Omron P7 fault codes 2

EF0: Communication Option Card External Fault

- What Happened: An external fault condition exists.
+ What to Do: Check for external conditions, verify parameters, and verify the communication signal.

EF3 to EF7: External Fault at Terminal S3 to S7

- What Happened: An external fault condition is connected to a multi-function digital input.
+ What to Do: Eliminate the cause of the external fault condition and remove the fault from a multi-function digital input.

FBL: PI Feedback Loss

- What Happened: This fault occurs when PI Feedback Loss Detection is programmed to fault and the PI Feedback is less than the PI Feedback Loss Detection Level for the specified time.
+ What to Do: Verify the Drive is programmed to receive the PI Feedback source signal and check that the PI Feedback source is installed and working properly.

GF: Ground Fault

- What Happened: Drive output grounding current has exceeded 50% of the Drive rated output current.
+ What to Do: Remove the motor and run the Drive without the motor, check the motor for a phase-to-ground short, and check the output current with a clamp-on meter to verify the DCCT reading.

LF: Output Phase Loss

- What Happened: An open-phase occurred at the Drive output.
+ What to Do: Check the wiring to the motor, check the motor for a phase-to-ground short, and ensure the output terminals are tightened properly.

LL3: Loss of Load Detection 1

- What Happened: Drive output current is less than L6-02 for more than the time set in L6-03.
+ What to Do: Ensure the values in L6-02 and L6-03 are appropriate and check the application/machine status to eliminate the fault.

OC: Overcurrent

- What Happened: Drive output current exceeded the overcurrent detection level.
+ What to Do: Remove the motor and run the Drive without the motor, check the motor and Drive for phase-to-phase shorts, verify C1-01 and C1-02 are set correctly, and check load conditions.

OH1: Cooling Fin/Cooling Fin Fan Overheat

- What Happened: The temperature of the Drive cooling fin exceeded the temperature programmed in parameter L8-02.
+ What to Do: Check for dirt build-up on the fans and cooling fins, reduce the ambient temperature around the Drive, and if necessary, replace the cooling fan.

OH3: Motor Overheat 1

- What Happened: Overheating of the motor as measured by the motor thermistor.
+ What to Do: Recheck the cycle time, load size, acceleration/deceleration times, V/F pattern, and motor rated current value.

OH4: Motor Overheat 2

- What Happened: Similar to OH3, with the Drive stopping operation according to the setting of L1-04.
+ What to Do: Follow the same steps as for OH3.