MICREX-SX SPH — NP1PH-08 / NP1PH-16
NP1PH-08 and NP1PH-16: MICREX-SX SPH200 CPUs
NP1PH-08 and NP1PH-16 are CPU modules in Fuji’s modular MICREX-SX SPH200 family. The CPU code alone does not set the machine’s I/O count; field signals enter through separate I/O modules. One important difference is program memory: Fuji lists 8,192 steps for NP1PH-08 and 16,384 steps for NP1PH-16.
What does the speed figure measure?
Fuji quotes 70 ns or more per sequence instruction for SPH200. This is not the scan time of the whole PLC application. Program size, I/O updates and communications affect the complete cycle. NP1PS SPH300 CPUs have a different processor and memory class; match installed rack parts by code.
Loading and backing up the program
Fuji’s table shows no built-in USB or Ethernet on NP1PH-08/16. Verify the actual programming port and cable on the installed unit; do not assume a direct USB connection. Preserve the project, module order and addressing before a CPU swap. Engineering tools sit under Fuji PLC software and manual titles under PLC CPU documents.
The broader family is under MICREX-SX SPH, with CPU and basic-unit distinctions in Fuji PLC CPUs.
Fuji’s table lists IL, ST, LD, FBD and SFC programming for SPH200. A useful backup includes the program and system definition, not only a note of CPU step capacity. If remote I/O is fitted, include its network arrangement in the replacement checks.