Omron A1000 fault codes 7
SvE: Zero-Servo Fault
SvE Zero Servo Fault
Position deviation during zero servo.
Cause Possible Solution
Torque limit is set too low. Set the torque limit to an appropriate value using parameters L7-01 to L7-04.
Excessive load torque. Reduce the amount of load torque.
Noise interference along PG encoder wiring. Check the PG signal for noise interference
STo: Pull-Out Detection
STo Motor Pull Out or Step Out Detection
Motor pull out or step out has occurred. Motor has exceeded its pull-out torque.
Cause Possible Solution
The wrong motor code is set (Yaskawa motors only). • Enter the correct motor code for the PM being used into E5-01.
• For special-purpose motors, enter the correct data to all E5 parameters according to the test report provided for the motor.
Load is too heavy.
• Increase the load inertia for PM motor (n8-55).
• Increase the pull-in current during accel/decel (n8-51).
• Reduce the load.
• Increase the motor or drive capacity.
Load inertia is too heavy. Increase the load inertia for PM motor (n8-55).
Acceleration and deceleration times are too short. • Increase the acceleration and deceleration times (C1-01 through C1-08).
• Increase the S-curve acceleration and deceleration times (C2-01).
Speed response is too slow. Increase the load inertia for PM motor (n8-55)
oPr: Operator Connection Fault
External Digital Operator Connection Fault
• The external operator has been disconnected from the drive.
Note: An oPr fault will occur when all of the following conditions are true:
• Output is interrupted when the operator is disconnected (o2-06 = 1).
• The Run command is assigned to the operator (b1-02 = 0 and LOCAL has been selected).
Cause Possible Solution
External operator is not properly connected to the drive.
• Check the connection between the operator and the drive.
• Replace the cable if damaged.
• Turn off the drive input power and disconnect the operator. Next reconnect the operator and turn the drive input power back on
voF: Output Voltage Detection Fault
Problem detected with the voltage on the output side of the drive.
Cause Possible Solution
Hardware is damaged. Replace either the control board or the entire drive. For instructions on replacing the control board, contact Yaskawa or your nearest sales representa
SEr: Too Many Speed Search RestSEr Too Many Speed Search Restarts
The number of Speed Search restarts exceeded the number set to b3-19.
Cause Possible Solution
Speed Search parameters are set to the wrong values.
• Reduce the detection compensation gain during Speed Search (b3-10).
• Increase the current level when attempting Speed Search (b3-17).
• Increase the detection time during Speed Search (b3-18).
• Repeat Auto-Tuning.
The motor is coasting in the opposite direction of the
Run command. Enable Bi-Directional Speed Search (b3-14 =1) arts
+ Next page >>