Omron A1000 fault codes 3

oC: Overcurrent 

The overcurrent alarm is triggered when the output current exceeds the maximum allowed limit. This can be caused by a short circuit or a fault in the system.
These are potential remedies if the motor has been damaged due to overheating or damage to the motor insulation. To check the insulation resistance, you can use an insulation tester to measure the resistance between the motor's windings and ground. If the insulation resistance is low, it is an indication of damaged insulation and the motor should be replaced.

These are potential remedies if a motor cable has shorted out or there is a grounding problem. You can check the motor cables for any signs of damage or wear and tear. If a short circuit is detected, it should be removed and the drive should be powered back up. You can also check the resistance between the motor cables and the ground terminal to see if there is a grounding issue. If there is damage to the cables, they should be replaced.

These are potential remedies if the load on the motor is too heavy. To start, you can measure the current flowing into the motor to determine if it exceeds the rated current of the drive. If it does, it may be necessary to replace the drive with a larger capacity unit. You should also determine if there are sudden fluctuations in the current level, as these can indicate that the load is too heavy for the drive. To avoid these fluctuations, you may need to reduce the load or switch to a larger drive.

These are potential remedies if the acceleration or deceleration times are too short. To calculate the torque needed during acceleration, you need to consider the load inertia and the specified acceleration time. If the current drive is not able to provide the right amount of torque, you can try the following solutions:

Increase the acceleration time.
Modify the S-curve characteristics to make the acceleration or deceleration smoother.
Increase the capacity of the drive by choosing a larger unit.

These are potential remedies if the drive is attempting to operate a specialized motor or a motor that is larger than the maximum size allowed. To start, you should check the capacity rating of the motor. It's important to ensure that the rated capacity of the drive is equal to or greater than the capacity rating found on the motor plate. If the drive's capacity is not sufficient, you may need to choose a larger drive to properly operate the motor.


This issue can occur if the magnetic contactor (MC) on the output side of the drive turns on or off unexpectedly. To prevent this from happening, you should set up the operation sequence so that the MC is not tripped while the drive is outputting power. This can be done by adjusting the timing or control signals for the MC to ensure that it does not interfere with the operation of the drive.

These are potential remedies if the V/f setting is not operating as expected. The V/f setting determines the relationship between the voltage and frequency applied to the motor. To ensure that the V/f setting is working correctly, you should:

Check the ratios between the voltage and frequency to ensure that they are set appropriately.
Set the parameters E1-04 through E1-10 (or E3-04 through E3-10 for motor 2) to the correct values.
If the voltage is too high relative to the frequency, you may need to lower the voltage to restore the correct V/f ratio.

These are potential remedies if there is excessive torque compensation. Torque compensation is used to correct for variations in the load on the motor and maintain a constant speed. To resolve excessive torque compensation:

Check the amount of torque compensation being applied to the motor.
Reduce the torque compensation gain (C4-01) until there is no speed loss and the desired performance is achieved. It's important to find a balance between maintaining the correct speed and avoiding overcompensation that can cause instability or reduced performance.


These are potential remedies if the drive is failing to operate properly due to noise interference. To resolve the issue:

Review the possible solutions for handling noise interference and implement any relevant solutions.
Check the control circuit lines, main circuit lines, and ground wiring to ensure that they are properly shielded and grounded. Improper shielding or grounding can allow external noise to interfere with the operation of the drive.
It's important to carefully review the section on handling noise interference and implement any necessary measures to reduce or eliminate noise in the drive system.

These are potential remedies if the overexcitation gain is set too high. The overexcitation gain affects the level of magnetic field generated by the motor, which in turn affects the performance of the drive. To resolve the issue:

Check if the fault occurs simultaneously with the overexcitation function operation. This may provide insight into the root cause of the issue.
Consider the motor flux saturation and reduce the value of n3-13 (Overexcitation Deceleration) if necessary. Setting the overexcitation gain too high can cause the motor to become saturated, reducing its performance and potentially causing the drive to fail. By reducing the overexcitation gain, you can ensure that the motor operates within its safe operating limits and avoid these issues.

These are potential remedies if a run command was applied while the motor was coasting. When the motor is coasting, it is in a state of free rotation and may not respond immediately to a run command. To resolve this issue:

Enable Speed Search at start (b3-01 = 1). Speed Search is a function that automatically synchronizes the drive and motor before starting the motor, which can prevent issues like this from occurring.
Program the Speed Search command input through one of the multi-function contact input terminals (H1-xx = 61 or 62). This allows you to initiate the Speed Search function through an external input, which can help ensure that the drive and motor are properly synchronized before starting the motor.
By implementing these remedies, you can avoid issues with the drive failing to operate properly when a run command is applied while the motor is coasting.


These are the potential remedies if the wrong motor code has been entered for PM Open Loop Vector or if the motor data is incorrect. The motor code and data are important parameters that affect the performance and operation of the drive. To resolve this issue:

Enter the correct motor code to E5-01. If the drive is specifically designed to work with Yaskawa motors, make sure that you enter the correct motor code for the specific Yaskawa motor you are using.
If a non-Yaskawa PM motor is used, enter "FFFF" to E5-01. This tells the drive that the motor is not a Yaskawa motor and allows it to use default parameters for non-Yaskawa motors.
Set the correct motor data to the E5-xx parameters or perform Auto-Tuning. Auto-Tuning is a feature that allows the drive to automatically set the motor data based on the characteristics of the motor being used. This can help ensure that the drive is properly configured for the motor, improving its performance and reducing the risk of issues like this from occurring.

These are potential remedies if the motor control method and the motor do not match. The motor control method and the motor used must match in order for the drive to function correctly and avoid issues:

Check which motor control method the drive is set to (A1-02). This parameter determines the type of motor control used by the drive.
For IM (Induction Motors), set A1-02 to "0", "1", "2", or "3". These values correspond to different types of induction motor control methods.
For PM (Permanent Magnet Motors), set A1-02 to "5", "6", or "7". These values correspond to different types of permanent magnet motor control methods.
By ensuring that the drive's control method matches the type of motor being used, you can ensure proper operation and avoid issues with the drive and motor.

This is a potential remedy if the drive's rated output current is too small.
If the drive's rated output current is smaller than the required current to power the connected motor, the drive may not be able to produce enough power to run the motor properly, which can lead to issues such as underperformance, stalling, or damage to the motor or drive.
In this case, the remedy is to use a larger drive that has a higher rated output current. This will ensure that the drive is able to provide enough power to the motor, avoiding issues and allowing for proper operation.