Gd200 fault codes
INVT GD200A Fault Codes and Troubleshooting
A GD200A trip should be treated as a diagnostic event, not simply as a message to clear from the keypad. Before resetting the drive, note the displayed code and check what the machine was doing when the fault occurred.
The INVT GD200A fault-tracking section explains how to reset a trip, review stored fault records and follow the basic troubleshooting sequence when the motor does not run or operates with abnormal vibration.
Safety note: Electrical inspection and maintenance of the VFD should only be carried out by qualified electrical personnel. Read the safety precautions for the drive before working on the power or motor circuits.
Resetting a GD200A Fault
After the cause of the trip has been corrected, the GD200A can be reset in several ways:
- Press the STOP/RST key on the operator panel
- Use a digital input assigned to the reset function
- Cycle drive power when appropriate
Do not restart the motor until the original fault condition has been removed.
Using the GD200A Fault History
The GD200A stores recent fault information in the P07 parameter group. This is particularly useful for intermittent faults that disappear after the drive is reset.
P07.27-P07.32 - Stores the six most recent faults
P07.33-P07.40 - Operating data recorded for the latest fault
P07.41-P07.48 - Operating data recorded for the previous fault
P07.49-P07.56 - Operating data recorded for the third most recent fault
For recurring trips, compare the stored operating values with the actual motor load, supply condition and machine state before changing parameters.
Recommended Fault-Checking Sequence
1. Check the operator panel and keypad connection.
2. Review the recorded fault information in the P07 group.
3. Compare the stored values with the actual operating conditions at the time of the trip.
4. Identify the likely cause of the displayed fault code.
5. Correct the fault before applying a reset.
6. Restart the drive only after confirming that the abnormal condition has been removed.
OUt1 - IGBT U-Phase Fault
Possible causes:
- Acceleration is too fast.
- The IGBT power module may be faulty.
- Electrical interference may cause incorrect operation.
- Drive or motor power wiring may be loose or incorrectly connected.
- Grounding may be inadequate.
Checks and corrective actions:
Increase the acceleration time. Check the power unit and motor wiring. Inspect grounding and look for strong interference from nearby electrical equipment.
OUt2 - IGBT V-Phase Fault
OUt2 indicates an abnormal condition associated with the V-phase IGBT output stage.
Apply the same basic checks used for OUt1: acceleration time, IGBT power stage, motor wiring, grounding and external electrical interference.
OUt3 - IGBT W-Phase Fault
OUt3 refers to the W-phase IGBT output stage. Inspect the output wiring and power stage and confirm that the acceleration ramp is not excessively short for the connected load.
OC1 - Overcurrent During Acceleration
OC1 is generated when the GD200A detects excessive current while the motor is accelerating.
Possible cause shown in the GD200A fault-tracking guide:
The acceleration or deceleration ramp may be too fast for the operating condition.
Checks and corrective actions:
Increase the ACC acceleration time and check the incoming power supply.
GD200A Powers Up but the Motor Does Not Run
The GD200A troubleshooting flow does not assume that a stationary motor automatically means a failed VFD. The recommended diagnosis starts at the incoming supply and follows the control chain toward the motor and mechanical load.
Check the drive power first
Confirm that the POWER indication is present and that the keypad display is active. Check whether the input-side contactor has closed correctly.
Measure the R-S-T input supply
If the drive does not operate normally, verify the R, S and T input voltages with a suitable meter.
Look for an active fault
If the keypad displays an alarm or fault message, resolve that condition before continuing with the start-command checks.
Verify the run-command source
The GD200A may receive its running command from the keypad, control terminals or a communication network. Make sure the selected command channel matches the actual machine wiring and control method.
Keypad operation:
Press RUN and check whether the drive starts normally.
Terminal operation:
Check the assigned digital input and its control voltage.
Communication operation:
Check the communication parameters and network configuration.
Check the speed reference
A valid RUN command will not produce useful motor operation if the commanded frequency or speed reference is incorrect.
Check the U-V-W output
If the run command and speed reference are correct, inspect the VFD output to the motor. An abnormal or missing U-V-W output may indicate a drive-side problem.
Verify the motor configuration
Make sure the selected motor type and motor parameters correspond to the motor actually connected to the drive.
Check the mechanical load
If the electrical conditions are normal, confirm that the motor is not being prevented from rotating by an overloaded, jammed or locked mechanical system.
Motor Vibration or Abnormal Noise
If the motor runs but produces abnormal vibration or noise, the GD200A troubleshooting chart recommends checking the system in the following order:
1. Verify the motor type and motor parameters.
2. Perform the appropriate motor parameter autotune if required.
3. If V/F control is being used, check the V/F-related vibration settings.
4. Determine whether the vibration is caused by an unstable reference frequency.
5. Inspect the mechanical load for vibration, looseness or irregular movement.
6. If the motor and mechanical system are normal but the problem remains, investigate the VFD.
This sequence is especially important when a replacement motor has been installed or when a GD200A has been moved from another machine. In these cases, the stored motor configuration may no longer match the connected motor.
INVT GD200A User Manual
+ INVT GD200A User Manual (PDF)
Related INVT GD200A Pages
+ INVT General Fault Codes and Troubleshooting
+ INVT Commissioning and Application Notes