Omron A1000 fault codes 2

CPF00, CPF01: Control Circuit Error  

A Control Circuit Error is caused by a self-diagnostic error in the control circuit. Possible solutions include cycling power to the drive, replacing the control board or the entire drive, and replacing the operator if its connector is damaged. Contact AVM or a sales representative for instructions on replacing the control board.

LF: Output Phase Loss

An Output Phase Loss occurs when there is a phase loss on the output side of the drive. This can happen when the output cable is disconnected, the motor winding is damaged, the output terminal is loose, the motor's rated current is less than 5% of the drive's rated current, an output transistor is damaged, or a single-phase motor is being used. Possible solutions include checking and correcting wiring, checking resistance between motor lines and replacing the motor if damaged, tightening the output terminal, checking drive and motor capacities, replacing the control board or the entire drive, and using a drive that is compatible with the motor. Contact AVM or a sales representative for instructions on replacing the control board.


LF2: Current Imbalance  

Output current imbalance (LF2) error is detected when one or more of the phases in the output current is lost. Possible causes and solutions include:

Phase loss has occurred on the output side of the drive: check for faulty wiring or poor connections and correct them.
Terminal wires on the output side of the drive are loose: tighten the terminals using the specified torque.
The output circuit is damaged: replace the control board or the entire drive.
Motor impedance or motor phases are uneven: measure the line-to-line resistance for each motor phase and ensure they are the same. Replace the motor if necessary.

nSE: Node Setup Error

Make sure that the node setup terminal is not closed during run. Only perform the node setup function when the drive is stopped.

CPF02: A/D Conversion Error

A/D conversion circuit is damaged.
• If the problem continues, replace either the control board or the entire drive. For instructions on replacing the control board,
contact Yaskawa or your nearest sales representative.
External noise is affecting the A/D conversion circuit.
• Check for noise sources such as power supply and other equipment.
• Take steps to counteract noise, such as using a shielded cable and grounding the shield.
• Use surge suppressors if required.
• Check the wiring to ensure it is correct.
• If the problem continues, replace either the control board or the entire drive. For instructions on replacing the control board,
contact Yaskawa or your nearest sales representative.
 
CPF03: Control Board Connection Error

Control Board Connection Error (CPF03) occurs when there is an error in the connection between the control board and the drive.

Possible Causes and Solutions:

Connection error: Turn off the power and check the connection between the control board and the drive. If the problem persists, replace either the control board or the entire drive.
Noise interference: Check various options to minimize the effect of noise and take steps to counteract noise in the control circuit, main circuit, and ground wiring. Use recommended cables or shielded lines and ground the shield on the controller side or drive input power side. Ensure that other equipment such as switches or relays don't cause noise and use surge suppressors if necessary. Separate communication wiring from drive power lines and install an EMC noise filter to the drive power supply unit.

CPF06,CPF07: EEPROM Memory Data Error

• There is an error in the data stored in the EEPROM (electrically erasable programmable read-only memory).
Cause Possible Solution
• The control circuit for the EEPROM has an error.
• Turn off the power and check the connection between the control board and the drive.
• If the problem persists, replace either the control board or the entire drive. For instructions on replacing the control board, contact Yaskawa or your nearest sales representative.

CPF08: Terminal Board Connection Error

CPF07 Terminal Board Connection Error
There is a fault connection between the terminal board and control board.
Cause Possible Solution
• Turn the power off and reconnect the control circuit terminal board.
• If the problem continues, replace either the control board or the entire drive. For instructions on replacing the control board, contact Yaskawa or your nearest sales representative.

CPF08
The cause of the error is not specified in the manual. Contact Yaskawa or your nearest sales representative for further assistance.

CPF20, CPF21: Control Circuit Error 

Control Circuit Error
Cause: The control circuit may be damaged.
Possible Solution:

Turn off the power to the drive and cycle it back on.
If the problem persists, replace either the control board or the entire drive.
If further assistance is needed, contact Yaskawa or a nearby sales representative for instructions on replacing the control board.

CPF22: Hybrid IC Error

Control Circuit Error
Cause: Hybrid IC on the main circuit is damaged.
Possible Solution:
• Turn off the power to the drive and then turn it back on.
• Refer to the troubleshooting guide in the manual for diagnosing and resetting faults.
• If the problem persists, either replace the control board or the entire drive. For instructions on replacing the control board,
contact AVM or your nearest sales representative.


CPF23: Control Board Connection Error

Drive fails to operate properly due to noise interference.
• Check the various options available to minimize the effects of noise.
• Take steps to counteract noise in the control circuit, main circuit, and ground wiring.
• Use only recommended cables or other shielded line. Ground the shield on the controller side or on the drive input power side.
• Ensure that other equipment such as switches or relays do not cause noise and use surge suppressors if required.
• Separate all communication wiring from drive power lines. Install an EMC noise filter to the drive power supply unit.

CPF24: Drive Unit Signal Fault  

Drive capacity cannot be detected correctly due to a signal fault.
Possible Solution:
• Replace either the control board or the entire drive.
• For instructions on replacing the control board, contact Yaskawa or the nearest sales representative.


CPF26 to CPF34: Control Circuit Error

If the cause of the error is determined to be a CPU error indicated by CPF26 to CPF34, then it is likely that the hardware of the control board or the entire drive is damaged. To resolve the issue, replace either the control board or the entire drive. If you need instructions on replacing the control board, contact Yaskawa or your nearest sales representative.

LT-1 Cooling Fan Maintenance Time. 
LT-2 Capacitor Maintenance Time.  The DC bus capacitors have reached 90% of their designated life
time. Replace the drive

LT-3 Soft Charge Bypass Relay Maintenance Time.  The DC bus charge circuit has reached 90% of its designated life
time. Replace the drive.

LT-4 IGBT Maintenance Time (50%) .  The IGBT’s have reached 50% of their designated life time. Check the load, carrier frequency, and output frequency.

 