IC697PWR711
Power Supply Module, 100W, 120/240 VAC or 125 VDC (IC697PWR711/IC697PWR713)
This power supply module is designed for Series 90-70 programmable controller systems and is rack-mounted, fitting into the leftmost slot of the rack. It can operate with either AC or DC inputs. Below are its key features:
Features:
- Operates with 120 VAC, 240 VAC, or 125 VDC.
- Provides +5V output at 20 amps, +12V output at 2 amps, and -12V output at 1 amp.
- Equipped with electronic short-circuit and overcurrent protection.
- Can power two racks with a single power supply.
- Power Factor Correction for AC operation.
- Includes a jumper for overvoltage protection devices.
Power Supply Operation:
This power supply can operate with either 120 VAC or 240 VAC nominal inputs and will also work with a nominal 125 VDC source. The operational voltage range is 90 VAC to 264 VAC and 100 VDC to 150 VDC. Active Power Factor Correction circuits help maintain a near-unity power factor for AC inputs, avoiding the need for oversized circuit breakers or wiring.
Overvoltage Protection:
An electronic shutdown circuit protects the system from voltages exceeding 6.2 volts. The system includes a backup voltage clamp for sustained overvoltage conditions. If the overvoltage is caused by internal faults, the fuse may open.
Overcurrent Protection:
Each of the three outputs includes an electronic current limit. An overload on any output may cause voltage collapse across all outputs. Normal operation resumes once the overload is removed, though cooling time may be necessary for components to recover.
Dual Rack Operation:
A single power supply can support two racks under the following conditions:
- Only 5V power is required for the second rack.
- The total current draw for both racks is less than 5.2 amps.
- The racks are mounted close enough to connect using a 3-foot power cable.
The power cable carries the +5V power bus and power sequencing signals. A 9-pin D-type connector is used for the interconnection. Note that communication and bus interface modules between the racks must be provided separately.
Mounting and Field Wiring:
The power supply is installed in the leftmost slot of any standard IC697 rack or VME integrator's rack. The power input terminal board has four terminals. L1 and N are for 120/240 VAC or 125 VDC input connections. Terminals three and four are for ground and overvoltage protection.
It is recommended that the ground terminal be connected to the ground on the rack and earth using AWG #12 (3.3 mm²) copper wire.