Omron 3G3JX fault codes

Troubleshooting Guide
Situation: The motor doesn't work.
Possible cause: No voltage observed for Inverter outputs U/T1, V/T2, and W/T3.
Remedy:
> Check the A001 setting (frequency reference selection) and the A002 setting (RUN command selection).
> Ensure power is supplied to terminals R/L1, S/L2, and T/L3 (the POWER LED indicator should light up).
> Check the connections of terminals R/L1, S/L2, T/L3, and U/T1, V/T2, W/T3.
> If the display shows "E **", press the Mode key to confirm the status, then reset.
> Check the allocation of the multi-function inputs (C001 to C005) and ensure the RUN key (RUN command) is turned on.
> If using terminal mode, set the potentiometer to H/O/L and ensure FW (or RV) input is connected to terminal L or PCS.
> Turn off RS and FRS inputs if they are still turned on.
Situation: Voltage observed for Inverter outputs U/T1, V/T2, and W/T3.
Possible cause: The motor is restrained or overloaded.
Remedy:
> Release the restraint and reduce the load.
> Operate the motor separately.
Situation: Motor rotation is in reverse.
Possible cause: Incorrect connection of output terminals U/T1, V/T2, and W/T3.
Remedy:
> Connect according to the motor phase sequence (generally U/T1, V/T2, and W/T3 in forward).
> Check the control circuit terminal and ensure F004 is set correctly in the motor rotation direction selection via the Digital Operator.
Situation: Motor rotation speed does not rise.
Possible cause: Overloaded motor or faulty frequency setting unit.
Remedy:
> Replace the frequency setting unit.
> Reduce the load on the motor.
Situation: Rotation is unstable.
Possible cause: Variable load or power voltage, or specific frequency issue.
Remedy:
> Increase the capacity of both the motor and Inverter.
> Reduce the variation in load or power voltage.
> Finely adjust the output frequency.
Situation: Motor rotation doesn't match.
Possible cause: Incorrect maximum frequency setting or V/F pattern.
Remedy:
> Check the V/F pattern according to the motor specifications.
> Check the transmission gear ratio.
Situation: Data value is abnormal or does not change with data set.
Possible cause: Data not stored correctly after changing.
Remedy:
> Input data again and press the Enter key.
> Wait at least 6 seconds after changing data and pressing the Enter key before turning off the power.
Situation: Cannot change data, frequency, operate, or stop.
Possible cause: Incorrect selection between operator and terminal modes, soft lock activated, or tripped.
Remedy:
> Check the selections of the setting modes of A001 and A002.
> Reset the SFT terminal and set b031 to 00 or 01 if soft lock is activated.
> Reset the trip if tripped.
Note: Wait at least 6 seconds after changing data and pressing the Enter key to store it. The data may not be set correctly if any key is operated, the reset is performed, or the power supply is disconnected within 6 seconds.