Omron G7 Fault Codes 2

OC (Overcurrent)
The inverter output current exceeded the overcurrent level (200% of the inverter's rated current).

    A short circuit or ground fault occurred at the inverter output. (This could be due to motor burnout, worn insulation, or damaged cables.)
    The load is too large, or the acceleration/deceleration time is too short.
    A motor with too large a capacity is being used for the inverter.
    A magnetic switch opened at the inverter output.
Solution: After fixing the cause, reset the fault.

GF (Ground Fault)
The ground fault current at the inverter output exceeded 50% of the rated output current.

    A ground fault occurred at the inverter output. (This may be due to motor burnout, worn insulation, or damaged cables.)
Solution: Fix the cause and reset the fault.

PUF (Main Fuse Blown)
The fuse in the main circuit blew.

    The output transistor failed due to a short circuit or ground fault.
    Check for a short circuit between the following terminals. A short circuit can damage the output transistor:
    B1 (3) ←→ U, V, W
Solution: After correcting the cause, replace the inverter.

OV (Overvoltage)
The main circuit DC voltage exceeded the overvoltage level:

    200V class: Approximately 410V
    400V class: Approximately 820V

    The deceleration time is too short, and the regenerative energy from the motor is too large.
    The power supply voltage is too high.
Solution: Increase the deceleration time or connect a braking resistor (or Braking Resistor Unit). Adjust the voltage to meet specifications.

UV1 - DC Bus Low Voltage Error
The DC voltage in the main circuit dropped below the low voltage detection level (L2-05):

    200V class: Approximately 190V
    400V class: Approximately 380V

This error can occur due to:
    A phase loss in the input power supply.
    A momentary power loss.
    Loose wiring at the input power supply terminals.
    Large voltage fluctuations in the input power supply.
Solution: Fix the issue and then reset the fault.

UV2 - Control Power Low Voltage Error
The control power supply voltage dropped.

Solution: Turn the power supply off and on again. If the problem persists, replace the inverter.

UV3 - Surge Suppressor Circuit Error
An error occurred in the surge suppressor (inrush prevention) circuit.

Solution: Turn the power supply off and on again. If the problem persists, replace the inverter.

PF - Input Phase Loss Error
The DC voltage in the main circuit fluctuates abnormally (not during regeneration). This error is detected when the L8-05 setting is "Active."

This error can occur due to:
    A phase loss in the input power supply.
    A momentary power loss.
    Loose input power supply terminals.
    Large voltage fluctuations in the input power supply.
    Voltage imbalance between the phases.
Solution: Fix the issue and then reset the fault.

LF - Output Phase Loss Error
A phase loss occurred at the inverter output. This error is detected when the L8-07 setting is "Active."

This error can occur due to:
    A break in the output cable.
    A break in the motor windings.
    Loose output terminals.
Solution: Fix the issue and then reset the fault. Also, check if the motor capacity being used is less than 5% of the inverter’s maximum motor capacity.

BUS - Communication Card Error
A communication error was detected on the Communication Option Card while setting the run command or frequency reference.
Solution: Check the communication devices and signals.

E-15 - SI-F/G Communication Error
A communication error was detected when a run command or frequency reference was set via the Communication Option Card, and continuous operation was set for E-15 selection.
Solution: Check the communication signals.

E-10 - SI-F/G CPU Fault
The SI-F/G Option Card became inoperable. There is an issue with the Digital Operator connection.

Solution: Disconnect and reconnect the Digital Operator. If the inverter's control circuit is faulty, replace the inverter.