Omron A1000 fault codes 9

UL3 Undertorque Detection 1
This error message is indicating that the current in the system has dropped below the minimum set value for torque detection, and has remained at this low level for longer than the allowed time. The cause of this issue could be that the parameters for torque detection (L6-02 and L6-03) are not set correctly for the current load, or there may be a problem with the machine itself. To resolve the issue, it is recommended to check the settings of the parameters and inspect the machine for any faults.

UL4 Undertorque Detection 2

This error message is indicating that the current in the system has dropped below the minimum set value for torque detection, and has remained at this low level for longer than the allowed time. The cause of this issue could be that the parameters for torque detection (L6-05 and L6-06) are not set correctly for the current load, or there may be a problem with the machine itself. To resolve the issue, it is recommended to check the settings of the parameters and inspect the machine for any faults.

UL5 Mechanical Weakening Detection 2
This error message is indicating that the conditions of the system have matched the conditions set for mechanical weakening detection (L6-08). The cause of this issue is likely that an undertorque was detected and it matched the conditions set for mechanical loss detection. To resolve the issue, it is recommended to check the load side for any problems.

Uv1 Undervoltage

This error message "Uv1 DC Bus Undervoltage" indicates that while the drive was stopped, the voltage in the DC bus fell below the undervoltage detection level (L2-05) and remained below that level for longer than the time set in L2-02. The possible causes of this issue include a loss of input power phase, loose wiring terminals, problems with the voltage from the drive input power, an interruption in power supply, worn capacitors in the main circuit, a damaged relay or contactor in the soft-charge bypass circuit, etc.

To resolve the issue, possible solutions include checking and correcting the wiring, tightening loose terminals, checking the voltage and correcting it to be within the specifications, checking the performance life of the capacitors and the soft-charge bypass, replacing the control board or the entire drive if necessary, etc. For more detailed instructions, refer to the manual or contact Yaskawa or a local sales representative.

Undervoltage in the DC bus can cause significant problems for the drive and the overall system. The undervoltage detection level (L2-05) is set to a specific value, and if the voltage falls below that level for longer than the time set in L2-02, the Uv1 error message will be triggered. The possible causes of this issue are various and could range from simple wiring problems to more complex issues such as worn capacitors or a damaged relay in the soft-charge bypass circuit.

To resolve the issue, it is important to thoroughly check and troubleshoot each potential cause. Some possible solutions include checking the wiring, tightening loose terminals, correcting the voltage to be within the specifications, checking the performance life of the capacitors and the soft-charge bypass, and replacing the control board or the entire drive if necessary. It is recommended to consult the manual or a local sales representative for detailed instructions on how to perform these steps.

In summary, Uv1 DC Bus Undervoltage is a serious issue that should be addressed promptly to ensure proper operation of the drive and the overall system.

Uv2 Control Power Supply Undervoltage .

This error code (Uv2) indicates that the voltage level in the control power supply is too low to operate the drive. This could have various causes, such as:

    Changing the L2-02 parameter from its default value without installing a Momentary Power Loss Ride-Thru unit (for certain models)
    Damaged control power supply wiring
    Damaged internal circuitry in the drive

To troubleshoot this error, you can try the following steps:

    Correct the setting of the L2-02 parameter or install the Momentary Power Loss Ride-Thru unit.
    Cycle the power to the drive and check if the error reoccurs.
    If the problem persists, replace the control board, the entire drive, or the control power supply if necessary.

If you need further assistance, you can contact Yaskawa or your nearest sales representative.


Uv3 Soft Charge Circuit Fault. 

The relay or contactor on the soft-charge bypass circuit is damaged.
• Cycle power to the drive and check if the fault reoccurs.
• If the problem persists, replace either the control board or the entire drive. Contact Yaskawa or your nearest sales representative for instructions on replacing the control board.
• Check monitor U4-06 for the performance life of the soft-charge bypass.
• Replace either the control board or the entire drive if U4-06 exceeds 90%. Contact Yaskawa or your nearest sales representative for instructions on replacing the control board.


EF0 Option Card External Fault: It is an error indicating that there is an external fault condition present in the system.

Possible Causes:
    An external fault was received from the PLC with other than F6-03 = 3 “alarm only” (the drive continued to run after external fault).
Possible Solutions:
    To resolve the issue, remove the cause of the external fault.
    Disconnect the external fault input from the PLC.
    Check the PLC program and correct any problems if found.
Note: Contact Yaskawa or your nearest sales representative for additional support and guidance.

EF1 External Fault (input terminal S1)
External fault at multi-function input terminal S1.
EF2 External Fault (input terminal S2)
External fault at multi-function input terminal S2.
EF3 External Fault (input terminal S3)
External fault at multi-function input terminal S3.
EF4 External Fault (input terminal S4)
External fault at multi-function input terminal S4.
EF5 External Fault (input terminal S5)
External fault at multi-function input terminal S5.
EF6 External Fault (input terminal S6)
External fault at multi-function input terminal S6.
EF7 External Fault (input terminal S7)
External fault at multi-function input terminal S7
EF8 External Fault (input terminal S8)
External fault at multi-function input terminal S8
Cause Possible Solution
An external device has tripped an alarm function. Remove the cause of the external fault and reset the fault.
Wiring is incorrect. • Ensure the signal lines have been connected properly to the terminals assigned for external fault detection (H1-†† = 20 to 2F).
• Reconnect the signal line.
Incorrect setting of multi-function contact inputs. • Check if the any unused terminals are set for H1-†† = 20 to 2F (External Fault).
• Change the terminal setting

FbH Excessive PID Feedback

"FbH Excessive PID Feedback" is an error message indicating that the PID (Proportional Integral Derivative) feedback input is too high for the set level for a longer period of time than specified. The cause could be either incorrect parameter settings, incorrect wiring for PID feedback, or a problem with the feedback sensor. To resolve the issue, check the settings of parameters b5-36 and b5-37, correct the wiring if necessary, and check or replace the sensor if damage is detected.

FbL PID Feedback Loss

The "FbL" fault refers to an issue with the PID (proportional-integral-derivative) feedback in a control system. This fault occurs when the programmed settings in parameters b5-12, b5-13, and b5-14 detect that the PID feedback level is below the detection level set in b5-13 for longer than the time set in b5-14.

The possible causes for this fault include:

  • Incorrect parameter settings for b5-13 and b5-14
  • Wiring problems for the PID feedback
  • Issues with the feedback sensor, such as damage or malfunction

To resolve this fault, check the settings of parameters b5-13 and b5-14 and ensure that they are set appropriately. If the wiring for the PID feedback is incorrect, correct it. If there is an issue with the feedback sensor, check the sensor on the controller side and replace it if necessary.

Hbb Safe Disable Signal Input

This error occurs when both Safe Disable Input channels (H1 and H2) are open or not receiving the correct signal. Possible solutions include:

    Check the signal status at the input terminals H1 and H2.
    Check the Sink/Source Selection for the digital inputs.
    If the Safe Disable function is not utilized, check if the terminals H1-HC and H2-HC are linked.
    If the problem persists, replace either the control board or the entire drive. Contact Yaskawa or the nearest sales representative for instructions on replacing the control board.

 HbbF Safe Disable Signal Input indicates that one of the two Safe Disable Inputs (H1 and H2) is open while the other one is closed. Possible causes and solutions for this fault are:

    The signals to the Safe Disable inputs are incorrect or the wiring is incorrect.
        Check the signal status at the input terminals H1 and H2.
        If the Safe Disable function is not utilized, make sure the terminals H1-HC and H2-HC are linked.
    One of the Safe Disable channels is faulty.
        Replace either the control board or the entire drive.
        For instructions on replacing the control board, contact Yaskawa or your nearest sales representative.

HCA Current Alarm The "HCA Current Alarm: Drive current exceeded overcurrent warning level" means that the drive is drawing more current than it is rated for, which is indicated by a value of 150% of the rated current. This can occur due to several reasons such as a heavy load, short acceleration and deceleration times, using a motor with capacity greater than the drive's maximum allowable capacity, or a momentary power loss during speed search. Possible solutions include reducing the load, increasing acceleration and deceleration times, using a motor within the allowable capacity range, or ignoring the alarm if it occurs briefly during a fault restart.