Omron 3G3JX fault codes 2
Error Codes
> E 01, E 02, E 03, E 04: Overcurrent Trip
> If the motor is restrained, or rapidly accelerated or decelerated, a large current flows through the Inverter, which may result in breakdown. To avoid this, an overcurrent protection circuit works to shut off the Inverter output.
> E 05: Overload Trip
> If an Inverter output current is detected and the motor is overloaded, an electronic thermal inside the Inverter operates to shut off the Inverter output. After a trip occurs, normal operation is restored in 10 seconds by resetting the Inverter.
> E 07: Overvoltage Trip
> If the incoming voltage and regenerative energy from the motor are too high, a protection circuit works to shut off the Inverter output when the voltage on the converter exceeds the specified level.
> E 08: EEPROM Error
> Shuts off the output if an error occurs in the EEPROM built into the Inverter due to external noise and abnormal temperature rise. Check the set data again if the error occurs. If the power is shut off during data initialization, an EEPROM error may occur when the power is next turned on. Shut off the power after completing data initialization.
> E 09: Undervoltage Trip
> Shuts off the output if the incoming voltage drops below the specified level, causing the control circuit not to work properly during a momentary power interruption.
> E 11: CPU Error
> Shuts off the output if the internal CPU has malfunctioned. If the multi-function output terminal (relay terminal) is set to 05 (alarm), the signal may not be output during the CPU error. In this case, no data is stored in the trip monitor. The same thing could happen if AL (05) is allocated to the relay output terminal. Again, no data is stored.
> E 12: External Trip
> If an error occurs in the external equipment or devices, the Inverter receives the signal, and the output is shut off. (Available with the external trip function selected)
> E 13: USP Trip
> Appears if the Inverter is turned on with the RUN command being input. (Available with the USP function selected) If an undervoltage trip occurs with the USP terminal turned ON, a USP trip occurs after a trip reset. Reset again to release the trip.
> E 14: Ground Fault Trip
> Shuts off the output if a ground fault between the Inverter output unit and the motor is detected when turning on the power. The ground fault trip cannot be released with the reset input. Shut off the power and check the wiring.
> E 15: Incoming Overvoltage Trip
> Appears if the incoming voltage has remained high for 100 seconds while the Inverter output is stopped.
> E 21: Temperature Error
> Shuts off the output if the temperature has risen in the main circuit due to malfunction of the cooling fan or other reasons.
> E 30: Driver Error
> Shuts off the output if overcurrent is detected in the main circuit.
> E 35: Thermistor Error
> While the thermistor input function is used, this detects the resistance of the external thermistor and shuts off the Inverter output.
> E 37: Emergency Shutoff
> With the emergency shutoff selected (DIP switch on the control board SW8 = ON), this error appears when an emergency shutoff signal is input from multi-function input terminal 3.
> E 60: Communications Error
> Occurs when the communication watchdog timer times out.