IC697MDL753
5/48 Volt DC 0.5 Amp Negative Logic, 32-Point Output Module
32 output points divided into two isolated groups of 16 points each
0.5 Amp capacity per point
High inrush capacity (10x rated current)
The 5/48 Volt DC 0.5 Amp Negative Logic Output Module provides 32 output points split into two isolated groups. This module operates over a wide range of voltages, from 5 volts DC to 10-60 volts DC, making it versatile for various industrial applications.
It offers a high inrush current capacity, making it suitable for loads with high inrush characteristics such as inductive and incandescent devices. The module is also compatible with TTL level devices.
LED indicators show the ON-OFF status of each point on the logic (PLC) side, located at the top of the module. The module is mechanically keyed to ensure correct replacement and is user-configurable without the need for jumpers or DIP switches.
Output Characteristics:
This module is compatible with various types of load devices, including:
Solenoids
Motor starters
Indicators
TTL interfaces
Each point has a 0.5 Amp capacity for long-term operation. The module can handle surge currents greater than the rated capacity, though the repetition rate depends on the duty cycle of the device. For incandescent devices with a 50% duty cycle, the following repetition rates apply:
Steady-State Current (mA) Repetition Rate (Hz)
100 5.0
250 1.0
500 0.1
Fault Mode Selection:
The output module can be configured so that the output points respond to specific fault conditions by either:
Maintaining the existing output state
Turning outputs OFF
For more detailed configuration information, refer to the Programming Software User’s Manual.
Fusing:
This module does not have internal fuses. If protection is required, external fuses can be added by the user. Recommended fuses include:
Littlefuse 312.750 (3/4 amp, 250 volts, Fast Acting)
Bussmann AGC-3/4 (3/4 amp, 250 volts, Fast Acting)
Mechanical Keying:
This module includes a mechanical key to prevent incorrect module substitution in a slot. The key latches onto the backplane center rail during installation and remains there if the module is removed. It ensures that only identical module types can be installed in the same slot.
Field Wiring:
Each group of 16 outputs is isolated from the other. A wire from the power source to the power input terminal for each group is required, as the power input terminals are not connected inside the module. The detachable terminal board can accept wires sized AWG #22 (0.36 mm²) to AWG #14 (2.10 mm²), and up to two wires of the same size can be connected to a single terminal.
Removing an I/O Module:
To remove the module:
Grasp the board cover firmly at the top and bottom.
Squeeze the rack clips on the back to disengage the module from the rail.
Pull the board out of the connector and slide it out of the rack.
Specifications:
Parameter Specification
Rated Voltage 5 volts DC (±5%) or 10 to 60 volts DC
Outputs per Module 32 (two groups of 16 outputs each)
Isolation 1500 volts (output to backplane), 500 volts between groups
Output Voltage Range 5 volts or 10 to 60 volts
Output Current 0.5 amps per point, 4 amps per group
Inrush Current 5 amps maximum for 20 ms (10 to 60 volts DC)
Output Voltage Drop 0.5 volts max (5 volts DC), 1 volt max (10 to 60 volts DC)
Response Time 1 ms typical (ON and OFF)
Output Leakage 250 µA max (5 volts DC), 1 mA max (10 to 60 volts DC)
Current from 5V Bus 0.25 amp
This module is ideal for applications that require high inrush capacity and isolated outputs in negative logic circuits.
>> GE Fanuc IC697MDL753 User manual (pdf)
----------