oFC00: Option Card Connection Error (CN5-C) oFC00 Option Card Connection Error at Option Port CN5-C
Option compatibility error
Cause Possible Solution
The option card installed into port CN5-C is
incompatible with the drive. Check if the drive supports the option card that you are attempting to instal. Contact Yaskawa for assistance.
A communication option card has been installed in
option port CN5-C. Communication option cards are supported by option port CN5-A only. More than one comm. option cannot be installed.


oFC01: Option Card Fault (CN5-C)  oFC01 Option Card Fault at Option Port CN5-C
Option not properly connected
Cause Possible Solution
The option board connection to port CN5-C is faulty.
• Turn the power off and reconnect the option card.
• Check if the option card is properly plugged into the option port. Make sure the card is fixed properly.
• Try to use the card in another option port (in case of a PG option use port CN5-B). If it works there, replace the drive. If the
error persists (oFA01 or oFb01 occur), replace the option board
oFC02: Option Card Fault (CN5-C)  oFC02 Option Card Fault at Option Port CN5-C
Same type of option card already connected
Cause Possible Solution
An option card of the same type is already installed in
option port CN5-A or CN5-B. Except for PG options, each option card type can only be installed once. Make sure only one type of option card is connected.
An input option card is already installed in option port
CN5-A or CN5-B.
Make sure that a comm. option, a digital input option, or an analog input option is installed. The same type of card cannot be
installed twice.
Three PG option boards are installed. Maximum two PG option boards can be used at the same time. Remove the PG option board installed into option port CN5A

oFC03, oFC11: Option Card Error (CN5-C)

to oFC12 to oFC17: Option Card Connection Error (CN5-C) 

to oFC30 to oFC43: Option Card Fault (CN5-C) 

oFC03 to oFC11
Option card error occurred at option port CN5-C
to oFC12 to oFC17
to oFC30 to oFC43
Cause Possible Solution
Option card or hardware is damaged.
• Cycle power to the drive.
• If the problem continues, replace either the control board or the entire drive. For instructions on replacing the control board,
contact Yaskawa or your nearest sales representanive


Err EEPROM: Write Error  
PF: Input Phase Loss 
Drive input power has an open phase or has a large imbalance of voltage between phases. Detected when L8-05 = 1 (enabled).
Cause Possible Solution
There is phase loss in the drive input power. • Check for wiring errors in the main circuit drive input power.
• Correct the wiring.
There is loose wiring in the drive input power terminals. • Ensure the terminals are tightened properly.
• Apply the tightening torque as specified in this manual. Refer to Wire Gauges and Tightening Torque on page 66
There is excessive fluctuation in the drive input power
voltage.
• Check the voltage from the drive input power.
• Review the possible solutions for stabilizing the drive input power.
There is poor balance between voltage phases. • Stabilize drive input power or disable phase loss detection.
The main circuit capacitors are worn.
• Check the maintenance time for the capacitors (U4-05).
• Replace the capacitor if U4-05 is greater than 90%. For instructions on replacing the capacitor, contact Yaskawa or your nearest sales representative.
Check for anything problems with the drive input power. If drive input power appears normal but the alarm continues to occur, replace either the control board or the entire drive. For instructions on  replacing the control board, contact Yaskawa or your nearest sales representative

PGo: PG Disconnect (for Control Mode with PG)  

PGo PG Disconnect (for any control modes using a PG option card)
No PG pulses are received for longer than the time set to F1-14.
Cause Possible Solution
PG cable is disconnected. Reconnect the cable.
PG cable wiring is wrong. Correct the wiring.
PG has no power. Check the power line to the PG encoder.
PG encoder brake is clamped shut. Ensure the motor brake releases properly
PGoH: PG Hardware Fault (when using PG-X3)  
PGoH PG Hardware Fault (detected when using a PG-X3 option card)
PG cable is not connected properly.
Cause Possible Solution
PG cable is disconnected. Reconnect the cable.


rF: Braking Resistor Fault 
The resistance of the braking resistor being used is too low.
Cause Possible Solution
The proper braking resistor option has not been
installed. Select the braking resistor option so that fits to the drives braking transistor specification.
Regenerative converter, regenerative unit, or braking
unit is being used. Disable the braking transistor protection selection (set L8-55 to 1)


rH: Dynamic Braking Resistor
Braking Resistor Overheat
Braking resistor protection was triggered.
Fault detection is enabled when L8-01 = 1 (disabled as a default).
Cause Possible Solution
Deceleration time is too short and excessive regenerative
energy is flowing back into the drive.
• Check the load, deceleration time, and speed.
• Reduce the load inertia.
• Increase the deceleration times (C1-02, C1-04, C1-06, C1-08, C1-09).
• Replace the dynamic braking option with a larger device that can handle the power that is discharged.
Excessive braking inertia. Recalculate braking load and braking power. Reduce the braking load by adjusting braking resistor settings.
The braking operation duty cycle is too high. Check the braking operation duty cycle. Braking resistor protection for ERF-type braking resistors (L8-01 = 1) allows a braking
duty cycle of maximum 3%.
The proper braking resistor has not been installed. • Check the specifications and conditions for the braking resistor device.
• Select the optimal braking resistor.
Note: The magnitude of the braking load trips the braking resistor overheat alarm, NOT the surface temperature. Using the braking resistor more frequently than it is rated for trips the alarm
even when the braking resistor surface is not very hot.

rr Dynamic Braking Transistor
The built-in dynamic braking transistor failed.
Cause Possible Solution
The braking transistor is damaged. • Cycle power to the drive and check if the fault reoccurs. Refer to Diagnosing and Resetting Faults on page 334.
• Replace either the control board or the entire drive. For instructions on replacing the control board, contact Yaskawa or your
nearest sales representative

oS Overspeed (for Control Mode with PG)
The motor speed feedback exceeded the F1-08 setting.
Cause Possible Solution
Overshoot is occurring. • Increase the settings for C5-01 (Speed Control Proportional Gain 1) and reduce C5-02 (Speed Control Integral Time 1).
• If using a Closed Loop Vector mode, enable Feed Forward and perform Inertia Auto-Tuning.
Incorrect speed feedback scaling if terminal RP is used
as speed feedback input in V/f control.
• Set H6-02 to the value of the speed feedback signal frequency when the motor runs at the maximum speed.
• Adjust the input signal using parameters H6-03 through H6-05.
Incorrect number of PG pulses has been set. • Check and correct parameter F1-01.
Inappropriate parameter settings. Check the setting for the overspeed detection level and the overspeed detection time (F1-08  an 09)