Omron 3G3IV fault codes


OC (Overcurrent):
- Reasons: Short circuit or grounding fault in the inverter output, excessive load, or short acceleration/deceleration times, using an unsuitable motor for the inverter, operation of the magnetic contactor in the inverter output.
- Solutions: Reset the fault after correcting it. Ensure there is no short circuit or grounding fault in the inverter output before turning the power back on.

GF (Ground Fault):
- Reasons: Ground fault in the inverter output (may be due to motor burning, insulation wearing off, or damaged cable).
- Solutions: Reset the fault after correcting it. Ensure there is no short circuit or grounding fault in the inverter output before turning the power back on.

PUF (Fuse Blown):
- Reasons: Fuse blown in the main circuit, output transistor failure due to a short circuit or grounding fault in the inverter output.
- Solutions: Replace the inverter after correcting the cause.

Ou (Main Circuit Overvoltage):
- Reasons: Main circuit DC voltage exceeds the overvoltage detection level, short acceleration time, and excessive regenerative energy of the motor.
- Solutions: Increase the deceleration time or connect a braking resistor. Check and correct the motor grounding fault.

Uu1/Uu2/Uu3 (Main Circuit Low Voltage, Control Power Failure, Current Limitation Circuit Failure):
- Reasons: Main circuit DC voltage below the low voltage detection level, drop in control power supply voltage, magnetic contactor in the main circuit not working.
- Solutions: Reset the fault after correcting the cause. Improve the power supply environment. Replace the inverter.

PF (Main Circuit Voltage Error):
- Reasons: Main circuit DC voltage is abnormally fluctuating (not during regeneration).
- Solutions: Reset the fault after correcting the cause.

LF (Output Open-phase):
- Reasons: Open-phase in the inverter output.
- Solutions: Reset the fault after correcting the cause. Check the capacities of the motor and inverter.

oH/oH1 (Cooling Fin Overheat):
- Reasons: The temperature of the inverter's cooling fins exceeds the set value or exceeds 100°C.
- Solutions: Install a cooling unit, remove the heat source, replace the cooling fan.

Fan (Inverter Cooling Fan Error):
- Reasons: The inverter's cooling fan has stopped or the heat sink is blocked.
- Solutions: Replace the cooling fan, clean the heat sink.

oH3/oH4 (Motor Overheat Alarm/Fault):
- Reasons: Motor has overheated.
- Solutions: Check the load size, acceleration/deceleration, and cycle times. Check the V/f characteristics. Check the motor temperature input and the setting of the motor's nominal current.

rH/rr (Mounted Brake Resistor Overheat/Internal Brake Transistor Error):
- Reasons: Brake resistor overheated, brake transistor not working properly.
- Solutions: Reduce the load, increase deceleration time, or reduce motor speed. Turn the power supply on and off. Replace the inverter.

oL1/oL2 (Motor/Inverter Overload):
- Reasons: Motor or inverter overloaded.
- Solutions: Check the load size and acceleration/deceleration times. Use the speed search function and adjust settings. Increase the inverter capacity.

oL3/oL4 (Over-torque Detected 1/2):
- Reasons: More current than the set current for a certain period.
- Solutions: Make sure the L6-02 and L6-03 settings are correct. Check the mechanical system and correct the cause of the over-torque.

UL3 (Insufficient Torque Detected 1/2):
- Reasons: Less current than the set current for a certain period.
- Solutions: Make sure the L6-02 and L6-03 settings are correct. Check the mechanical system and correct the cause of insufficient torque.

oS (Over Speed):
- Reasons: Speed exceeded the value set in F1-08 for longer than the value set in F1-09.
- Solutions: Readjust the gain. Check the reference circuit and reference gain. Check the F1-08 and F1-09 settings.