Omron A1000 fault codes 12
End1: Excessive V/f Setting . The error "End1 Excessive V/f Setting (detected only during Rotational Auto-Tuning, and displayed after Auto-Tuning is complete)" indicates that the torque reference exceeded 20% during the Auto-Tuning process. This error can impact the performance of the drive and cause issues with the operation of the motor.
The possible solutions to this error are:
Verify the information written on the motor nameplate before Auto-Tuning the drive and enter that data into the parameters T1-03 through T1-05.
Enter the proper information into parameters T1-03 to T1-05 and repeat the Auto-Tuning process.
If possible, disconnect the motor from the load and perform the Auto-Tuning process again. If the load cannot be uncoupled, use the Auto-Tuning results as they are.
It is recommended to seek assistance from a technician if the problem persists even after trying these solutions.
End2: Motor Iron Core Saturation Coefficient Error . The error "End2 Motor Iron-Core Saturation Coefficient (detected only during Rotational Auto-Tuning and displayed after Auto-Tuning is complete)" indicates that the data entered during the Auto-Tuning process is incorrect or that the results from Auto-Tuning are outside the parameter setting range, which requires the iron-core saturation coefficient (E2-07, E2-08) to be assigned a temporary value.
The possible solutions to this error are:
- Make sure the data entered into the T1 parameters match the information written on the motor nameplate.
- Restart the Auto-Tuning process and enter the correct information.
- Check and correct any faulty motor wiring.
** Disconnect the motor from the machine and perform the Rotational Auto-Tuning process again.
It is recommended to seek assistance from a technician if the problem persists even after trying these solutions.
End3: Rated Current Setting Alarm . The entered current rating for the motor during Auto-Tuning is incorrect.
- Verify the current rating written on the motor nameplate and enter it into parameter T1-04.
- Perform Auto-Tuning again with the correct current rating entered.
End4 Adjusted Slip Value Fell Below Lower Limit . - Check for any mechanical issues that might affect the slip calculation.
- Ensure that the motor is properly sized for the application and that it has the correct voltage and frequency.
- Make sure that the load on the motor is within its specified operating range.
- Confirm that the power supply is providing clean and stable power to the drive.
- If the problem persists, consider seeking assistance from a qualified technician or service provider.
End5: Resistance Between Lines Error .
- Make sure that the motor is properly sized for the application and that it has the correct voltage and frequency.
- Ensure that the load on the motor is within its specified operating range.
- Confirm that the power supply is providing clean and stable power to the drive.
- If possible, try a different motor cable to eliminate a potential cable issue.
- Check for any environmental factors that might affect the resistance measurement, such as high temperature or high humidity.
- If the problem persists, consider seeking assistance from a qualified technician or service provider.
End6: Leakage Inductance Alarm .
- Check the motor and motor cable connection for faults
- Make sure that the motor is properly sized for the application and that it has the correct voltage and frequency.
- Ensure that the load on the motor is within its specified operating range.
- Confirm that the power supply is providing clean and stable power to the drive.
- If possible, try a different motor cable to eliminate a potential cable issue.
- Check for any environmental factors that might affect the leakage inductance measurement, such as high temperature or high humidity.
- If the problem persists, consider seeking assistance from a qualified technician or service provider.
End7: No-Load Current Alarm .
- Ensure that the motor is properly sized for the application and that it has the correct voltage and frequency.
- Confirm that the power supply is providing clean and stable power to the drive.
- Check for any environmental factors that might affect the no-load current measurement, such as high temperature or high humidity.
- If possible, try a different motor cable to eliminate a potential cable issue.
- Make sure that the load on the motor is within its specified operating range.
- If the problem persists, consider seeking assistance from a qualified technician or service provider.
Er-01: Motor Data Error.
- Confirm that the motor data entered in the drive parameters matches the motor nameplate information. - Make sure that the drive and motor capacities match. - Check the motor rated current and no-load current and correct the settings as necessary. - Confirm that the base frequency and motor rated speed are set correctly. - Ensure that the correct pole number is entered in T1-06. - If the problem persists, consider seeking assistance from a qualified technician or service provider.
Er-02: Alarm .
- Check the drive display or manual for the specific alarm code that was triggered.
- Identify and resolve the cause of the alarm.
- Restart the Auto-Tuning process once the issue has been addressed.
- If the problem persists, consider seeking assistance from a qualified technician or service provider.
Er-03: STOP button Input . Possible Solutions:
- Check that the motor and drive are connected properly and functioning normally.
- Ensure that the input data for the Auto-Tuning process is correct.
- Confirm that the power supply is providing clean and stable power to the drive.
- Repeat the Auto-Tuning process, making sure not to cancel it prematurely.
- If the problem persists, consider seeking assistance from a qualified technician or service provider.
Er-04: Line-to-Line Resistance Error .
- Check the motor and motor cable connection for faults.
- Ensure that the motor is properly sized for the application and that it has the correct voltage and frequency.
- Confirm that the power supply is providing clean and stable power to the drive.
- If possible, try a different motor cable to eliminate a potential cable issue.
- Check for any environmental factors that might affect the line-to-line resistance measurement, such as high temperature or high humidity.
- Repeat the Auto-Tuning process, making sure to enter the correct information.
- If the problem persists, consider seeking assistance from a qualified technician or service provider.
Er-05: No-Load Current Error .
- Confirm that the power supply is providing clean and stable power to the drive.
- Ensure that the motor is properly sized for the application and that it has the correct voltage and frequency.
- Check for any environmental factors that might affect the no-load current measurement, such as high temperature or high humidity.
- Repeat the Auto-Tuning process, making sure to enter the correct information.
- If the problem persists, consider seeking assistance from a qualified technician or service provider.
Er-08: Rated Slip Error .
- Confirm that the power supply is providing clean and stable power to the drive.
- Ensure that the motor is properly sized for the application and that it has the correct voltage and frequency.
- Check for any environmental factors that might affect the slip measurement, such as high temperature or high humidity.
- Repeat the Auto-Tuning process, making sure to enter the correct information.
- If the problem persists, consider seeking assistance from a qualified technician or service provider.
Er-09: Acceleration Error .
Er-09 Acceleration Error occurs when the motor fails to accelerate for the specified acceleration time. Possible solutions include increasing the acceleration time, checking the torque limit settings, and ensuring the load is not too high during rotational auto-tuning. If a mechanical brake is installed, it should be fully lifted during tuning.
Er-10: Motor Direction Error . If the error persists, check the load torque specifications and adjust the torque control settings accordingly.
Encoder signal lines not properly connected: To resolve this issue, you need to physically inspect the wiring connections between the encoder and the drive and make sure that they are properly connected and secure. The wiring diagram or manual of the drive and encoder should provide information on the proper connections.
Motor and PG direction are opposite: To resolve this issue, check the motor speed monitor U1-05 while turning the motor manually in the forward direction. If the sign displayed is negative, change the setting of parameter F1-05 to correct the direction. The manual of the drive should provide instructions on how to change the parameter setting.
Load pulled the motor in the opposite direction: If the load pulled the motor in the opposite direction of the speed reference and caused the torque to exceed 100%, uncouple the motor from the load and repeat the Auto-Tuning process. If the error persists, check the load torque specifications and adjust the torque control settings accordingly to prevent the motor from exceeding its torque limits.
It is important to note that the above solutions are general suggestions and the specific steps may vary depending on the drive and motor model and the exact cause of the ER-10 error. Consulting the manual and technical support of the manufacturer can provide more specific guidance on resolving the issue.
Er-11: Motor Speed Error .
- Reduce the torque reference (F1-03) until the ER-11 error clears.
The motor is loaded beyond its maximum torque capacity. Reduce the load on the motor or replace the motor with one that has a higher torque capacity.
The motor parameters are not set correctly. Perform an Auto-Tuning procedure or manually set the motor parameters (F1-00 to F1-02) using the specifications of the motor.
The PG feedback signal is incorrect. Check the wiring and connections to the PG encoder and correct any issues found.
Torque reference is too high: To resolve this issue, you can try increasing the acceleration time (C1-01), reducing the torque reference (F1-03) until the ER-11 error clears, or disconnecting the machine from the motor if possible.
Motor loaded beyond maximum torque capacity: If the motor is loaded beyond its maximum torque capacity, reduce the load on the motor or replace it with one that has a higher torque capacity.
Er-12: Current Detection Error .
- Check the motor wiring for an open circuit between motor lines.
- Check for loose connections or loose wire nuts in the motor and control circuit.
- Check for poor power supply voltage to the drive.
- Check for poor power supply voltage to the motor.
- If the problem persists, replace either the control board or the entire drive.
Missing motor phase: To resolve this issue, you need to physically inspect the wiring connections between the motor and the drive and make sure that all three phases (U/T1, V/T2, W/T3) are present and properly connected. If a problem is found, correct it.
Current exceeded the current rating of the drive: If the current exceeded the current rating of the drive, you need to check the motor wiring for a short between motor lines, check if a magnetic contactor is used between the motors and make sure it is closed. If the problem persists, replace either the control board or the entire drive.
Current too low: To resolve this issue, you need to check the motor wiring for an open circuit between motor lines, check for loose connections or loose wire nuts in the motor and control circuit, check for poor power supply voltage to the drive and motor. If the problem persists, replace either the control board or the entire drive.
It is important to note that the above solutions are general suggestions and the specific steps may vary depending on the drive and motor model and the exact cause of the ER-12 error. Consulting the manual and technical support of the manufacturer can provide more specific guidance on resolving the issue.
Er-13: Leakage Inductance Error .
- Verify the load on the motor during tuning. If the load is too high, it may cause the tuning process to fail.
- Check the power supply voltage to the drive. If it is too low, the drive may not be able to generate the necessary currents for tuning.
- Try resetting the drive and repeating the tuning process.
- Ensure that the motor cable length is within the specified range as longer cable lengths can increase the leakage inductance.
- Check if the motor has a high resistance connection, which can cause an increase in leakage inductance and result in a failure to tune.
- If the problem persists, consider replacing the motor or contacting the manufacturer for further assistance.
Er-14: Motor Speed Error 2 . - Check the load on the motor during tuning. If the load is too high, it may cause the speed to exceed the reference.
- Check the power supply voltage to the drive. If it is too low, the drive may not be able to generate the necessary torque for the motor.
- Verify that the motor is properly connected to the drive and that the wiring is correct.
- Ensure that the motor cable length is within the specified range as longer cable lengths can affect the motor speed.
- Consider reducing the speed reference in the drive.
- Check if the motor has a high resistance connection, which can cause a reduction in motor speed and result in an error during tuning.
- If the problem persists, try resetting the drive and repeating the tuning process or consider contacting the manufacturer for further assistance.
Er-15: Torque Saturation Error .
- Check the load on the motor during tuning. If the load is too high, it may cause the output torque to reach the limit.
- Check the power supply voltage to the drive. If it is too low, the drive may not be able to generate the necessary torque for the motor.
- Verify that the motor is properly connected to the drive and that the wiring is correct.
- Ensure that the motor cable length is within the specified range as longer cable lengths can affect the motor torque.
- Check if the motor has a high resistance connection, which can cause a reduction in motor torque and result in an error during tuning.
- Consider reducing the test signal frequency and amplitude to lower the torque output during tuning.
- If the problem persists, try resetting the drive and repeating the tuning process or consider contacting the manufacturer for further assistance.
Er-16 Inertia ID Error .
- Check the load on the motor during tuning. If the load is too high, it may cause the drive to misidentify the inertia.
- Check the power supply voltage to the drive. If it is too low, the drive may not be able to generate the necessary torque for the motor.
- Verify that the motor is properly connected to the drive and that the wiring is correct.
- Ensure that the motor cable length is within the specified range as longer cable lengths can affect the motor inertia.
- Check if the motor has a high resistance connection, which can cause a reduction in motor torque and result in an error during tuning.
- Consider adjusting the test signal frequency and amplitude to achieve a more accurate detection of the motor inertia.
- If the problem persists, try resetting the drive and repeating the tuning process or consider contacting the manufacturer for further assistance.
Er-17: Reverse Prohibited Error .
- Check if the reverse rotation restriction is set in the drive parameter settings. If it is, try changing it to allow reverse rotation.
- Verify that the wiring connections for the motor are correct and that there is no fault in the motor.
- Check if the motor has a mechanical or electrical restriction that prevents it from rotating in reverse.
- Ensure that the motor is properly connected to the drive and that the wiring is correct.
- If the problem persists, try resetting the drive and repeating the tuning process or consider contacting the manufacturer for further assistance.
Er-18: Induction Voltage Error .
- Check the accuracy of the data entered in T2-** parameters and ensure that it matches the data from the motor nameplate or manufacturer specifications.
- Verify that the wiring connections for the motor are correct and that there is no fault in the motor.
- Check the power supply voltage to the drive. If it is too low, the drive may not be able to generate the necessary voltage for the motor.
- Ensure that the motor is properly connected to the drive and that the wiring is correct.
- If the problem persists, try resetting the drive and repeating the tuning process or consider contacting the manufacturer for further assistance.
Er-19: PM Inductance Error .
- Check the accuracy of the data entered in T2-** parameters E5-08 or E5-09 and ensure that it matches the data from the motor nameplate or manufacturer specifications.
- Verify that the wiring connections for the motor are correct and that there is no fault in the motor.
- Check the power supply voltage to the drive. If it is too low, the drive may not be able to generate the necessary voltage for the motor.
- Ensure that the motor is properly connected to the drive and that the wiring is correct.
- If the problem persists, try resetting the drive and repeating the tuning process or consider contacting the manufacturer for further assistance.
Er-20: Stator Resistance Error . The "Er-20 Stator Resistance Error" message is typically generated by a variable frequency drive (VFD) and indicates that the stator resistance tuning has attempted to set a value that is outside the allowable range. The possible solutions for this error are:
Double check the data that was entered into the T2-** parameters. Ensure that the values are within the correct range and match the specifications for the drive.
Perform Auto-Tuning again. The Auto-Tuning function can be used to automatically set the optimal values for the stator resistance parameters, and can often resolve the Er-20 error.
It's important to follow the manufacturer's instructions and guidelines when performing any adjustments or repairs to the VFD. If the issue persists, it's best to consult with a qualified technician or seek technical support from the manufacturer.
Er-21: Z Pulse Correction Error . The "Er-21 Z Pulse Correction Error" message is typically generated by a variable frequency drive (VFD) and indicates a problem with the pulse generator (PG) encoder. The pulse generator encoder provides position information to the drive, which is used to control the motor's speed and position. The possible causes and solutions for this error are:
Motor was coasting when Auto-Tuning was performed. Make sure the motor has completely stopped before attempting Auto-Tuning again.
Incorrect wiring for the motor or the PG encoder. Check the wiring for the motor and the PG encoder and ensure that they are properly connected.
Incorrect direction or number of pulses set for the PG encoder. Check the direction and number of pulses set for the PG encoder, and make sure they are correct.
Damaged PG encoder. Check the signal output from the PG encoder attached to the motor, and replace the PG if it is damaged.
It's important to follow the manufacturer's instructions and guidelines when performing any adjustments or repairs to the VFD. If the issue persists, it's best to consult with a qualified technician or seek technical support from the manufacturer.
- previous page <<