Omron 3G3rV fault codes 2
CPF07 - RAM-Err: This error indicates an ASIC internal RAM fault. Corrective Actions: Try turning the power supply off and on again. If the control circuit is damaged, replace the inverter.
CPF08 - WAT-Err: This error indicates a watchdog timer fault. Corrective Actions: Try turning the power supply off and on again. If the control circuit is damaged, replace the inverter.
CPF09 - CPU-Err: This error indicates a CPU-ASIC mutual diagnosis fault. Corrective Actions: Try turning the power supply off and on again. If the control circuit is damaged, replace the inverter.
CPF10 - ASIC-Err: This error indicates an ASIC version fault. Corrective Actions: If the inverter control circuit is faulty, replace the inverter.
CPF20 - Option A/D Error: This error indicates a Communications Option Card A/D converter error. Corrective Actions: Turn off the power and insert the Card again. If the Option Card's A/D converter is faulty, replace the Communications Option Card.
CPF21 - Option CPU Down: This error indicates a Communications Option Card self-diagnostic error. Corrective Actions: If there is a Communications Option Card fault, replace the Option Card.
CPF23 - Option DPRAM Err: This error indicates a Communications Option Card DPRAM error. Corrective Actions: If this error occurs, it may be necessary to replace the Communications Option Card.
These CPF error codes are related to faults in the inverter's control circuit, ASIC, RAM, watchdog timer, and issues with the Communications Option Card. The corrective actions typically involve resetting the power supply and, if the issue persists, replacing the faulty components.
EF (blinking) - External Fault:
Meaning: This alarm indicates that both the forward and reverse run commands have been ON for more than 0.5 seconds.
Probable Causes: The sequence of the forward and reverse run commands is incorrect.
Corrective Actions: Check the sequence of the forward and reverse run commands. Since the rotational direction is unknown, the motor will be decelerated to a stop when this minor fault occurs.
Uu (blinking) - DC Bus Undervolt:
Meaning: This alarm indicates a main circuit undervoltage condition when there was no Run signal. It can occur if the main circuit DC voltage was below the Undervoltage Detection Level Setting (L2-05), the surge current limiting contactor opened, or the control power supply voltage went below the CUV level.
Probable Causes: See causes for UV1, UV2, and UV3 faults in the previous table.
Corrective Actions: See corrective actions for UV1, UV2, and UV3 faults in the previous table.
Alarms are a type of inverter protection function that does not operate the fault contact output. The system will automatically return to its original status once the cause of the alarm has been removed. When an alarm occurs, the Digital Operator display flashes, and the alarm is output from the multi-function outputs (H2-01 to H2-03). Take appropriate countermeasures according to the table above to resolve the alarms.
ou (blinking) - DC Bus Overvolt:
Meaning: The main circuit DC voltage exceeded the overvoltage detection level.
Probable Cause: The power supply voltage is too high.
Corrective Action: Decrease the voltage so it's within specifications.
oH (blinking) - Heatsink Overtemp:
Meaning: The temperature of the Inverter's cooling fins exceeded the setting in L8-02.
Probable Causes: The ambient temperature is too high, there is a heat source nearby, or the Inverter cooling fan has stopped.
Corrective Actions: Install a cooling unit, remove the heat source, or replace the cooling fan.
oH2 (blinking) - Over Heat 2:
Meaning: This is an Inverter overheating pre-alarm.
Probable Cause: An OH2 alarm signal (Inverter overheating alarm signal) was input from a multi-function input terminal (S3 to S7).
Corrective Action: Clear the multi-function input terminal's overheating alarm input.
oH3 (blinking) - Motor Overheat 1:
Meaning: The motor has overheated.
Probable Causes: Check the size of the load, the length of the acceleration, deceleration, and cycle times, V/f characteristics, and the motor temperature input on terminals A1 and A2.
oL3 (blinking) - Overtorque Det 1:
Meaning: There has been a current greater than the setting in L6-02 for longer than the setting in L6-03.
Probable Causes: Check the settings in L6-02 and L6-03, and the mechanical system to correct the cause of the overtorque.
oL4 (blinking) - Overtorque Det 2:
Meaning: There has been a current greater than the setting in L6-05 for longer than the setting in L6-06.
Probable Causes: Check the current setting in L6-05, time setting in L6-06, and the mechanical system to correct the cause of the overtorque.
UL3 (blinking) - Undertorque Det 1:
Meaning: There has been a current less than the setting in L6-02 for longer than the setting in L6-03.
Probable Causes: Check the settings in L6-02 and L6-03, and the mechanical system to correct the cause of the undertorque.
UL4 (blinking) - Undertorque Det 2:
Meaning: There has been a current less than the setting in L6-05 for longer than the setting in L6-06.
Probable Causes: Check the current setting in L6-05, time setting in L6-06, and the mechanical system to correct the cause of the undertorque.
oS (blinking) - Overspeed Det:
Meaning: The speed has been greater than the setting in F1-08 for longer than the setting in F1-09.
Probable Causes: Overshooting/undershooting, reference speed too high, inappropriate settings in F1-08 and F1-09.
Corrective Actions: Adjust gain, check reference circuit and gain, check settings in F1-08 and F1-09.
PGO (blinking) - PG Open:
Meaning: The PG is disconnected.
Probable Causes: Break in PG wiring, incorrect wiring, power not supplied to PG.
Corrective Actions: Fix broken/disconnected wiring, fix wiring, supply power properly.
dEu (blinking) - Speed Deviation:
Meaning: The speed deviation has been greater than the setting in F1-10 for longer than the setting in F1-11.
Probable Causes: Load too large, acceleration/deceleration time too short, load locked, inappropriate settings in F1-10 and F1-11.
Corrective Actions: Reduce load, lengthen acceleration/deceleration time, check mechanical system, check settings in F1-10 and F1-11.
OF0 (blinking) - Opt External Flt:
Meaning: External error detected for Communications Card other than SI-K2.
Probable Causes: Continuing operation specified for EF0 (F6-03 = 3) and an external fault was input from the Option Card.
Corrective Actions: Remove the cause of the external fault.
FbL (blinking) - Feedback Loss:
Meaning: PID Feedback Reference Lost.
Probable Causes: PID feedback reference loss detected, PID feedback input less than PID feedback loss detection level for longer than PID feedback loss detection time.
Corrective Actions: -.
CE (blinking) - Memobus Com Err:
Meaning: RS-422A/485 Communications Error.
Probable Causes: Normal reception not possible for 2 s or longer after received control data.
Corrective Actions: Check communications devices and signals.
bUS (blinking) - Option Com Err:
Meaning: Option Card Communications Error.
Probable Causes: Communications error in a mode where the run command or a frequency reference is set from a Communications Option Card.
Corrective Actions: Check communications devices and signals.
CALL (blinking) - ComCall:
Meaning: Communications on Standby.
Probable Causes: Control data not normally received when power was turned ON.
Corrective Actions: Check communications devices and signals.