The OL1 error code indicates that the electronic motor overload protection has tripped, which means that the motor has drawn more current than what is allowed by the protection. This can be caused by a number of reasons, including a blocked impeller, overloading of the motor, or a malfunction in the motor itself. To resolve the issue, you should try to identify the cause of the problem and take appropriate steps to correct it, such as clearing any blockages or reducing the load on the motor. If the problem persists, you may need to call a technician to diagnose and repair the motor.
The "Load is too heavy. Reduce the load" message means that the system is detecting that the load placed on the motor is exceeding its capacity, which can cause the OL1 error to trip. To resolve the issue, you should reduce the load placed on the motor by either removing some of the load or rearranging it in a way that reduces the strain on the motor.
The "Cycle times are too short during acceleration and deceleration. Increase the acceleration and deceleration times (C1-01 through C1-08)" message means that the system is detecting that the motor is being accelerated and decelerated too quickly, which can cause excessive stress on the motor and lead to the OL1 error tripping. To resolve the issue, you should increase the acceleration and deceleration times by adjusting the relevant parameters (C1-01 through C1-08) in the system settings. This will give the motor more time to ramp up to its desired speed and slow down, reducing the stress on the motor and helping to prevent the OL1 error from tripping.
The message "A general purpose motor is driven below the rated speed with too high load" indicates that the motor is being operated below its designed speed and with a load that is too heavy for its capacity. This can result in the motor overheating and tripping the overload protection.
To resolve the issue, you can take the following steps:
Reduce the load on the motor.
Increase the speed at which the motor is operating.
If the motor is required to operate at low speeds, either increase the motor's capacity by using a motor with a higher rating or use a motor specifically designed to operate in the desired speed range.
By taking these steps, you can reduce the strain on the motor and prevent the overload protection from tripping.
The message "The output voltage is too high. Adjust the user-set V/f patterns (E1-04 through E1-10)" indicates that the voltage being supplied to the motor is exceeding its maximum rating, which can result in the motor overheating and tripping the overload protection.
To resolve the issue, you can adjust the user-set V/f patterns (E1-04 through E1-10) in the system settings. Specifically, you may need to reduce parameters E1-08 and E1-10, but be careful not to reduce them too much as this can reduce the motor's load tolerance at low speeds.
By making these adjustments, you can reduce the voltage supplied to the motor and prevent the overload protection from tripping.
-The message "The wrong motor rated current is set to E2-01" means that the value set for the motor-rated current in parameter E2-01 does not match the actual current rating of the motor.
To resolve the issue, you should follow these steps:
Check the motor-rated current by referring to the nameplate or data sheet for the motor.
Enter the value written on the motor nameplate into parameter E2-01 in the system settings.
By setting the correct motor-rated current in parameter E2-01, you can ensure that the system is properly configured to operate the motor and prevent the overload protection from tripping.
-The message "The maximum output frequency is set incorrectly" means that the maximum frequency at which the drive can operate the motor is not set correctly in the system.
To resolve the issue, you should follow these steps:
Check the rated frequency indicated on the motor nameplate.
Enter the rated frequency into parameter E1-06 (Base Frequency) in the system settings.
Additionally, if multiple motors are being run off the same drive, you should:
Disable the motor protection function (L1-01 = 0) in the system settings.
Install a thermal relay to each motor to provide individual protection for each motor.
By setting the correct maximum output frequency and providing individual protection for each motor, you can ensure that the system is properly configured to operate the motors and prevent the overload protection from tripping.
-The message "The electrical thermal protection characteristics and motor overload characteristics do not match" means that the protection settings for the motor in the system do not match the actual characteristics of the motor.
To resolve the issue, you should follow these steps:
Check the motor characteristics by referring to the motor nameplate or data sheet.
Correct the type of motor protection that has been selected (L1-01) in the system settings to match the actual characteristics of the motor.
Install an external thermal relay to provide additional protection for the motor.
By correctly setting the motor protection and installing an external thermal relay, you can ensure that the system is properly configured to protect the motor and prevent the overload protection from tripping.
-The message "The electrical thermal relay is operating at the wrong level" means that the thermal relay, which provides protection for the motor by monitoring the current, is not set to the correct level.
To resolve the issue, you should follow these steps:
Check the current rating listed on the motor nameplate.
Check the value set for the motor-rated current (E2-01) in the system settings.
By verifying the current rating of the motor and ensuring that the correct value is set for the motor-rated current in the system, you can ensure that the thermal relay is set to the correct level and provide proper protection for the motor.
-The message "Motor overheated by overexcitation operation" means that the motor has become overheated due to excessive overexcitation, or applying too much power to the motor.
To resolve the issue, you should follow these steps:
Prevent excessive overexcitation operation or provide proper cooling to the motor.
Reduce the excitation deceleration gain (n3-13) in the system settings.
Set parameter L3-04 (Stall Prevention during Deceleration) to a value other than 4 in the system settings.
By reducing the excitation and properly controlling the stall prevention during deceleration, you can help prevent excessive overexcitation and reduce the risk of motor damage from overheating.
-The message "Speed Search related parameters are set incorrectly" means that the parameters related to the Speed Search function in the system are not set correctly.
To resolve the issue, you should follow these steps:
Check the values set for Speed Search-related parameters.
Adjust the Speed Search current and Speed Search deceleration times (b3-02 and b3-03 respectively) in the system settings.
After conducting Auto-Tuning, enable Speed Estimation Speed Search (b3-24 = 1) in the system settings.
The message "Output current fluctuation due to input phase loss" means that the output current is fluctuating because of a loss of one or more phases in the input power supply.
To resolve the issue, you should:
Check the power supply for phase loss and make sure that all three phases are present and properly connected.
By correcting the Speed Search parameters and checking the input power supply, you can ensure that the system is operating correctly and reduce the risk of output current fluctuations.
ol2
The message "oL2 Drive Overload" means that the thermal sensor in the drive has triggered the overload protection.
This indicates that the drive is overheating and needs to be cooled down. To resolve the issue, you should:
Check the air flow and ventilation around the drive to ensure that it is not being blocked or restricted.
Check the ambient temperature to ensure that it is within the acceptable range for the drive.
Check the drive's cooling fan to ensure that it is functioning properly.
Reduce the load on the drive to reduce the heat generated.
By addressing the air flow, temperature, cooling fan, and load, you can help prevent further overheating and reduce the risk of damage to the drive.
-The messages indicate possible causes for the drive overload and suggest actions to resolve the issue.
Load is too heavy: Reduce the load applied to the drive.
Acceleration or deceleration times are too short: Increase the settings for the acceleration and deceleration times (C1-01 through C1-08).
The output voltage is too high: Adjust the preset V/f pattern (E1-04 through E1-10) by reducing E1-08 and E1-10. Be careful not to lower E1-08 and E1-10 excessively because this reduces load tolerance at low speeds.
Drive capacity is too small: Replace the drive with a larger model to handle the increased load.
Overload occurred when operating at low speeds: Reduce the load when operating at low speeds, replace the drive with a larger model, or lower the carrier frequency (C6-02).
Excessive torque compensation: Reduce the torque compensation gain (C4-01) until there is no speed loss but less current.
Speed Search related parameters are set incorrectly: Check and adjust the settings for all Speed Search related parameters, including the current used during Speed Search and the Speed Search deceleration time (b3-03 and b3-02 respectively). Enable the Speed Estimation Speed Search (b3-24 = 1) after Auto-Tuning the drive.
Output current fluctuation due to input phase loss: Check the power supply for phase loss and take necessary measures to resolve it.
By following these steps and making necessary adjustments, you can resolve the drive overload and prevent future occurrences.
ol3
The load exceeds the set torque limit for too long a time.
• Review the settings for torque detection limit (L6-02) and the time limit (L6-03).
• Check the status of the machine and remove any faults that may be causing the issue.
ol4
It's possible that the fault is caused by incorrect settings of parameters L6-05 and L6-06. To resolve the issue, check the values of these parameters and adjust them as needed. It's important to ensure that the parameters are appropriate for the load to prevent the current from exceeding the value set for overtorque Detection 2 for an extended period of time.
Fault on the machine side (e.g., machine is locked up). Check the status of the load. Remove the cause of the fault.
ol5
oL5 Mechanical Weakening Detection 1
Check the cause of the mechanical weakening by checking the load and the drive parameters.
• Check the load conditions and adjust if necessary.
• Check the settings of L6-08 and adjust if necessary to match the load conditions.
oL7 High Slip Braking oL
The above mentioned solutions are the possible solutions for the "oL7 High Slip Braking oL" error. This error is triggered when the output frequency stays constant for a time greater than the time set in n3-04 during High Slip Braking. To resolve this error, you can try reducing the deceleration times, using a braking resistor, increasing the setting of n3-04, or checking if something on the load side is restricting the deceleration.
The cause of oL7 High Slip Braking error is that the output frequency stayed constant for longer than the time set in n3-04 during High Slip Braking. Possible solutions include reducing deceleration times, using a braking resistor, increasing the setting of n3-04 or installing a thermal relay.