IC697VDD100

Digital Input Board Overview

The Digital Input Board is a 64-channel, optically isolated digital input board capable of detecting Changes of State (COS) on any of the 64 inputs. This COS data can be utilized in Sequence of Events (SOE) acquisition, making it ideal for event-driven systems. The board offers pulse accumulation data, time tag data, and programmable debounce for each input, along with various interrupt options. For detailed information, refer to Figure 1-1 on page 1-4.

Key Features of the Digital Input Board

  • 64 optically isolated inputs
  • Multiple functions per channel:
    • COS detection
    • SOE reporting
    • Pulse accumulation reporting
    • Time tag reporting
    • Programmable debounce times
  • Available in 24 VDC or 18 VAC options
  • Voltage sensing
  • 1000 VDC or 700 VRMS channel-to-channel and channel-to-VMEbus isolation (1 minute)
  • Pulse accumulation for up to 65,535 pulses per channel
  • SOE monitoring on a channel-by-channel basis
  • Debounce time software-controlled on a channel-by-channel basis
  • COS monitoring software-controlled on a channel-by-channel basis
  • A24/A16 addressing capability
  • Supports supervisory bus access, nonprivileged bus access, or both
  • Release-On-Acknowledge (ROAK) interrupts on all VMEbus levels

Functional Description

The Digital Input Board provides COS detection for all 64 inputs. Each input can be configured via software to detect rising edges, falling edges, or both. Alternatively, it can be configured to ignore all changes for a specific channel. The board also supports various reporting and interrupt functionalities.

Each COS event can be stored in an SOE buffer, where it is time-tagged with a relative timer value (up to 65,535 ms). The timer can be reset via the VMEbus. Additionally, each COS event is recorded in the Pulse Accumulation Count registers, which track the number of events per channel.

VMEbus interrupts are available on any level, selectable via software, with a single byte vector placed on the bus during the acknowledge cycle. The interrupt is cleared automatically during the acknowledge (Release-On-Acknowledge or ROAK). Addressing is jumper-selected, supporting both A24 and A16 address spaces.

Address modifiers are also jumper-selected, supporting nonprivileged access, supervisory access, or both. After a system reset, the board performs a self-test, setting the Self-Test Complete bit in the Control and Status Register (CSR) when the test is finished.

Default Board Initialization

The Fail LED is ON

All interrupts are disabled

All flags are cleared

Test mode is enabled

The Interrupt Vector Register (IVR) is cleared

The COS registers are cleared

Pulse Accumulation Interrupt (PAI) registers are cleared

The Input Debounce/Select Registers (DSRs) are cleared

Input Pulse Accumulation Count (PAC) registers are cleared

The time tag clock is set to zero (0) and stopped

SOE maximum count is cleared

SOE count is cleared

SOE buffers contain test data if the self-test fails; otherwise, the buffers are cleared

The Self-Test Complete bit is set in the CSR

>> GE Fanuc IC697VDD100 User manual (pdf)

++ Other 90-30 PLC modules

----------

+ Ge-Fanuc 2 Homepage

+ Ge-Fanuc Contact (for Automation Mall)

+ About Ge-Fanuc

Reminder: GE Fanuc IC697VDD100 and other Ge-Fanuc modules are available for sale at Otomasyon Mall. Please note that some of the devices are used products, so take this into consideration when purchasing. However, once products are out of stock, new ones will not be restocked. The information above is based on general knowledge and does not guarantee accuracy. For more detailed and precise information, it is recommended to refer to the relevant device’s user manual. 06.03.2013 

"Please note: The user manuals, commissioning suggestions, error codes, and solution recommendations provided on this page are not binding. The information and documents above are open to and even in need of improvement. As the Otomasyon Mall Community, we gladly welcome your suggestions and contributions. If you have field experience and insights on ease of use, please do not hesitate to share them with us."