Omron 3G3SX fault codes

   Autoreset Trip: When the maximum number of trips is reached during automatic reset, the trip message is marked with the hour counter "A".

Motor I2t ("I2t" Overload): The I2t value has been exceeded.
> Overloading of the motor according to the programmed I2t settings.
> Check for mechanical overload of the motor or machine (bearings, gearboxes, chains, belts, etc.).
> Change the Motor I2t Current setting in the menu group [230].

PTC (Motor Thermistor Overheating): The motor thermistor (PTC) has exceeded the maximum level.
> Check for mechanical overload of the motor or machine.
> Check the motor cooling system.
> Motor self-cooling at low speed, excessive load.
> Set PTC to OFF in menu [234].

Motor PTC (Motor Thermistor Overheating): The motor thermistor (PTC) has exceeded the maximum level.
> Check for mechanical overload of the motor or machine.
> Check the motor cooling system.
> Motor self-cooling at low speed, excessive load.
> Set PTC to OFF in menu [237].

PT100 (Motor PT100 Elements Overheating): Motor PT100 elements have exceeded the maximum level.
> Check for mechanical overload of the motor or machine.
> Check the motor cooling system.
> Motor self-cooling at low speed, excessive load.
> Set PT100 to OFF.

Motor Loss (Phase Loss or Large Imbalance in Motor Phases): Phase loss or significant imbalance in motor phases.
> Check the motor voltage in all phases.
> Check for loose or poor motor cable connections.
> If all connections are correct, contact your supplier.
> Set the motor loss alarm to OFF.

Locked Rotor (Torque Limit When Motor Stops): Mechanical rotor blockage.
> Check for mechanical issues with the motor or connected machine.
> Set the locked rotor alarm to OFF.

External Trip (External Input Active): External input (DigIn 1-8) active:
> Active low function at the input.
> Check the equipment triggering the external input.
> Check the programming of digital inputs DigIn 1-8.

External Motor Temperature (External Input Active): External input (DigIn 1-8) active:
> Active low function at the input.
> Check the equipment triggering the external input.
> Check the programming of digital inputs DigIn 1-8.

Mon MaxAlarm (Maximum Alarm Level Exceeded): Maximum alarm level (overload) reached.
> Check the load condition of the machine.
> Check the monitor setting on page 215 of Section 11-6.

Mon MinAlarm (Minimum Alarm Level Exceeded): Minimum alarm level (underload) reached.
> Check the load condition of the machine.
> Check the monitor setting on page 215 of Section 11-6.

Comm Error (Serial Communication Error): Error in serial communication (optional).
> Check the serial communication cables and connections.
> Check the serial communication settings (baud rate, parity, stop bits).
> Check if the correct communication parameters are used.

Inrush Current Alarm (Current Exceeds Inrush Limit): The current exceeds the inrush limit.
> Check the current setting in the Inrush Current setting menu.
> Check the electrical parameters.