Omron 3G3JV fault codes 2
10. Digital Operator Transmission Fault 1 (F00)
- Meaning: An initial memory fault has been detected.
+ Possible Causes and Solutions:
> Internal circuitry fault of the inverter. → Turn the inverter off and on. Replace the inverter if the same fault occurs again.
11. Digital Operator Transmission Fault 2 (F01)
- Meaning: A ROM fault has been detected.
+ Possible Causes and Solutions:
> Internal circuitry fault of the inverter. → Turn the inverter off and on. Replace the inverter if the same fault occurs again.
12. Initial Memory Fault (F04)
- Meaning: An error in the built-in EEPROM of the inverter has been detected.
+ Possible Causes and Solutions:
> Internal circuitry fault of the inverter. → Initialize the inverter with n01 set to 8 or 9 and turn the inverter off and on. Replace the inverter if the same fault occurs again.
13. Analog-to-Digital Converter Fault (F05)
- Meaning: An analog-to-digital converter fault has been detected.
+ Possible Causes and Solutions:
> Internal circuitry fault of the inverter. → Turn the inverter off and on. Replace the inverter if the same fault occurs again.
14. Digital Operator Fault (F07)
- Meaning: An error in the built-in control circuit of the Digital Operator has been detected.
+ Possible Causes and Solutions:
> Internal circuitry fault of the Digital Operator. → Turn the Digital Operator off and on. Replace the Digital Operator if the same fault occurs again.
15. Communications Time-Over (CE)
- Meaning: Normal RS-422/485 communications were not established within 2 seconds. The inverter will detect this error if n68 (RS-422/485 communications time-over detection selection) is set to 0, 1, or 2.
+ Possible Causes and Solutions:
> Short-circuit, ground fault, or disconnection on the communications line. → Check and correct the line.
> Incorrect termination resistance setting. → Set the termination resistance of only the inverter located at each end of the network to ON.
> Noise influence. → Do not wire the communications line along with power lines in the same conduit. Use twisted-pair shielded wire for the communications line, and ground it at the Master.
> Master's program error. → Check and correct the program so that communications will be performed more than once every 2-second period.
> Communications circuit damage. → If the same error is detected as a result of a self-diagnostic test, change the inverter.
16. Emergency Stop (STP)
- Meaning: An emergency stop alarm is input to a multi-function input.
+ Possible Causes and Solutions:
> Emergency stop alarm input to a multi-function input. → Remove the cause of the fault.
> Incorrect sequence. → Check and change the external fault input sequence, including the input timing and NO or NC contact.
17. OFF Power Supply Error
+ Possible Causes and Solutions:
> Insufficient power supply voltage, control power supply fault, hardware fault, no power supply provided. → Check and correct the power supply wire and voltage.
> Terminal screws are loosened. → Check and tighten the terminal screws.
> The Inverter is damaged. → Replace the Inverter.
18. Main Circuit Undervoltage (UV) (flashing)
- Meaning: The main circuit DC voltage has reached the undervoltage detection level.
+ Possible Causes and Solutions:
> Power supply to the Inverter has phase loss, power input terminal screws are loose, or the power line is disconnected. → Check the above and take necessary countermeasures.
> Incorrect power supply voltage. → Make sure that the power supply voltage is within specifications.
19. Main Circuit Overvoltage (flashing)
- Meaning: The main circuit DC voltage has reached the overvoltage detection level.
+ Possible Causes and Solutions:
> The power supply voltage is too high. → Decrease the voltage so it will be within specifications.
20. Radiation Fin Overheated (OH) (flashing)
- Meaning: The temperature of the radiation fins of the Inverter has reached 110°C ± 10°C.
+ Possible Causes and Solutions:
> The ambient temperature is too high. → Ventilate the Inverter or install a cooling unit.
21. Communications Standby (CAL) (flashing)
- Meaning: No normal DSR message has been received during RS-422/485 communications.
+ Possible Causes and Solutions:
> A short-circuit, ground fault, or disconnection has occurred on the communications line. → Check and correct the line.
> The termination resistance setting is incorrect. → Set the termination resistance of only the Inverter located at each end of the network to ON.
> Master's program error. → Check the start of communications and correct the program.
> Communications circuit damage. → If a CAL or CE error is detected as a result of a self-diagnostic test, change the Inverter.
22. Overtorque Detection (OL3) (flashing)
- Meaning: There has been a current or torque the same as or greater than the setting in n60 for overtorque detection level and that in n61 for overtorque detection time.
+ Possible Causes and Solutions:
> The mechanical system is locked or has a failure. → Check the mechanical system and correct the cause of overtorque.
> The parameter settings were incorrect. → Adjust the n60 and n61 parameters according to the mechanical system. Increase the set values in n60 and n61.
Sequence error (SER):
> Probable cause: A sequence change has been input while the Inverter is in operation.
> Remedy: Check and adjust the local or remote selection sequence as multi-function input.
External base block (bb):
> Probable cause: The external base block command has been input as multi-function input.
> Remedy: Remove the cause of external base block input. Check and change the external fault input sequence including the input timing and NO or NC contact.
Forward- and reverse-rotation input (EF):
> Probable cause: The forward and reverse commands are input to the control circuit terminals simultaneously for 0.5 s or more.
> Remedy: Check and adjust the local or remote selection sequence.
Emergency stop (STP):
> Probable cause: The emergency stop alarm signal is input as multi-function input. A multi-function input 1, 2, 3, or 4 set to 20 or 22 has been used.
> Remedy: Remove the cause of the fault. Check and change the external fault input sequence including the input timing and NO or NC contact.
Cooling fan fault (FAN):
> Probable cause: The cooling fan wiring has a fault, or the cooling fan is not in good condition or beyond repair.
> Remedy: Turn off the Inverter, dismount the fan, and check and repair the wiring. Check and remove foreign material or dust on the fan. Replace the fan if necessary.
Communications time-over (CE):
> Probable cause: A short-circuit, ground fault, or disconnection has occurred on the communications line. Noise influence. Master's program error.
> Remedy: Check and correct the line. Set the termination resistance of only the Inverter located at each end of the network to ON. Use twisted-pair shielded wire for the communications line and ground it at the Master. Check and correct the program so that communications will be performed more than once every 2-second period.
Operation error (OP):
> Probable cause: Parameter setting errors such as duplicated values for multi-function inputs, incorrect V/f pattern settings, rated motor current set exceeds 150% of the rated output current of the Inverter, frequency reference upper and lower limits do not satisfy the condition, or jump frequencies do not satisfy the condition.
> Remedy: Check and correct the respective values and settings to ensure they meet the required conditions.