Omron 3G3XV fault codes 2
- Over Torque Detection (%l3 or OL3):
- - The motor operates in a preset mode if the Inverter output current exceeds the overtorque detection level. This function protects the machine or monitors the output torque.
- External Fault Signal Input (ef4 or EF4, ef5 or EF5):
- - When an external alarm signal is input, the Inverter operates according to a preset stop method (coasting to a stop or ramp to stop).
- Control Circuit Fault Thermistor Fault (cpf00 to cpf05):
- - The Inverter output is shut off if there's a transmission error in the control circuit or a component fails.
Low-Voltage Protection (UV):
- Monitor Display: uU (Blink)
- Status: Non-operation
- Description: This occurs when the main circuit DC voltage drops below the detection level while the inverter output is off.
- Troubleshooting: Check the main circuit voltage and ensure it is sufficient for the inverter operation.
Over Torque Detection (OL3):
- Monitor Display: %l3 (Blink)
- Status: Non-operation
- Description: This function is used to protect the machine and to monitor the inverter's output torque. The inverter output reacts in a preset manner when the output current exceeds the over torque detection level.
- Troubleshooting: Adjust the over torque detection level or check for any mechanical issues causing excessive torque demand.
Stall Prevention:
- During Acceleration: Inverter acceleration is stopped when 170% or more of the inverter rated current is required by the load to prevent overload protection (OL2) or overcurrent (OC) from occurring. Acceleration is enabled again when the current is reduced to less than 170%.
- During Normal Operation: Output frequency is decreased when 160% of the inverter rated current or greater is required by the load to prevent motor and inverter overload (OL1, OL2). Acceleration is enabled again when the current is reduced below 160%.
- During Deceleration: Deceleration is stopped when the DC voltage rises due to motor regenerative energy to prevent overvoltage trips (OV). Deceleration resumes when the DC voltage decreases.
- Status: Non-operation
- Troubleshooting: Check the load requirements and adjust the acceleration/deceleration settings accordingly to prevent stalling.
Simultaneous Forward and Reverse Rotation Commands (EF):
- Monitor Display: ef (Blink)
- Status: Non-operation
- Description: The inverter is stopped according to the preset stop method when forward and reverse rotation commands are simultaneously detected for a period exceeding 500 ms.
- Troubleshooting: Check the control signals to ensure that forward and reverse commands are not being sent simultaneously.
External Base Block Signal Input (BB):
- Monitor Display: bb (Blink)
- Status: Non-operation
- Description: When an external base block signal is input, the motor coasts to a stop. The inverter output is immediately turned on at the previously set frequency when the external base block signal is removed.
- Troubleshooting: Check the external base block signal and ensure it is functioning correctly.
Low-Voltage Protection (UV):
- Cause: Input voltage drop
- Corrective Action: Check the input power supply voltage using a tester. If the voltage is low, adjust the input voltage.
Over Torque Detection (OL3):
- Cause: Motor current exceeded the set value due to machine fault or overload.
- Corrective Action: Check the driven machine and correct the cause of the fault or set to a higher value.
Stall Prevention (During Acceleration):
- Cause: Insufficient power for accel/decel, overload, phase loss
- Corrective Action: Set proper accel/decel time for smooth operation.
Stall Prevention (During Normal Operation):
- Cause: Insufficient power for accel/decel, overload, phase loss
- Corrective Action: Lighten the load or increase inverter capacity.
Simultaneous Forward and Reverse Rotation Commands (EF):
- Cause: Operation sequence error, 3-wire/2-wire selection error
- Corrective Action: Recheck the control sequence and constant settings (No. 32).
External Base Block Signal Input (BB):
- Cause: Not specified
- Corrective Action: Not specified
Correcting Motor Faults:
- Motor does not rotate: Check power supply voltage, reduce the load if locked, correct any displayed faults, ensure FWD or REV run command is entered, check frequency setting signal, and verify Operation Method Selection Mode.
- Motor rotating in the wrong direction: Check the wiring of output terminals and FWD/REV run signals.
- Motor rotates, but variable speed does not work: Correct the wiring of the frequency setting circuit and reduce the load if it's too large.
- Motor speed is too high (low): Check motor specifications, maximum frequency set value, and base frequency.
- Motor speed is unstable: Reduce the load, reduce load variation, or increase inverter or motor capacity.
The Accel/Decel Prohibit Function is a feature in some VFDs (Variable Frequency Drives) that allows you to temporarily suspend acceleration or deceleration without stopping the motor. This can be useful in applications where you need to momentarily hold the motor at its current speed, such as during a process that requires a constant speed for a specific duration.
Here's how the function works based on your description:
- Function Activation: You can activate the Accel/Decel Prohibit Function using multifunction contact input terminals. For example, you can set constant No. 32 to a value of 8 to assign the Accel/Decel Prohibit Command to terminal 4, and set constant No. 33 to a value of 6 to assign it to terminal 5.
- Operation: When an Accel/Decel Prohibit Command is input during acceleration or deceleration, the VFD will maintain the current output frequency, effectively stopping any further acceleration or deceleration. The motor will continue to run at the speed it was at when the command was received.
- Override by Stop Command: If a stop command is received while the Accel/Decel Prohibit Command is active, the prohibit command will be overridden, and the motor will stop.
- Setting Values: In your example, No. 32 is set to 1, and No. 33 is set to 3. These values would correspond to different functions based on the VFD's programming manual. You would need to refer to the specific manual for your VFD to understand what these values represent.
- Time Chart: The time chart mentioned would typically illustrate how the motor speed (frequency) remains constant during the period when the Accel/Decel Prohibit Command is active, and how it resumes acceleration or deceleration once the command is removed.
It's important to consult the specific manual for your VFD model to understand the exact implementation and settings for the Accel/Decel Prohibit Function, as the details can vary between different manufacturers and models.