IC697MDL750

24/48 Volt DC, 0.5 Amp, 32-Point Output Module

    32 output points divided into four isolated groups of 8 points each
    0.5 amp capacity per point
    High inrush capacity (20 times the rated current)

The 24/48 Volt DC 0.5 Amp Output Module for the Programmable Logic Controller (PLC) provides 32 output points, divided into four isolated groups. This module supports high inrush current, making it suitable for various loads with such characteristics. LED indicators are present at the top of the module, showing the ON-OFF status of each point on the logic (PLC) side of the circuit.

The module is mechanically keyed to ensure the correct replacement with a similar module type in the field. I/O references are user-configurable without using jumpers or DIP switches.

The module configuration is done using MS-DOS or Windows programming software, running on Windows 95 or Windows NT, over Ethernet TCP/IP or via the SNP port.


Output Characteristics:

This module is compatible with various load devices such as:

    Solenoids
    Motor starters
    Indicators

Each point has a 0.5 amp current capacity, and the module can transiently conduct a higher surge current. For incandescent devices operating at a 50% duty cycle, typical repetition rates are:


Steady-State Current (mA)    Repetition Rate (Hz)
100    5
250    1
500    0.1


Fault Mode Selection:

This output module can be configured from the programmer so that output points assume one of two states in response to certain operating or default conditions:

    Maintain existing output state
    Turn outputs OFF

For more detailed information, refer to the Programmable Controllers Reference Manual.


Fusing:

This module does not contain internal fuses. However, if protection is required, an external fuse can be connected. Recommended fuses include:

    Littlefuse 312.750 (3/4 amp, 250 volt, Fast Acting)
    Bussmann AGC-3/4 (3/4 amp, 250 volt, Fast Acting)


Mechanical Keying:

The module has a mechanical key to prevent the incorrect substitution of one module type for another. The key fits a uniquely shaped area on the board below the connector, remaining in place when the module is removed.


Field Wiring:

The module is wired as shown in Figure 2. Each group of eight outputs is isolated, requiring a wire from the power source to the power input terminals for each group. The terminal board accepts wire sizes from AWG #22 (0.36 mm²) to AWG #14 (2.1 mm²).


Removing the I/O Module:

To remove an I/O module from its slot in a rack:

    Grasp the board firmly at the top and bottom.
    Squeeze the rack clips to disengage the module from the rail.
    Slide the board along the card guide and remove it from the rack.


Specifications:
Parameter    Specification
    Rated Voltage    24 or 48 volts DC
    Outputs per Module    32 (four groups of 8 outputs each)
    Isolation    1500 volts (output to backplane), 500 volts (between groups)
    Output Voltage Range    20 to 60 volts
    Output Current    0.5 amps per point, 2 amps per group
    Inrush Current    10 amps maximum for 20 ms
    Output Voltage Drop    1 volt (2 ohms) maximum
    Response Time-On    1 ms maximum
    Response Time-Off    1 ms maximum
    Output Leakage Current    1 mA maximum
    Current Required from 5V Bus    0.25 amps

This module is compatible with the VME system and is designed to meet VME standard C.1.

For installations requiring compliance with FCC or European Union Directives, refer to Installation Requirements for Conformance to Standards.

>> GE Fanuc IC697MDL750 User manual (pdf)

++ Other 90-30 PLC modules

----------

+ Ge-Fanuc 2 Homepage

+ Ge-Fanuc Contact (for Automation Mall)

+ About Ge-Fanuc

Reminder: GE Fanuc IC697MDL750 and other Ge-Fanuc modules are available for sale at Otomasyon Mall. Please note that some of the devices are used products, so take this into consideration when purchasing. However, once products are out of stock, new ones will not be restocked. The information above is based on general knowledge and does not guarantee accuracy. For more detailed and precise information, it is recommended to refer to the relevant device’s user manual. 06.03.2013 

"Please note: The user manuals, commissioning suggestions, error codes, and solution recommendations provided on this page are not binding. The information and documents above are open to and even in need of improvement. As the Otomasyon Mall Community, we gladly welcome your suggestions and contributions. If you have field experience and insights on ease of use, please do not hesitate to share them with us."