Omron A1000 fault codes 11

oPE01 Drive Capacity Setting Fault , to match the actual capacity of the drive. Ensure that the correct drive model has been selected in o2-04. If necessary, replace the drive with one of the correct capacity.

oPE02: Parameter Setting Range Error. Check the values of parameters set in U1-18 to ensure they are within the possible setting range. If any parameters are found to be outside the range, adjust them to the proper values. It is important to resolve any other errors that may be occurring at the same time before addressing this error, as other errors may take precedence over oPE02.

oPE03 Multi-Function Input Selection Error  occurs when there is a contradictory setting assigned to multi-function contact inputs H1-01 to H1-08. The possible causes for this error are:

    The same function is assigned to two multi-function inputs (excluding "Not used" and "External Fault").
    The Up command was set but the Down command was not, or vice versa.
    The Up 2 command was set but the Down 2 command was not, or vice versa.
    Run/Stop command for a 2-wire sequence was set, but Forward/Reverse command was not.
    "Drive Enable" is set to multi-function input S1 or S2.

Possible solutions for this error include:

    Ensure all multi-function inputs are assigned to different functions.
    Re-enter the multi-function settings to avoid this error.
    Correctly set functions that need to be enabled in combination with other functions.

This error message is indicating that two conflicting functions (Up/Down Command and PID control) have been assigned to the multi-function input terminals at the same time. To resolve the issue, either disable the PID control by setting b5-01 to 0 or disable the Up/Down command by setting the appropriate parameter to an appropriate value.

oPE03 Multi-Function Input Selection Error occurs when a contradictory setting is assigned to multi-function contact inputs H1-01 to H1-08.
The following are possible causes and solutions for this error:

    The same function is assigned to two multi-function inputs. Ensure all multi-function inputs are assigned to different functions and re-enter the multi-function settings.
    The Up command was set but the Down command was not, or vice versa. Correctly set functions that need to be enabled in combination with other functions.
    The Up 2 command was set but the Down 2 command was not, or vice versa.
    The Run/Stop command for a 2-wire sequence was set, but the Forward/Reverse command was not.
    "Drive Enable" is set to multi-function input S1 or S2. Correctly set functions that need to be enabled in combination with other functions.
    Two of the following functions are set at the same time:
        Up/Down Command (10 vs. 11)
        Up 2/Down 2 Command (75 vs. 76)
        Hold Accel/Decel Stop (A)
        Analog Frequency Reference Sample/Hold (1E)
        Offset Frequency 1, 2, 3 Calculations (44, 45, 46)
        Check if contradictory settings have been assigned to the multi-function input terminals and correct any setting errors.

Check and correct the settings assigned to the multi-function input terminals to ensure they do not conflict with each other. If External Search Command 1 and External Search Command 2 (61 vs. 62) are both enabled, disable one of them. If Fast Stop N.O. and Fast Stop N.C. (15 vs. 17) are both selected, choose only one of them. If KEB for Momentary Power Loss and High Slip Braking (65, 66, 7A, 7B vs. 68) are both enabled, disable one of them. If Motor Switch Command and Accel/Decel Time 2 (16 vs. 1A) are both enabled, disable one of them. If KEB Command 1 and KEB Command 2 (65, 66 vs. 7A, 7B) are both enabled, disable one of them. If FWD Run Command (or REV) and FWD/REV Run Command (2-wire) (40, 41 vs. 42, 43) are both enabled, disable one of them. If External DB Command and Drive Enable (60 vs. 6A) are both enabled, disable one of them. If Motor Switch Command and Up 2/Down 2 Command (16 vs. 75, 76) are both enabled, disable one of them.

If b1-15 = 4 (Pulse Train Input) and the pulse train input selection is not set for the frequency reference (H6-01 > 0), set H6-01 to a value greater than 0. If b1-15 or b1-16 set to 3 but no option card is connected, either connect an option card or change the setting to a different value. If H3-02 or H3-10 are set to 0 (Frequency Bias) and b1-15 = 1 (Analog Input), change H3-02 or H3-10 to a different value.

If H2-†† = 38 (Drive Enabled) but H1-†† is not set to 6A (Drive Enable), set H1-†† to 6A. If H1-†† = 7E (Direction Detection) but H6-01 is not set to 3 (for V/f Control with PG using terminal RP as speed feedback input),

oPE04: Terminal Board Mismatch Error. To resolve the issue of oPE04 Initialization required, first check if the drive, control board, or terminal board has been replaced. If yes, it is possible that the parameter settings between the control board and the terminal board no longer match. To load the stored parameter settings from the terminal board to the drive, set A1-03 to 5550. After drive replacement, initialize the parameters by setting A1-03 to 1110 or 2220.
oPE05: Run Command Selection Error. The Run command and frequency reference source selection error (oPE05) can be caused by a number of different issues. The possible solutions to this error include:

    Reconnecting the input option card to the drive if the frequency reference or run command has been assigned to an option card, but no input option card is connected.
    Setting H6-01 to 0 if the frequency reference is assigned to the pulse train input, but terminal RP is not set for frequency reference input.
    Setting the input data to 16-bit (F3-03 = 2) if the digital card input is set for BCD special for a 5-digit input (F3-01 = 6), but the data length is set for 8-bit or 12-bit.
    Making sure parameters are set properly if the source of frequency reference setting is assigned to an option card and the action for the analog card is set for separate terminal input.

oPE06: Control Method Selection Error.  A control mode has been selected that requires a PG encoder to be connected to the drive, but no encoder is connected (A1-02 = 2 or 4).
• Connect a PG encoder to the drive.
• Correct the value set to A1-02.
An improper control method has been selected.
• Check the manual for the appropriate control method and set the correct value for A1-02.

oPE07: Multi-Function Analog Input Selection Error  . Multi-Function Analog Input Selection Error. A contradictory setting is assigned to multi-function analog inputs H3-02, H3-06, or H3-10 and PID functions conflict.

Possible Solutions:

    Change the settings of H3-02, H3-06, and H3-10 so that functions do not conflict.
    Make sure both 0 (frequency reference bias) and F (not used) can be set to H3-02, H3-06, and H3-10 at the same time.
    Disable one of the conflicting PID selections (e.g. H3-02, H3-06, or H3-10 = B and H6-01 = 1, H3-02, H3-06, or H3-10 = C and H6-01 = 2, H3-02, H3-06, or H3-10 = C and b5-18 = 1, or H6-01 = 2 and b5-18 = 1).


oPE08 Parameter Selection Error occurs when a function is set that is not valid for the selected motor control method. Possible solutions include:

    Check the motor control method and the functions available.
    In Open Loop Vector Control, make sure that n2-02 is less than n2-03.
    In Open Loop Vector Control, make sure that C4-02 is less than C4-06.
    In OLV/PM, set the correct motor code (E5-01), and set E5-03 to 0 and either E5-09 or E5-24 to the correct value, the other to 0.
    In using a PG option card, make sure that b1-14 (Phase Order Selection) is not set to 1 (Switch phase order).
    In AOLV/PM, make sure that the minimum frequency (E1-09) is not set lower than 1/20 of the base frequency setting.
    Use U1-18 to find parameters set outside the specified range.

Note: Other errors will take precedence over oPE08 if multiple errors occur at the same time.
oPE09: PID Control Selection Error.     If b5-15 (PID Sleep Function Operation Level) is not 0 and the stopping method is set to either DC Injection Braking or coast to stop with a timer (b1-03 = 2 or 3), set b5-15 to another value besides 0 and change the stopping method to coast to stop or ramp to stop (b1-03 = 0 or 1).
    If PID control is set to b5-01 = 1 or 2 and the lower limit for the frequency reference (d2-02) is not 0 while reverse output is enabled (b5-11 = 1), correct the lower limit for the frequency reference.
    If PID control is set to b5-01 = 3 or 4 and the lower limit for the frequency reference (d2-01) is not 0, correct the lower limit for the frequency reference.

oPE10: V/f Data Setting Error. The following setting errors have occurred where:
• E1-04 is greater than or equal to E1-06, E1-06 is greater than or equal to E1-07, E1-07 is
greater than or equal to E1-09, or E1-09 is greater than or equal to E1-11.
• E3-04 is greater than or equal to E3-06, E3-06 is greater than or equal to E3-07, E3-07 is
greater than or equal to E3-09, or E3-09 is greater than or equal to E3-11.
Cause Possible Solutions
— Correct the settings for E1-04, E1-06, E1-07, E1-09, and E1-11 (for motor 2, correct E3-04,
E3-06, E3-07, E3-09, and E3-11).

oPE11: Carrier Frequency Setting Error. Correct the setting for the carrier frequency.
Cause Possible Solutions
The following simultaneous contradictory settings: C6-05 is greater than 6 and C6-04 is
greater than C6-03 (carrier frequency lower limit is greater than the upper limit). If C6-05 is
less than or equal to 6, the drive operates at C6-03. Correct the parameter settings.
Upper and lower limits between C6-02 and C6-05 contradict each other.

oPE13: Pulse Train Monitor Selection Error. Incorrect setting of monitor selection for pulse train (H6-06).
Cause Possible Solutions
Scaling for the pulse train monitor is set to 0 (H6-07 = 0) while H6-06 is not set to 101, 102,
105, or 116. Change scaling for the pulse train monitor or set H6-06 to 101, 102, 105, or 116

oPE15: Torque Control Setting Error. Parameters settings that are not allowed in combination with Torque Control have been set.
Cause Possible Solutions
Torque Control in enabled (d5-01 = 1) while the Speed/Torque Control switch function is
assigned to a digital input (H1-†† = 71).
Correct the parameter settings.
Either Torque Control is enabled by d5-01 = 1, the or Speed/Torque Control switch is assigned
to a digital input H1-†† = 71, while at the same time:
• Feed Forward is enabled (n5-01 = 1), or
• Droop Control is enabled (b7-01 ≠ 0), or
• Intelligent Stall Prevention or Intelligent Stall Prevention 2 is enabled (L3-04 = 2 or 5), or
• A digital input is set for the power KEB 1 or KEB 2 (H1-†† = 7A or 7B)

oPE16: Energy Saving Constants Error. Cause Possible Solutions
In AOLV/PM the automatically calculated energy saving coefficients are out of the allowable
range. Check and correct the motor data in E5 parameters.

oPE18: Online Tuning Parameter Setting Error. Parameters that control Online Tuning are not set correctly.
Cause Possible Solutions
One of the following setting errors has occurred while Online Tuning is enabled in OLV (A1-
02 = 2):
• E2-02 has been set below 30% of the original default value
• E2-06 has been set below 50% of the original default value
• E2-03 = 0
Make sure E2-02, E2-03, and E2-06 are set the correct values.