Omron E7 fault codes 2
PF (Main Circuit Voltage Fault)
Meaning: The DC voltage in the main circuit fluctuates abnormally (when not during regeneration).
Possible Causes:
+ A momentary power loss in the input power supply may have occurred.
+ The cables connected to the input power supply may be loose.
+ The fluctuations in input voltage may be too high.
+ The voltage balance between phases may be poor.
Corrective Actions: Reset the error after resolving the issue.
oH (Cooling Fin Overheating)
Meaning: The temperature of the inverter’s cooling fin exceeded the set limit (L8-02) or 105°C.
Possible Causes:
+ The ambient temperature may be too high.
+ There may be a heat source nearby.
Corrective Actions:
+ Install a cooling unit for the ambient temperature.
+ Eliminate the heat source.
oH1 (Inverter’s Cooling Fan Stopped)
Meaning: The internal cooling fan of the inverter stopped.
Possible Causes:
+ The cooling fan may not be working.
Corrective Actions: Replace the cooling fan (contact your supplier).
oH3 (Motor Overheating Alarm)
Meaning: The inverter will stop or continue running as set when the motor overheats.
Possible Causes:
+ The motor may be overloaded or run at high speeds for an extended period.
Corrective Actions:
+ Check the load size and acceleration/deceleration times.
+ Check the V/f characteristics.
+ Check the motor temperature input at terminal A2.
oH4 (Motor Overheating Fault)
Meaning: The inverter will stop based on the setting in L1-04 when the motor overheats.
Possible Cause: The motor overheated.
Corrective Actions:
+ Check the load size and acceleration/deceleration times.
+ Check the V/f characteristics.
+ Check the motor temperature input at terminal A2.
oL1 (Motor Overload)
Meaning: The motor overload protection function was activated based on the motor's internal temperature.
Possible Causes:
+ The load may be too heavy, or the acceleration/deceleration and cycle times may be too short.
+ V/f characteristics voltage may be too high or too low.
+ The motor’s rated current setting (E2-01) may be incorrect.
Corrective Actions:
+ Check the load size and acceleration/deceleration times.
+ Check the V/f characteristics.
+ Verify the motor's rated current setting (E2-01).
oL2 (Inverter Overload)
Meaning: The inverter overload protection function was activated based on the inverter's internal temperature.
Possible Causes:
+ The load may be too heavy, or the acceleration/deceleration and cycle times may be too short.
+ V/f characteristics voltage may be too high or too low.
+ The inverter capacity may be insufficient.
Corrective Actions:
+ Check the load and acceleration/deceleration times.
+ Check the V/f characteristics.
+ Replace the inverter with one of higher capacity.
oL3 (Overtorque Detected 1)
Meaning: Torque exceeding the limit set in L6-02 was applied for longer than the time set in L6-03.
Possible Causes: Not specified.
Corrective Actions:
+ Ensure the settings for L6-02 and L6-03 are correct.
+ Check the mechanical system and correct the cause of the overtorque.
oL7 (High-slip Braking OL - High-slip Braking Overload)
Meaning: The output frequency did not change for the duration set in N3-04.
Possible Causes:
+ The inertia of the connected machine may be too high.
Corrective Actions:
+ Ensure the load has sufficient inertia.