Omron A1000 fault codes 5
oFA00: Option Card Connection Error at Option Port CN5-A
Option compatibility error
Cause:
The option card installed in port CN5-A is not compatible with the drive.
Possible Solution:
Check if the drive supports the option card that is being installed.
If the PG option card is connected to option port CN5-A, note that PG option boards are only supported by option ports CN5-B and CN5-C. Place the PG option card into the correct option port.
Contact Yaskawa for additional assistance.
oFA01: Option Card Error at Option Port CN5-A
Cause: Incorrect connection of the option card
Possible Solution:
Turn off power and reconnect the option card.
Ensure the option card is securely and properly inserted into the option port.
If the option card is not a communication option, try using it in a different option port. If it works, replace the drive. If the error persists (oFb01 or oFC01 appear), replace the option board.
to oFA03 to oFA06: Option Card Error (CN5-A)
oFA10, oFA11:
to oFA12 to oFA17:
to oFA30 to oFA43: Option card or hardware is damaged.
Cause Possible Solution
The option card or hardware is damaged.
• Cycle power to the drive by turning it off and then turning it on again.
• If the issue persists, replace either the control board or the entire drive. For instructions on replacing the control board, contact Yaskawa or a local sales representative for assistance
dEv: Excessive Speed Deviation (for Control Mode with PG)
Cause Possible Solution
The load is too heavy. Reduce the load.
Acceleration and deceleration times are set too short. Increase the acceleration and deceleration times (C1-01 through C1-08).
The load is locked up. Check the machine.
Parameters are not set appropriately. Check the settings of parameters F1-10 and F1-11.
Incorrect speed feedback scaling if terminal RP is used
as speed feedback input in V/f control.
• Set H6-02 to the same value as the speed feedback signal frequency when the motor runs at maximum speed.
• Adjust the speed feedback signal using parameters H6-03 through H6-05.
• Make sure the speed feedback signal frequency does not exceed the maximum input frequency of terminal RP.
Motor brake engaged. Ensure the motor brake releases properly.
oFb00 Option Card Fault at Option Port CN5-B
Option compatibility error
Cause Possible Solution
The option card installed into port CN5-B is
incompatible with the drive. Check if the drive supports the option card that you are attempting to install. Contact Yaskawa for assistance.
A communication option card has been installed in
option port CN5-B. Communication option cards are supported by option port CN5-A only. More than one comm. option cannot be installet.
--------------
oFb01 Option Card Fault at Option Port CN5-B
Option not properly connected
Cause Possible Solution
The option board connection to port CN5-B is faulty.
• Turn the power off and reconnect the option card.
• Check if the option card is properly plugged into the option port. Make sure the card is fixed properly.
• Try to use the card in another option port (in case of a PG option use port CN5-C). If option card still doesn’t work there,
replace the drive. If the error persists (oFA01 or oFC01 occur), replace the option board.
-----------------
oFb02 Option Card Fault at Option Port CN5-B
Same type of option card already connected
Cause Possible Solution
An option card of the same type is already installed in
option port CN5-A. Except for PG options, each option card type can only be installed once. Make sure only one type of option card is connected.
An input option card is already installed in option port
CN5-A.
Make sure that a comm. option, a digital input option, or an analog input option is installed. The same type of card cannot be
installed twice
oFb03, oFb11: Option Card Error (CN5-B)
to oFb12 to oFb17: Option Card Connection Error (CN5-B)
oFb30 to oFb43: Option Card Connection Error (CN5-B)
oFb03 to oFb11
Option card error occurred at Option Port CN5-Bto oFb12 to oFb17
to oFb30 to oFb43
Cause Possible Solution
Option card or hardware is damaged.
• Cycle power to the drive.
• If the problem continues, replace either the control board or the entire drive. For instructions on replacing the control board,
contact Yaskawa or your nearest sales represenative
dv1: Z Pulse Fall Detection The motor turned one full rotation without the Z pulse being detected.
Cause Possible Solution
PG encoder is not connected, not wired properly, or is
damaged.
• Make sure the PG encoder is properly connected and all shielded lines are properly grounded.
• If the problem continues after cycling power, then replace either the PG option card or the PG encoder itself
• Check the wiring between the PG encoder and the control board.
• Make sure the encoder is not damaged and functioning properly.
• If the problem persists, contact Yaskawa or your nearest sales representative for further assistance.
dv2 Z Pulse Noise Fault Detection
The Z pulse is out of phase by more than 5 degrees for the number of times specified in parameter F1-17.
Cause Possible Solution
Noise interference along the PG cable. Separate the PG cable lines from the source of the noise (very possibly drive output wiring).
PG cable is not wired properly. Rewire the PG encoder and make sure all shielded lines are properly grounded.
PG option card or the PG encoder is damaged. If the problem continues after cycling power, then replace either the PG option card or the PG encoder itself
dv3: Inversion Detection Inversion Detection
The torque reference and acceleration are in opposite directions from one another (one is in reverse and the other is forward)
while at the same time the speed reference and actual motor speed differ by over 30% for the number of pulses set to F1-18.
Cause Possible Solution
The Z pulse offset is not set properly to E5-11. Set the value for Δθ to E5-11 as specified on the motor nameplate. Replacing the PG encoder or changing the application so that
the motor rotates in reverse instead requires readjustment of the Z pulse offset.
An external force on the load side has caused the motor
to move.
• Make sure the motor is rotating in the right direction.
• Look for any problems on the load side that might be causing the motor to rotate in the opposite direction.
Noise interference along the PG cable affecting the A or
B pulse. Rewire the PG encoder and make sure all lines including shielded line are properly connected.
PG encoder is disconnected, not wired properly, or the
PG option card or PG itself is damaged.
Rotational direction for the PG encoder set to F1-05 is
the opposite of the order of the motor lines. Make sure motor lines for each phase (U, V, W) are connected properly
dv4: Inversion Prevention Detection
dv4
Inversion Prevention Detection
Pulses indicate that the motor is rotating in the opposite direction of the speed reference. Set the number of pulses to trigger
inverse detection to F1-19.
Note: Disable inverse detection in applications where the motor may rotate in the opposite direction of the speed reference.
Setting F1-19 to 0 disables this feature
Cause Possible Solution
The Z pulse offset is not set properly to E5-11.
• Set the value for Δθ to E5-11 as specified on the motor nameplate.
• If the problem continues after cycling power, then replace either the PG option card or the PG encoder itself. Replacing the PG
encoder or changing the application so that the motor rotates in reverse instead requires readjustment of the Z-pulse offset.
Noise interference along the PG cable affecting the A or
B pulse.
• Make sure the motor is rotating in the correct direction.
• Look for any problems on the load side that might be causing the motor to rotate in the opposite direction.
PG encoder is disconnected, not wired properly, or the
PG option card or PG itself is damaged.
• Rewire the PG encoder and make sure all lines including shielded line are properly connected.
• If the problem continues after cycling power, then replace either the PG option card or the PG encoder itself
dWFL: DriveWorksEZ Fault Fault output by DriveWorksEZ • Correct whatever caused the fault.
Digital Operator Display
E5: SI-T3 Watchdog Timer Error
E5 SI-T3 Watchdog Timer Error
The watchdog has timed out
Data has not been received from the PLC, triggering the
watchdog timer. ⇒ Execute DISCONNECT or ALM_CLR, then issue a CONNECT command or SYNC_SET command and proced to phase
PASS MEMOBUS/Modbus Test Mode Complete . The completion of the MEMOBUS/Modbus communication test mode indicates that the test was successful and communication between the devices using the MEMOBUS/Modbus protocol was established without any errors. No further action is required.
PGo PG Disconnect (for Control Mode with PG) . "PGo PG Disconnect" error message is indicating that the control system is not receiving pulses from the PG encoder for a longer period of time than what is set in the F1-14 setting. This error can be caused by several factors, including a disconnected PG cable, incorrect wiring of the PG cable, insufficient power supply to the PG encoder, or a brake that is holding the PG. To resolve the issue, check the PG cable connection, verify the PG cable wiring, ensure the correct power supply is connected to the PG encoder, and check if the brake is releasing properly.
PGoH PG Hardware Fault (when using PG-X3)."PGoH PG Hardware Fault" is an error message that occurs when using a PG-X3 option card and indicates that the PG cable has become disconnected. To resolve the issue, simply reconnect the PG cable to the option card and the control system. If the error persists after reconnecting the cable, it may be necessary to check for any damage to the cable or the option card, and replace them if necessary.
rUn During Run 2, Motor Switch Command Input.The "rUn Motor Switch during Run" error message indicates that a command to switch motors was entered while the drive was running. This is not a recommended operation and can cause damage to the drive and/or the motor. To resolve the issue, change the operation pattern so that the motor switch command is only entered when the drive is stopped. It is recommended to stop the drive, perform the motor switch, and then restart the drive to ensure proper operation and avoid potential damage.
SE MEMOBUS/Modbus Test Mode Fault .The "SE MEMOBUS/Modbus Communication Test Mode Error" alarm indicates an error in the MEMOBUS/Modbus communication test mode. This error occurs when a digital input set to 67H (MEMOBUS/Modbus test) is closed while the drive is running. To resolve the issue, stop the drive and run the test again while ensuring that the digital input is not closed. If the error persists, it may be necessary to check the wiring and configuration of the digital input and the drive to ensure that they are properly set up for MEMOBUS/Modbus communication. This alarm will not trigger a multi-function output terminal that is set for alarm output (H2- = 10).
TrPC IGBT Maintenance Time (90%) . The "TrPC IGBT Maintenance Time (90%)" message indicates that the IGBTs in the drive have reached 90% of their expected performance life. This means that the IGBTs are approaching the end of their useful life and may start to degrade in performance. To prevent unexpected failures and ensure continued operation, it is recommended to replace the drive. Failing to do so may result in decreased performance and potential damage to the drive and/or the connected motor.