oPE01 - kVA Selection:
Meaning: Incorrect Inverter capacity setting.
Probable Cause: The Inverter capacity setting doesn't match the Unit.
Corrective Action: Contact your dealer.
oPE02 - Limit Parameter setting range error:
Meaning: The parameter setting is outside of the valid setting range.
Probable Cause: -.
Corrective Action: -.
Terminal Multi-function input selection error:
Meaning: Errors in the multi-function input (H1-01 to H1-06) settings.
Probable Cause: Various errors in the multi-function input settings.
Corrective Action: Various corrective actions depending on the specific error.
oPE05 - Sequence Select:
Meaning: Option Card selection error.
Probable Cause: Option Card selected as frequency reference source, but no Option Card is connected.
Corrective Action: Connect the Option Card or adjust the settings accordingly.
oPE06 - PG Opt Missing:
Meaning: Control method selection error.
Probable Cause: V/f control with PG feedback selected, but no PG Speed Control Card is connected.
Corrective Action: Connect the PG Speed Control Card or adjust the settings accordingly.
oPE07 - Analog Selection:
Meaning: Multi-function analog input selection error.
Probable Cause: Errors in analog input selection and PID function selection settings.
Corrective Action: Adjust the settings to correct the selection error.
oPE08 - Parameter selection error:
Meaning: Setting made that is not required in the current control method.
Probable Cause: Function used only with open loop vector control selected for V/f control.
Corrective Action: Adjust the settings to match the current control method.
oPE09 - PID control selection error:
Meaning: Conflicting settings made simultaneously.
Probable Cause: Conflicting settings in PID control mode, PID sleep function operation level, and stopping method selection.
Corrective Action: Adjust the settings to remove the conflict.
oPE10 - V/f Ptrn Setting:
Meaning: V/f data setting error.
Probable Cause: Parameters do not satisfy specified conditions.
Corrective Action: Adjust parameters E1-04, E1-06, E1-07, and E1-09 to meet the specified conditions.
oPE11 - CarrFrq/On-Delay:
Meaning: Parameter setting error related to carrier frequency.
Probable Cause: Various parameter setting errors.
Corrective Action: Adjust the parameters to correct the setting errors.
Err EEPROM R/W Err:
Meaning: EEPROM write error.
Probable Cause: Verification error occurred when writing to EEPROM.
Corrective Action: Try power cycling the device and setting the parameters again.
Er-01 Data Invalid Motor:
Meaning: Error in data input for autotuning.
Probable Causes: Error in the relationship between motor output and rated current, or between no-load current setting and input motor rated current.
Corrective Actions: Check input data, capacity of Inverter and motor, and motor rated current and no-load current.
Er-02 Minor Fault Alarm:
Meaning: Minor fault occurred during autotuning.
Probable Causes: Various minor faults during autotuning.
Corrective Actions: Check input data, wiring, machine, and load.
Er-03 STOP Key:
Meaning: STOP key input during autotuning.
Probable Causes: STOP key pressed to cancel autotuning.
Er-04 Resistance Line-to-line:
Meaning: Line-to-line resistance error.
Probable Causes: Autotuning not completed in specified time, or results exceeded parameter setting range.
Corrective Actions: Check input data, motor wiring, and disconnect motor from machine if connected.
Er-05 No-load current:
Meaning: No-load current error.
Probable Causes: Error in no-load current setting.
Corrective Actions: Check no-load current setting.
REr-08 Rated Slip:
Meaning: Rated slip error.
Probable Causes: Error in rated slip setting.
Corrective Actions: Check rated slip setting.
Er-09 Accelerate:
Meaning: Acceleration error (detected only for rotational autotuning).
Probable Causes: Motor did not accelerate in specified time.
Corrective Actions: Increase acceleration time, increase reverse torque limits if low, and disconnect motor from machine if connected.