Omron 3G3XV fault codes

Low Voltage Protection:
- Causes: Inverter capacity is too small, voltage drop due to wiring, a motor of large capacity (11 kW or greater) connected to the same power system has been started, rapid acceleration with generator power supply, operation sequence when power is off, or defective electromagnetic contactor.
- Troubleshooting: Check the power capacity and power system. If the UV display appears when the inverter power is turned off while the operation signal is input, remove the power after stopping the inverter.
Overcurrent Protection:
- Causes: Extremely rapid acceleration/deceleration, motor on/off switching at the inverter output side, motor of a capacity greater than the inverter rating has been started, high-speed motor or pulse motor has been started, or inverter output has been short-circuited.
- Troubleshooting: Investigate the error cause, correct it, then restart. If a transistor error occurs, replace the inverter.
Ground-fault Protection:
- Causes: Ground-fault at the inverter output side.
- Troubleshooting: Investigate and correct the ground-fault.
Overvoltage Protection:
- Causes: Overvoltage, insufficient deceleration time, regenerative load (motor is turned by the load), or high input voltage compared to motor rated voltage.
- Troubleshooting: If braking torque is not proper, extend the deceleration time or use a braking resistor.
Fuse Blown:
- Causes: Repeated overcurrent protection (OC), repeated overload protection (OL2), power reset, or rapid deceleration in excess excitation (improper V/f characteristic setting).
- Troubleshooting: Turn off the power supply once and turn it on again. If the fault occurs again after replacement, replace the inverter.
Cooling Fin Overheat:
- Causes: Defective cooling fan, ambient temperature rise, or clogged filter.
- Troubleshooting: Replace the cooling fan and clean the filter. Ensure the ambient temperature is 104°F (40°C) or less, or 113°F (45°C) or less with the top cover off.
Overload Protection:
- Causes: Motor overload, low-speed operation or extended acceleration time, improper V/f characteristic setting.
- Troubleshooting: Investigate the cause of overload and review the operation pattern, V/f characteristic, and motor/inverter capacities.
Over Torque Detection:
- Causes: Motor current exceeds the preset value because of machine error or overload.
- Troubleshooting: Check the use of the machine. Correct the overload cause or set a higher detection level that is within the allowable range.
External Fault Signal Input:
- Causes: External fault condition occurred.
- Troubleshooting: Correct the cause of the fault input.
Control Circuit Fault Thermistor Fault:
- Causes: External noise, excess vibration or shock.
- Troubleshooting: Record all data of cpf04, then initialize. Turn off power, then turn on again. If the error is persistent, replace the inverter.
Low Voltage Protection (uU1 or UV1):
- Causes: When the power voltage to the Inverter drops, it may not produce enough torque, and the motor can overheat. The Inverter stops outputting if the main circuit DC voltage drops below a certain level for 15 ms or longer.
- Detection levels: Approximately 210 V or less for 200 V 3-phase, 170 V or less for 200 V single-phase, and 420 V or less for 400 V 3-phase.
Overcurrent Protection (%c or OC):
- Causes: The Inverter output is shut off if the output current exceeds about 200% of the rated current.
Ground-fault Protection (gf or GF):
- Causes: The Inverter output is shut off if there's a ground fault on the output side of the Inverter.
Overvoltage Protection (%U or OV):
- Causes: The Inverter output is shut off if the main circuit DC voltage becomes too high due to regeneration energy from motor deceleration or negative load.
- Detection levels: Approximately 410 V or more for 200 V class and 820 V or more for 400 V class.
Fuse Blown:
- Causes: The Inverter output is shut off if the main circuit transistor fails. The fuse clears to prevent wiring damage from short-circuit current.
Cooling Fin Overheat (%h or OH):
- Causes: The Inverter output is shut off if the ambient temperature rises and the heat sink fin reaches 90°C. Check for a defective cooling fan or clogged filter.
Overload Protection (%l1 or OL1 for motor, %l2 or OL2 for Inverter):
- Causes: The Inverter output is stopped if motor overload is detected by the electronic thermal overload in the Inverter. Use a thermal relay or protector for each motor if driving more than one.
- Maximum rated overload: 150% for 1 minute.