Omron J1000 fault codes 4
oL3 Overtorque 1:
- Cause: Drive output current was greater than the value set in L6-02 for longer than the time set in L6-03, possibly due to inappropriate parameter settings or a fault on the machine side.
- Solution: Check parameters L6-02 and L6-03, check the status of the machine, and remove the cause of the fault.
ov DC Bus Overvoltage:
- Cause: The DC bus voltage exceeded the trip point due to surge voltage in the drive input power, a short-circuited motor, ground current overcharging the main circuit capacitors, or noise interference causing incorrect drive operation.
- Solution: Install a DC reactor or an AC reactor, check the motor power cable, relay terminals, and motor terminal box for short circuits, correct grounding shorts, review solutions for handling noise interference, check control circuit lines, main circuit lines, and ground wiring, install a surge protector to the magnetic contactor coil, and set the number of fault restarts (L5-01) to a value other than 0.
PASS MEMOBUS/Modbus Communication Test Mode Complete:
- Cause: MEMOBUS/Modbus test has finished normally, verifying that the test was successful.
- Solution: No action required as this indicates a successful test completion. No minor fault output is generated.
SE MEMOBUS/Modbus Communication Test Mode Error:
- Cause: A digital input programmed to 67H (MEMOBUS/Modbus test) was closed while the drive was running.
- Solution: Stop the drive and run the test again. No minor fault output is generated for this alarm.
Uv Undervoltage:
- Cause: One of the following conditions was true when the drive was stopped and a run command was entered: DC bus voltage dropped below the under voltage detection level, the contactor to suppress inrush current in the drive was open, or there was low voltage in the control drive input power. This alarm outputs only if L2-01 is not 0 and DC bus voltage is below the detection level.
- Solution: Check for wiring errors in the main circuit drive input power and correct the wiring, ensure the terminals have been properly tightened, check the voltage and lower the voltage of the drive input power to within the specified limits, check the maintenance time for the capacitors and replace the drive if U4-05 exceeds 90%, check for a tripped alarm when the magnetic contactor, line breaker, and leakage breaker are turned on, check the capacity of the drive input power transformer, check the temperature inside the drive, and replace the drive if the CHARGE indicator light is broken or disconnected.
oPE01 Drive Capacity Setting Fault:
- Cause: The drive capacity setting (o2-04) and the actual capacity of the drive are not the same.
- Solution: Correct the value set to o2-04 to match the actual drive capacity.
oPE02 Parameter Range Setting Error:
- Cause: Parameters were set outside the possible setting range.
- Solution: Set parameters to the proper values within the allowable range.
oPE03 Multi-Function Input Selection Error:
- Cause: A contradictory setting is assigned to multi-function contact inputs, such as the same function assigned to two inputs, incorrect settings for Up/Down commands, or contradictory settings for other functions.
- Solution: Ensure all multi-function inputs are assigned to different functions, correctly set functions that need to be enabled in combination with other functions, and check for contradictory settings.
oPE05 Run Command/Frequency Reference Source Selection Error:
- Cause: Frequency reference is assigned to an option unit that is not connected to the drive, or the Run command is assigned to serial communication but no communication option is connected.
- Solution: Reconnect the option unit to the drive or correct the assignment of the Run command.
oPE10 V/f Data Setting Error:
- Cause: Setting errors occurred where E1-04 is greater than or equal to E1-06, which is greater than or equal to E1-07, which is greater than or equal to E1-09.
- Solution: Correct the settings for E1-04, E1-06, E1-07, and E1-09 to ensure they follow the correct order and values.
oPE11 Carrier Frequency Setting Error:
- Cause: Contradictory settings where C6-05 is greater than 6 and C6-04 is greater than C6-03 (carrier frequency lower limit is greater than the upper limit), or upper and lower limits between C6-02 and C6-05 contradict each other.
- Solution: Correct the parameter settings to ensure that the carrier frequency lower limit is not greater than the upper limit and that there are no contradictions between the upper and lower limits.
Diagnosing and Resetting Faults:
- If a fault occurs simultaneously with power loss, ensure there are no short circuits before restarting the drive. Turn on the drive input power, remove the cause of the fault, and reset.
- If the drive still has power after a fault occurs, look at the LED operator for fault information, refer to the Fault Displays section, and reset the fault.
- You can view fault history data by navigating to U2-02 (Fault History) in the parameter setting screen.
Fault Reset Methods:
- Fix the cause of the fault, restart the drive, and press the STOP button on the digital operator to reset the fault.
- For resetting via Fault Reset Digital Input S4, close then open the fault signal digital input via terminal S4.
- If these methods do not reset the fault, turn off the drive main power supply and reapply power after the LED operator display is out.
Troubleshooting without Fault Display:
- Cannot Change Parameter Settings: Ensure the drive is not running, check the Access Level, ensure the operator is in Parameter Setup Mode, and verify the password if required.
- Motor Does Not Rotate Properly: Check if the drive is in Drive Mode, verify the frequency reference source, ensure correct wiring in the control circuit terminals, and adjust settings as needed.
- Motor is Too Hot: Reduce the load if it's too heavy, cool the surrounding area if it's too hot, and check the motor fan.
- Motor Stalls During Acceleration or With Large Loads: Reduce the load, increase the acceleration time, and ensure the motor size and drive size are appropriate.
- Motor Rotates in One Direction Only: If "Reverse run prohibited" is selected, change the setting to allow reverse operation.
- Peripheral Devices Affected by Drive Operation: Change the carrier frequency to reduce noise, install noise filters, use conduit for shielding, and ensure proper grounding.
- Ground Fault Interrupter Activates When Drive is Running: Use a ground fault interrupter with a higher leakage current detection level or one that incorporates high-frequency corrective actions, and consider lowering the carrier frequency.