wiring error in the braking transistor. To solve the issue, you need to identify the cause and take appropriate action such as increasing deceleration time, installing a braking resistor or a DC reactor, reducing braking torque, checking the motor wiring, reducing input power voltage, rewiring the braking resistor device, and so on.