Omron F7 fault codes

   OC (Overcurrent):
+ Meaning: The inverter output current exceeded the overcurrent detection level (200% of the nominal current).
+ Possible Causes: A short circuit or grounding fault in the inverter output (which may be due to motor burnout, insulation wear, or cable damage), excessive load, or too short acceleration/deceleration time, using a motor not suitable for the inverter, or activating a magnetic contactor on the inverter output.
+ Corrective Actions: After correcting the cause of the fault, reset the error. Ensure there is no short circuit or grounding fault in the inverter output before turning the power back on.

   GF (Ground Fault):
+ Meaning: The ground fault current in the inverter output exceeded approximately 50% of the inverter's nominal output current.
+ Possible Causes: Grounding fault in the inverter output (which may be due to motor burnout, insulation wear, or cable damage).
+ Corrective Actions: After correcting the cause of the fault, reset the error. Ensure there is no short circuit or grounding fault in the inverter output before turning the power back on.

   PUF (Fuse Blown):
+ Meaning: The main circuit fuse has blown.
+ Possible Causes: Failure of the output transistor due to a short circuit or grounding fault in the inverter output.
+ Corrective Actions: After correcting the cause, replace the inverter.

   Ou (Main Circuit Overvoltage):
+ Meaning: The main circuit DC voltage exceeded the overvoltage detection level.
+ Possible Causes: The deceleration time is too short, and the motor's regenerative energy is too high.
+ Corrective Actions: Increase the deceleration time or connect a braking resistor. Check and correct the motor's grounding fault.

   Uu1/Uu2/Uu3 (Main Circuit Undervoltage, Control Power Error, Current Limiting Circuit Error):
+ Meaning: The main circuit DC voltage fell below the undervoltage detection level, the control power supply voltage dropped, or the main circuit magnetic contactor did not respond.
+ Possible Causes: An open phase in the input power supply, momentary power loss, loose terminals in the input power supply, voltage fluctuations in the input power supply, or the magnetic contactor in the control circuit being released.
+ Corrective Actions: After correcting the cause, reset the error. Improve the power supply environment. Replace the inverter if necessary.

   PF (Main Circuit Voltage Error):
+ Meaning: The main circuit DC voltage is fluctuating abnormally (not during regeneration).
+ Possible Causes: An open phase in the input power supply, momentary power loss, loose terminals in the input power supply, voltage fluctuations in the input power supply.
+ Corrective Actions: After correcting the cause, reset the error.

   LF (Output Open Phase):
+ Meaning: An open phase occurred in the inverter output.
+ Possible Causes: Broken wire in the output cable, broken wire in the motor winding, or loose output terminals.
+ Corrective Actions: After correcting the cause, reset the error. Check the motor and inverter capacity.

   oH/oH1 (Cooling Fin Overheating):
+ Meaning: The temperature of the inverter's cooling fins exceeded the set level or 100°C.
+ Possible Causes: The ambient temperature is too high, a heat source is nearby, or the inverter's cooling fan has stopped.
+ Corrective Actions: Install a cooling unit, remove the heat source, or replace the cooling fan.

   Fan (Inverter Cooling Fan Error):
+ Meaning: The inverter's cooling fan stopped, or the heat sink is blocked.
+ Possible Causes: The inverter's cooling fan has stopped, or the heat sink is blocked.
+ Corrective Actions: Replace the cooling fan, clean the heat sink.

   oH3/oH4 (Motor Overheating Alarm/Error):
+ Meaning: The motor has overheated.
+ Possible Causes: Excessive load, too short acceleration/deceleration and cycle times, or inappropriate V/f characteristics.
+ Corrective Actions: Check the load size, acceleration/deceleration and cycle times. Verify the V/f characteristics. Check the motor temperature input and the motor's nominal current setting.

   rH/rr (Installed Brake Resistor Overheating/Internal Brake Transistor Error):
+ Meaning: The brake resistor overheated, or the brake transistor is not functioning properly.
+ Possible Causes: Overheating of the brake resistor, damage to the brake transistor.
+ Corrective Actions: Reduce the load, increase the deceleration time, or reduce the motor speed. Power cycle the unit. Replace the inverter if necessary.