Omron G7 Fault Codes 2
OC (Overcurrent)
The inverter output current exceeded the overcurrent level (200% of the inverter's rated current).
A short circuit or ground fault occurred at the inverter output. (This could be due to motor burnout, worn insulation, or damaged cables.)
The load is too large, or the acceleration/deceleration time is too short.
A motor with too large a capacity is being used for the inverter.
A magnetic switch opened at the inverter output.
Solution: After fixing the cause, reset the fault.
GF (Ground Fault)
The ground fault current at the inverter output exceeded 50% of the rated output current.
A ground fault occurred at the inverter output. (This may be due to motor burnout, worn insulation, or damaged cables.)
Solution: Fix the cause and reset the fault.
PUF (Main Fuse Blown)
The fuse in the main circuit blew.
The output transistor failed due to a short circuit or ground fault.
Check for a short circuit between the following terminals. A short circuit can damage the output transistor:
B1 (3) ←→ U, V, W
Solution: After correcting the cause, replace the inverter.
OV (Overvoltage)
The main circuit DC voltage exceeded the overvoltage level:
200V class: Approximately 410V
400V class: Approximately 820V
The deceleration time is too short, and the regenerative energy from the motor is too large.
The power supply voltage is too high.
Solution: Increase the deceleration time or connect a braking resistor (or Braking Resistor Unit). Adjust the voltage to meet specifications.
UV1 - DC Bus Low Voltage Error
The DC voltage in the main circuit dropped below the low voltage detection level (L2-05):
200V class: Approximately 190V
400V class: Approximately 380V
This error can occur due to:
A phase loss in the input power supply.
A momentary power loss.
Loose wiring at the input power supply terminals.
Large voltage fluctuations in the input power supply.
Solution: Fix the issue and then reset the fault.
UV2 - Control Power Low Voltage Error
The control power supply voltage dropped.
Solution: Turn the power supply off and on again. If the problem persists, replace the inverter.
UV3 - Surge Suppressor Circuit Error
An error occurred in the surge suppressor (inrush prevention) circuit.
Solution: Turn the power supply off and on again. If the problem persists, replace the inverter.
PF - Input Phase Loss Error
The DC voltage in the main circuit fluctuates abnormally (not during regeneration). This error is detected when the L8-05 setting is "Active."
This error can occur due to:
A phase loss in the input power supply.
A momentary power loss.
Loose input power supply terminals.
Large voltage fluctuations in the input power supply.
Voltage imbalance between the phases.
Solution: Fix the issue and then reset the fault.
LF - Output Phase Loss Error
A phase loss occurred at the inverter output. This error is detected when the L8-07 setting is "Active."
This error can occur due to:
A break in the output cable.
A break in the motor windings.
Loose output terminals.
Solution: Fix the issue and then reset the fault. Also, check if the motor capacity being used is less than 5% of the inverter’s maximum motor capacity.
BUS - Communication Card Error
A communication error was detected on the Communication Option Card while setting the run command or frequency reference.
Solution: Check the communication devices and signals.
E-15 - SI-F/G Communication Error
A communication error was detected when a run command or frequency reference was set via the Communication Option Card, and continuous operation was set for E-15 selection.
Solution: Check the communication signals.
E-10 - SI-F/G CPU Fault
The SI-F/G Option Card became inoperable. There is an issue with the Digital Operator connection.
Solution: Disconnect and reconnect the Digital Operator. If the inverter's control circuit is faulty, replace the inverter.