IC697MDL940

Relay Output, 16 Point Module

    16 points: 8 isolated Form C and 2 groups of 4 Form A
    2 amps per point switching capacity
    RC snubber and fuse protection for each point
    No external power supply required for operation
    Removable field wiring terminal

The IC697MDL940 is a versatile 16-point Relay Output Module that can switch various low to medium power loads such as relays, contactors, and lamps. The module is designed with 2 amps per point switching capacity for 120/240 VAC or 24 VDC, and 0.2 amps per point for 125 VDC. Each relay coil is powered by the module itself, and each output is individually fused with a 3 amp fuse and equipped with an RC snubber to reduce noise transients.

LED indicators display the ON-OFF status for each output on the logic (PLC) side of the circuit. The module’s removable terminal board simplifies field wiring, while the mechanical keying feature ensures correct replacement with a similar module type.

I/O references are user-configurable without jumpers or DIP switches, and configuration is done using MS-DOS or Windows programming software over Ethernet TCP/IP or through the SNP port.


Output Protection:

    Fusing: Each output is protected with a 3 amp fuse. Recommended replacements are:
        3AG - 3.0 amp, 250V, Fast Acting
        Metric 5 x 20 mm - 3.0 amp, 250V, Fast Acting

    Suppression: Each output has an RC snubber for high-frequency noise suppression. It is recommended to add suppression at the load to enhance the system's reliability and contact life.


Fault Mode Selection:

The module can be configured so that output points either:

    Maintain the existing output state, or
    Turn outputs OFF.

More details can be found in the Programming Software User’s Manual.


Mechanical Keying:

The module includes a mechanical key to prevent incorrect insertion into a slot designed for another module type. When installed, the key stays attached to the backplane and ensures only the correct module type is inserted into the slot.


Field Wiring:

The removable terminal board can handle wire sizes from AWG #22 (0.36 mm²) to AWG #14 (2.1 mm²). Up to 40 wires of the same size can be routed through the terminal board cavity, and cable ties can secure the wire bundle.


Electrical Specifications:
Parameter    Details
Relay Type    Fixed coil, moving armature
Outputs per Module    16 (8 points - Form C, 2 groups of 4 points - Form A)
Isolation    1500 volts (output to backplane), 500 volts (between Form C circuits or Form A groups)
Maximum Load Current (Resistive)    16 amps per module, 4 amps per group (Form A)
Output Switching Characteristics    Nominal voltage rating: 120/240 VAC or 5/24/125 VDC
Maximum Power    480 VA (AC loads) or 60 watts (DC loads)
Max Load Current (Resistive)    2 amps at 5-265 VAC (47-63 Hz), 2 amps at 5-30 VDC, 0.2 amps at 31-125 VDC
Minimum Load Current    10 mA
Output Leakage Current    1 mA at 120 VAC
Response Time-On    10 ms maximum
Response Time-Off    10 ms maximum
Switching Frequency    20 cycles/minute (inductive load)
Contact Type    Silver alloy
Contact Resistance    0.2 ohms maximum
Contact Life    Mechanical: 20 million operations, Electrical: 10⁵ operations at rated load
Protection (per output)    3 amp fuse, Snubber (R = 47 ohms, C = 0.015 μF)
Current Required from 5V Bus    750 mA

The module supports the VME standard C.1 for system compatibility. For installations requiring compliance with FCC or European Union standards, refer to the installation guidelines.

>> GE Fanuc IC697MDL940 User manual (pdf)

++ Other 90-30 PLC modules

----------

+ Ge-Fanuc 2 Homepage

+ Ge-Fanuc Contact (for Automation Mall)

+ About Ge-Fanuc

Reminder: GE Fanuc IC697MDL940 and other Ge-Fanuc modules are available for sale at Otomasyon Mall. Please note that some of the devices are used products, so take this into consideration when purchasing. However, once products are out of stock, new ones will not be restocked. The information above is based on general knowledge and does not guarantee accuracy. For more detailed and precise information, it is recommended to refer to the relevant device’s user manual. 06.03.2013 

"Please note: The user manuals, commissioning suggestions, error codes, and solution recommendations provided on this page are not binding. The information and documents above are open to and even in need of improvement. As the Otomasyon Mall Community, we gladly welcome your suggestions and contributions. If you have field experience and insights on ease of use, please do not hesitate to share them with us."