IC697MDL750
24/48 Volt DC, 0.5 Amp, 32-Point Output Module
32 output points divided into four isolated groups of 8 points each
0.5 amp capacity per point
High inrush capacity (20 times the rated current)
The 24/48 Volt DC 0.5 Amp Output Module for the Programmable Logic Controller (PLC) provides 32 output points, divided into four isolated groups. This module supports high inrush current, making it suitable for various loads with such characteristics. LED indicators are present at the top of the module, showing the ON-OFF status of each point on the logic (PLC) side of the circuit.
The module is mechanically keyed to ensure the correct replacement with a similar module type in the field. I/O references are user-configurable without using jumpers or DIP switches.
The module configuration is done using MS-DOS or Windows programming software, running on Windows 95 or Windows NT, over Ethernet TCP/IP or via the SNP port.
Output Characteristics:
This module is compatible with various load devices such as:
Solenoids
Motor starters
Indicators
Each point has a 0.5 amp current capacity, and the module can transiently conduct a higher surge current. For incandescent devices operating at a 50% duty cycle, typical repetition rates are:
Steady-State Current (mA) Repetition Rate (Hz)
100 5
250 1
500 0.1
Fault Mode Selection:
This output module can be configured from the programmer so that output points assume one of two states in response to certain operating or default conditions:
Maintain existing output state
Turn outputs OFF
For more detailed information, refer to the Programmable Controllers Reference Manual.
Fusing:
This module does not contain internal fuses. However, if protection is required, an external fuse can be connected. Recommended fuses include:
Littlefuse 312.750 (3/4 amp, 250 volt, Fast Acting)
Bussmann AGC-3/4 (3/4 amp, 250 volt, Fast Acting)
Mechanical Keying:
The module has a mechanical key to prevent the incorrect substitution of one module type for another. The key fits a uniquely shaped area on the board below the connector, remaining in place when the module is removed.
Field Wiring:
The module is wired as shown in Figure 2. Each group of eight outputs is isolated, requiring a wire from the power source to the power input terminals for each group. The terminal board accepts wire sizes from AWG #22 (0.36 mm²) to AWG #14 (2.1 mm²).
Removing the I/O Module:
To remove an I/O module from its slot in a rack:
Grasp the board firmly at the top and bottom.
Squeeze the rack clips to disengage the module from the rail.
Slide the board along the card guide and remove it from the rack.
Specifications:
Parameter Specification
Rated Voltage 24 or 48 volts DC
Outputs per Module 32 (four groups of 8 outputs each)
Isolation 1500 volts (output to backplane), 500 volts (between groups)
Output Voltage Range 20 to 60 volts
Output Current 0.5 amps per point, 2 amps per group
Inrush Current 10 amps maximum for 20 ms
Output Voltage Drop 1 volt (2 ohms) maximum
Response Time-On 1 ms maximum
Response Time-Off 1 ms maximum
Output Leakage Current 1 mA maximum
Current Required from 5V Bus 0.25 amps
This module is compatible with the VME system and is designed to meet VME standard C.1.
For installations requiring compliance with FCC or European Union Directives, refer to Installation Requirements for Conformance to Standards.