Omron G7 Fault Codes 3
OH (OH1) - Heatsink Overheat Error
The temperature of the inverter's heatsink has exceeded the value set in L8-02 or 105°C.
This error may occur due to:
The ambient temperature being too high.
A heat source located near the inverter.
The inverter’s cooling fan stopped working (for devices 18.5 kW and above).
Solution: Install a cooling unit to lower the ambient temperature, remove the nearby heat source, or replace the cooling fan.
OH3 - Motor Overheat Alarm
An alarm indicating that the motor is overheating. The inverter will stop or continue to operate based on the L1-03 setting.
This error may occur due to:
The load being too large.
Acceleration, deceleration, and cycle times being too short.
Check the V/f characteristics.
Verify the motor's rated current (E2-01).
OH4 - Motor Overheat Error
This error occurs when the motor overheats. The inverter will stop based on the L1-04 setting.
This error may occur due to:
The load being too large.
Acceleration, deceleration, and cycle times being too short.
Check the V/f characteristics.
Verify the motor's rated current (E2-01).
RH - Braking Resistor Overheat
The braking resistor protection function (set in L8-01) has been activated. This is usually caused by the deceleration time being too short and excessive regenerative energy from the motor.
Solution: Reduce the load, increase the deceleration time, or lower the motor speed. Consider switching to a Braking Resistor Unit.
RR - Braking Transistor Error
The internal braking transistor is not functioning correctly.
Solution: Try turning the power off and on again. If the problem persists, replace the inverter.
OL1 - Motor Overload Error
The motor overload protection function has been activated based on the internal electronic thermal value. The load may be too heavy, and acceleration/deceleration and cycle times may be too short.
Solution: Check the load size, acceleration, deceleration, and cycle times. Verify the V/f characteristics and motor rated current (E2-01).
OL2 - Inverter Overload Error
The inverter overload protection function has been activated based on the internal electronic thermal value. The load may be too heavy, and acceleration/deceleration and cycle times may be too short.
Solution: Check the load size, acceleration, deceleration, and cycle times. Verify the V/f characteristics. If the inverter capacity is too low, replace it with a larger capacity inverter.
OL3 - Excessive Torque Detected 1
A current above the value set in L6-02 occurred for longer than the time set in L6-03.
Solution: Ensure that L6-02 and L6-03 settings are appropriate. Check the mechanical system and resolve the cause of the excessive torque.
OL4 - Excessive Torque Detected 2
A current above the value set in L6-05 occurred for longer than the time set in L6-06.
Solution: Ensure that L6-05 and L6-06 settings are appropriate. Check the mechanical system and resolve the cause of the excessive torque.
OL7 - High Slip Braking Overload
The output frequency did not change for longer than the time set in N3-04. The returning inertia load may be too large.
Solution: Verify that the load is an inertial load. Set the deceleration time to less than 120 seconds.
CPF00 - Digital Operator Communication Error 1
Communication with the Digital Operator could not be established within 5 seconds after power-on.
Solution: The Digital Operator may not be properly connected. Disconnect and reconnect it. If there is an issue with the inverter’s control circuits, replace the inverter. If there’s an external RAM failure, try turning the power off and on again.
CPF01 - Digital Operator Communication Error 2
After communication was established, a communication error with the Digital Operator occurred for more than 2 seconds.
Solution: If the Digital Operator is not fully connected, disconnect and reconnect it. If there’s an issue with the inverter’s control circuits, replace the inverter.
CPF02 - Baseblock Circuit Error
An error was detected in the baseblock circuit.
Solution: Try turning the power off and on again. If the control circuit is damaged, replace the inverter.
CPF03 - EEPROM Error
An error occurred in the EEPROM.
Solution: Try turning the power off and on again. If the control circuit is damaged, replace the inverter.