Omron E7 Fault codes 4
CPF21 (Communications Option Card Self Diagnostic Error)
Meaning: An error occurred during the self-diagnostic process of the communication option card.
Possible Causes: The communication option card may be faulty.
Corrective Actions: Replace the option card.
CPF22 (Communications Option Card Model Code Error)
Meaning: There is an error with the model code of the communication option card.
Possible Causes: The communication option card may be faulty.
Corrective Actions: Replace the option card.
CPF23 (Communications Option Card DPRAM Error)
Meaning: An error occurred with the DPRAM of the communication option card.
Possible Causes: The communication option card may be faulty.
Corrective Actions: Replace the option card.
Errors During Autotuning:
Er-01 (Motor Data Error)
Meaning: There is an error with the data entered for autotuning.
Possible Causes:
+ There may be an error in the input data.
+ The relationship between motor power and the rated current of the motor may be incorrect.
Corrective Actions:
+ Check the input data.
+ Check the inverter and motor capacity.
+ Check the motor's rated current.
Er-02 (Alarm)
Meaning: A minor error occurred during autotuning.
Possible Causes:
+ There may be an issue with the input data or cables.
Corrective Actions:
+ Check the input data.
+ Check the cables and machine.
Er-03 (STOP Key Input)
Meaning: The STOP key was pressed to cancel autotuning.
Possible Causes: The stop command was mistakenly given.
Corrective Actions: Check the load.
Er-04 (Line-to-line Resistance Error)
Meaning: Autotuning was not completed within the specified time.
Possible Causes:
+ The results of the autotuning exceeded the set range for the user parameter.
Corrective Actions:
+ Check the input data.
+ Check the motor cables.
+ If the motor is connected to the machine, disconnect it.
End3 (Rated Current Setting Alarm)
Meaning: The rated current setting is too high.
Corrective Actions: Check the input data (especially the motor's rated current).
oPE09 (PI Control Selection Error)
Meaning: Several settings have been made simultaneously.
Possible Causes:
+ b5-01 (PI Control Mode Selection) is set to a value other than zero.
+ b5-15 (PI Sleep Function Operating Level) is set to a value other than zero.
+ b1-03 (Stopping Method Selection) is set to 2 or 3.
Corrective Actions: Check these settings and adjust them if necessary.
oPE10 (V/f Data Setting Error)
Meaning: Parameters E1-04, E1-06, E1-07, and E1-09 do not meet certain conditions.
Conditions:
+ E1-04 (FMAX) ≥ E1-06 (FA) ≥ E1-07 (FB) ≥ E1-09 (FMIN)
+ E3-02 (FMAX) ≥ E3-04 (FA) ≥ E3-05 (FB) ≥ E3-07 (FMIN)
Corrective Actions: Verify that these parameters are set correctly.
oPE11 (Parameter Setting Error)
Meaning: There is a parameter setting error.
Possible Causes:
+ C6-05 (Carrier Frequency Gain) > 6 and C6-03 (Carrier Frequency Upper Limit) < C6-04 (Carrier Frequency Lower Limit).
+ Upper/lower limit error between C6-03 and C6-04.
Corrective Actions: Check the parameters and ensure correct limits are set.
Err (EEPROM Write Error)
Meaning: A verification error occurred while writing to the EEPROM.
Corrective Actions:
+ Try turning the power supply off and on again.
+ Try resetting the parameters.
oPE01 (Incorrect Inverter Capacity Setting)
Meaning: The inverter capacity setting does not match the device.
Possible Causes: An incorrect capacity setting has been made.
Corrective Actions: Check parameter o2-04 and set the correct capacity.
oPE02 (Parameter Setting Range Error)
Meaning: The parameter setting is outside the valid range.
Possible Causes: The set parameter is invalid.
Corrective Actions: Ensure that the parameters are within the valid setting range.
oPE03 (Multi-function Input Selection Error)
Meaning: An error has been made in the multi-function input settings (H1-01 to H1-05).
Possible Causes:
+ The same setting has been selected for more than one multi-function input.
+ Up/down commands have been selected separately (they should be used together).
+ Up/down commands (10 and 11) and Acceleration/Deceleration Ramp (A) have been selected at the same time.
+ Speed Search 1 (61) and Speed Search 2 (62) have been selected at the same time.
+ External Base Block NO (8) and External Base Block NC (9) have been selected at the same time.
+ PI control (b5-01) was activated when up/down commands (10 and 11) were selected.
+ Emergency stop commands NO and NC were selected at the same time.
Corrective Actions: Configure the multi-function input settings correctly.
oPE05 (Option Card Selection Error)
Meaning: An option card has been selected as the frequency reference source, but the card is not connected.
Possible Causes: The card is not connected or incorrectly selected.
Corrective Actions: Connect the option card or make the correct selection.
oPE09 (PI Control Selection Error)
Meaning: Several settings have been made simultaneously, which conflict with each other.
Possible Causes:
+ b5-01 (PI Control Mode Selection) is set to a value other than zero.
+ b5-15 (PI Sleep Function Operating Level) is set to a value other than zero.
+ b1-03 (Stopping Method Selection) is set to 2 or 3.
Corrective Actions: Check these settings and adjust them to ensure there are no conflicts.