Omron 3G3SV fault codes 2

- Overload Protection (Motor):
- Causes:
- Overload, low-speed operation or extended acceleration time, improper V/f characteristic setting.
- Solutions:
- Investigate the cause of overload and review the operation pattern, V/f characteristic, and motor/inverter capacities.

- Over Torque Detection:
- Causes:
- Motor current exceeds the preset value because of machine error or overload.
- Solutions:
- Check the use of the machine. Correct the overload cause or set a higher detection level within the allowable range.

- External Fault Signal Input:
- Causes:
- External fault condition occurred.
- Solutions:
- Correct the cause of the fault input.

- Control Circuit Fault / Thermistor Fault:
- Causes:
- External noise.
- Excess vibration or shock.

- Solutions:
- Record all data and make initialization.
- Turn off power, then turn on again. If the error is persistent, replace the inverter.


- Low-voltage Protection (Main Circuit Voltage Insufficient):
The monitor display appears when the main circuit DC voltage drops under the detection level while the inverter output is off. (UV) (Blink) Non-operation

- Over Torque Detection:
This function is used to protect the machine and to monitor the inverter’s output torque. The inverter output reacts in a preset manner when the inverter output current exceeds the over torque detection level. The monitor display blinks when “operation continue” is preset. (OL3) (Blink) Non-operation

- Stall Prevention (Acceleration/Deceleration):
- During acceleration: Inverter acceleration is stopped when 170% of or more of the inverter rated current is required by the load. This prevents overload protection (OL2) or overcurrent (OC) from occurring. When current is reduced to less than 170%, acceleration is enabled.
- During normal operation: Output frequency is decreased when 160% of the inverter rated current or greater is required by the load. This prevents motor and inverter overload (OL1, OL2). When current is reduced below 160%, inverter acceleration is then enabled.
- During deceleration: Deceleration is stopped when the DC voltage is caused to rise by motor regenerative energy. This prevents overvoltage trips (OV). When DC voltage decreases, deceleration to the set value then resumes.


- Simultaneous Normal and Reverse Rotation Commands:
When forward and reverse rotation commands are simultaneously detected for a period of time exceeding 500 ms, the inverter is stopped according to the preset stop method. (EF) (Blink) Non-operation

- External Base Block Signal Input (Main Circuit Transistor Instantaneous Shut-Off):
When an external base block signal is input, the motor coasts to a stop. When the external base block signal is removed, the inverter output is immediately turned on at the previously set frequency. (BB) (Blink) Non-operation

- Low-voltage Protection (Main Circuit Voltage Insufficient):
- Cause:
- Input voltage drop
- Troubleshooting:
- Check the main circuit DC voltage in Un-xx. If the voltage is low, adjust the input voltage.

- Over Torque Detection:
- Cause:
- Motor current exceeded the set value because of machine fault or overload.
- Troubleshooting:
- Check the driven machine and correct the cause of the fault or set to a higher value.

- Stall Prevention (Acceleration/Deceleration):
- During Acceleration:
- Cause: Insufficient power for accel/decel, overload, phase loss
- Troubleshooting: Set proper accel/decel time for smooth operation. For stall prevention during normal operation, lighten the load or increase inverter capacity.

- During Normal Operation:
- During Deceleration

- Simultaneous Normal and Reverse Rotation Commands:
- Cause:
- Operation sequence error, 3-wire/2-wire selection error
- Troubleshooting:
- Recheck the control sequence. Recheck constant settings (No. 32 and No. 33).

- External Base Block Signal Input (Main Circuit Transistor Instantaneous Shut-Off):
- Troubleshooting:
- This condition occurs when an external base block signal is input, causing the motor to coast to a stop. When the external base block signal is removed, the inverter output is immediately turned on at the previously set frequency. Check for any external signals that might be causing this condition and ensure proper wiring and signal integrity.