Alpha AL2-2TC-ADP


The Mitsubishi Alpha 2 AL2-2TC-ADP is a thermocouple input adapter designed for use with K-type thermocouple sensors. It converts the thermocouple sensor’s temperature readings into a 0-10V analog signal for processing by the Alpha 2 series controller. This module is used in conjunction with the Alpha 2 series (version 2.0 or later) DC-powered controllers to enable precise temperature measurement and control. Below is a detailed breakdown of the key features and functionality of the AL2-2TC-ADP for electrical technicians:

    K-Type Thermocouple Compatibility: The AL2-2TC-ADP supports K-type thermocouple sensors, which are widely used in industrial applications due to their broad temperature range and accuracy. These sensors conform to the JIS 1602-1995 (IEC 584-1 1977, IEC 584-2 1982) standards, ensuring reliable temperature measurements.

    Two Input Channels: The module features two separate input terminals, each designed to accept a K-type thermocouple sensor. This allows it to process data from two different temperature measurement points simultaneously.

    0-10V Analog Output: The thermocouple input is amplified and converted to a 0-10V analog signal that can be processed by the Alpha 2 series controller. This makes it easy to integrate temperature data into the controller’s logic for further processing, monitoring, or control tasks.

Configuration and Modes:

    Analog Input Modes: The Alpha 2 series controllers can be configured to operate in three different analog input modes:
        Normal Mode: For processing standard analog signals.
        TC Mode (Thermocouple): For processing temperature data from thermocouple sensors using the AL2-2TC-ADP.
        PT100 Mode: For use with PT100 temperature sensors via the AL2-2PT-ADP module.

Calibration and Adjustments:

To ensure accurate temperature measurements, the AL2-2TC-ADP module offers both offset and gain calibration features, as well as fine adjustment capabilities.

    Offset Calibration (Stop Mode Only):
        Before performing offset calibration, refer to the Alpha 2 Hardware Manual to prepare the module for calibration.
        Set the input mode to TC (thermocouple) in the analog input settings menu.
        Choose -50°C in the Calibrate menu to complete the offset calibration. This process adjusts the baseline temperature measurement.

    Gain Calibration (Stop Mode Only):
        Gain calibration ensures that the thermocouple input provides accurate measurements at higher temperatures.
        In the Calibrate menu, set the temperature to 450°C for the K-type thermocouple input. This ensures that the readings at the higher end of the thermocouple's range are accurate.

    Fine Offset Adjustment (OffsetFine):
        The OffsetFine adjustment allows you to make small, precise changes to the offset value. This can be done in both Run and Stop modes, allowing for real-time adjustments if necessary. Use the + and - buttons to fine-tune the offset value.

Applications:

    Temperature Monitoring and Control: The AL2-2TC-ADP is ideal for applications requiring precise temperature monitoring and control, particularly in industrial environments where K-type thermocouples are commonly used. This could include process control, HVAC systems, or any system where temperature regulation is crucial.

    Multi-Point Temperature Sensing: With its dual input channels, the module allows for monitoring of two different temperature points simultaneously, which is useful for complex systems requiring temperature measurements at multiple locations.

Installation and Setup:

    Easy Integration: The AL2-2TC-ADP can be easily installed on any Alpha 2 series controller (version 2.0 or later). Configuration and calibration are performed through the controller’s user interface, making it simple to set up and adjust.

    Mode Switching: To switch between different modes (Normal, TC, PT100), use the controller’s TopMenu and navigate to the Analog Input settings in stop mode. From there, you can select the appropriate mode based on the input type.

The Mitsubishi Alpha 2 AL2-2TC-ADP thermocouple input adapter provides a reliable and efficient solution for integrating K-type thermocouple sensors into the Alpha 2 series controllers. It converts the temperature data into a 0-10V analog signal, allowing the controller to process and manage temperature readings with high accuracy. With features like offset and gain calibration, along with fine-tuning capabilities, this module ensures precise temperature control in various industrial applications.

>> Alpha AL2-2TC-ADP User manual (pdf)

----------

+ Mitsubishi Automation Homepage

+ Mitsubishi Electric Contact (for Automation Mall)

+ About Mitsubishi Electric

Reminder: Alpha AL2-2TC-ADP and other Mitsubishi PLC modules are available for sale at Otomasyon Mall. Please note that some of the devices are used products, so take this into consideration when purchasing. However, once products are out of stock, new ones will not be restocked. The information above is based on general knowledge and does not guarantee accuracy. For more detailed and precise information, it is recommended to refer to the relevant device’s user manual. 02.09.2012 

"Please note: The user manuals, commissioning suggestions, error codes, and solution recommendations provided on this page are not binding. The information and documents above are open to and even in need of improvement. As the Otomasyon Mall Community, we gladly welcome your suggestions and contributions. If you have field experience and insights on ease of use, please do not hesitate to share them with us."