Omron E7 Fault codes 3

UL3 (Undertorque Detected 1)

   Meaning: Torque applied was below the level set in L6-02 for a duration longer than the time set in L6-03.
   Possible Causes: Not specified.
   Corrective Actions:
+ Ensure the settings for L6-02 and L6-03 are correct.
+ Check the mechanical system and resolve the cause of the low torque.

FbL (PI Feedback Lost)

   Meaning: PI feedback loss detection is enabled (b5-12 ≠ 0), and the PI feedback input dropped below the level set in b5-13 (PI feedback loss detection level) for longer than the time set in b5-14.
   Possible Causes: Not specified.
   Corrective Actions:
+ Check the PI feedback signal source.
+ Inspect the cables.

EF0 (External Fault Input from Communications Option Card)

   Meaning: External fault input from the Communications Option Card.
   Possible Causes: Not specified.
   Corrective Actions:
+ Check the Communications Option Card and communication signals.

EF3 - EF7 (External Fault)

   Meaning: External fault input from one of the multi-function input terminals (S3 - S7).
   Possible Causes: Not specified.
   Corrective Actions:
+ Resolve the cause of the external fault.

oPr (Digital Operator Connection Fault)

   Meaning: The connection to the digital operator used as the RUN command source was lost during operation.
   Possible Causes: Not specified.
   Corrective Actions:
+ Check the connection to the digital operator.

CE (MEMOBUS Communications Error)

   Meaning: No valid data was received for more than 2 seconds after control data was received.
   Possible Causes: Not specified.
   Corrective Actions:
+ Check the communication devices and signals.

bUS (Option Communications Error)

   Meaning: A communication error was detected with an Option Card during a RUN command or when setting a frequency reference.
   Possible Causes: Not specified.
   Corrective Actions:
+ Check the communication devices and signals.

CPF00 (Digital Operator Communications Error 1)

   Meaning: Communication could not be established with the Digital Operator within 5 seconds of power-up.
   Possible Causes:
+ The Digital Operator may not be connected properly.
+ The control circuits of the inverter may be faulty.
   Corrective Actions:
+ Remove and reinsert the Digital Operator.
+ Replace the inverter.

CPF01 (Digital Operator Communications Error 2)

   Meaning: Communication with the Digital Operator was lost for more than 2 seconds after it was established.
   Possible Causes:
+ The Digital Operator may not be connected properly.
+ The control circuits of the inverter may be faulty.
   Corrective Actions:
+ Remove and reinsert the Digital Operator.
+ Replace the inverter.

CPF02 (Baseblock Circuit Error)

   Meaning: An error occurred in the baseblock circuit.
   Possible Causes: The control circuit may be damaged.
   Corrective Actions: Try turning the power off and on again. If the problem persists, replace the inverter.

CPF03 (EEPROM Error)

   Meaning: An error occurred in the EEPROM.
   Possible Causes: The control circuit may be damaged.
   Corrective Actions: Try turning the power off and on again. If the problem persists, replace the inverter.

CPF04 (CPU Internal A/D Converter Error)

   Meaning: An error occurred in the CPU's internal A/D converter.
   Possible Causes: The control circuit may be damaged.
   Corrective Actions: Try turning the power off and on again. If the problem persists, replace the inverter.

CPF05 (CPU External A/D Converter Error)

   Meaning: An error occurred in the CPU's external A/D converter.
   Possible Causes: The control circuit may be damaged.
   Corrective Actions: Try turning the power off and on again. If the problem persists, replace the inverter.

CPF06 (Option Card Connection Error)

   Meaning: The option card is not properly inserted.
   Possible Causes: The option card may not be properly inserted, or the card or inverter may be faulty.
   Corrective Actions: Turn off the power and reinsert the card. If the issue persists, replace the card or inverter.

CPF07 (ASIC Internal RAM Fault)

   Meaning: An error occurred in the internal RAM of the ASIC.
   Possible Causes: The control circuit may be damaged.
   Corrective Actions: Try turning the power off and on again. If the problem persists, replace the inverter.

CPF08 (Watchdog Timer Fault)

   Meaning: An error occurred in the watchdog timer.
   Possible Causes: The control circuit may be damaged.
   Corrective Actions: Try turning the power off and on again. If the problem persists, replace the inverter.

CPF09 (CPU-ASIC Mutual Diagnosis Fault)

   Meaning: An error occurred during mutual diagnosis between the CPU and ASIC.
   Possible Causes: The control circuit may be damaged.
   Corrective Actions: Try turning the power off and on again. If the problem persists, replace the inverter.

CPF10 (ASIC Version Fault)

   Meaning: There is an error in the version of the ASIC.
   Possible Causes: The inverter's control circuit is faulty.
   Corrective Actions: Replace the inverter.

CPF20 (Communications Option Card A/D Converter Error)

   Meaning: An error occurred in the A/D converter of the Communications Option Card.
   Possible Causes:
+ The option card may not be properly inserted.
+ The A/D converter of the option card may be faulty.
   Corrective Actions:
+ Turn off the power and reinsert the card.
+ Replace the option card.