Alpha AL2-2PT-ADP

The Mitsubishi Alpha 2 Smart Relay AL2-2PT-ADP is a PT100 input adapter designed to process data from PT100 temperature sensors. This module is compatible with 100Ω 3-wire PT100 temperature sensors, commonly used in industrial environments for precise temperature monitoring and control. Below is a detailed explanation of the module's key features and usage for electrical technicians:

    PT100 Sensor Support: The AL2-2PT-ADP module is compatible with 3-wire PT100 temperature sensors with a 100Ω resistance and a temperature coefficient of 3.850 ppm/°C. These sensors follow the JIS C1604-1997 (IEC 751) standard, which ensures high accuracy and reliability in temperature measurement.

    Analog Input Modes: The Alpha 2 series controllers offer three different modes for configuring analog inputs:
        Normal Mode: For general analog signals.
        PT100 Mode: Specifically for processing data from PT100 temperature sensors.
        TC Mode: For thermocouple sensors, used with the AL2-2TC-ADP module.

Calibration of PT100 Inputs:

    Offset Calibration (Stop Mode Only):
        Before calibration, follow the instructions in the Alpha 2 Hardware Manual to prepare the hardware.
        Once the mode is set to PT100, select Calibrate from the analog input settings menu and choose -50°C to complete the offset calibration.

    Gain Calibration (Stop Mode Only):
        The gain calibration ensures accuracy at higher temperatures. For PT100 sensors, choose 200°C in the Calibrate menu to complete the gain calibration.

    Fine Offset Adjustment (OffsetFine):
        The OffsetFine adjustment can be made in both Run and Stop modes. This feature allows fine-tuning of the offset value using the + and - buttons, making it particularly useful for precise temperature measurements.

Applications:

    Temperature Monitoring and Control: The AL2-2PT-ADP module is ideal for applications that require precise temperature monitoring and control. It processes data from PT100 sensors, which are commonly used in industrial systems like heating, cooling, or process control.

    Industrial Automation: In industrial automation, this module is used for monitoring temperature changes in critical systems. By integrating PT100 sensors, it allows for accurate control in applications such as temperature-sensitive processes or environmental control systems.

Calibration Steps:

    Mode Selection (Stop Mode Only):
        While in stop mode, select Others... from the menu and navigate to Analog Input. Choose PT100 mode from the available options to configure the input for PT100 sensors.

    Offset and Gain Calibration:
        The offset calibration ensures accurate measurements at lower temperatures (e.g., -50°C), while the gain calibration provides accuracy at higher temperatures (e.g., 200°C for PT100). Both steps are crucial for reliable temperature readings.

    Fine Offset Adjustment:
        Once calibration is complete, OffsetFine can be used to make small adjustments to the sensor readings in real-time, providing enhanced accuracy.


The Mitsubishi Alpha 2 AL2-2PT-ADP PT100 input adapter is designed to process temperature data from PT100 sensors, offering precise and reliable temperature measurement and control. It works with the Alpha 2 series controllers, allowing for easy integration and configuration. With support for offset and gain calibration, this module ensures accurate temperature readings across a wide range of industrial applications. The AL2-2PT-ADP is ideal for environments requiring accurate and continuous temperature monitoring, such as HVAC systems, process control, or other temperature-critical industrial processes.


>> Alpha AL2-2PT-ADP User manual (pdf)

----------

+ Mitsubishi Automation Homepage

+ Mitsubishi Electric Contact (for Automation Mall)

+ About Mitsubishi Electric

Reminder: Connectors and other Mitsubishi PLC modules are available for sale at Otomasyon Mall. Please note that some of the devices are used products, so take this into consideration when purchasing. However, once products are out of stock, new ones will not be restocked. The information above is based on general knowledge and does not guarantee accuracy. For more detailed and precise information, it is recommended to refer to the relevant device’s user manual. 02.09.2012 

"Please note: The user manuals, commissioning suggestions, error codes, and solution recommendations provided on this page are not binding. The information and documents above are open to and even in need of improvement. As the Otomasyon Mall Community, we gladly welcome your suggestions and contributions. If you have field experience and insights on ease of use, please do not hesitate to share them with us."