24/48 Volt DC, 2 Amp, 16 Point Output Module
16 output points: Four isolated groups of 4 points each
2 amp capacity per point
High inrush capacity: 10x rated current
The 24/48 Volt DC 2 Amp Output Module provides 16 output points divided into four isolated groups of 4 points each. Each group of four outputs is individually fused with a 10-amp fuse. The module supports a high degree of inrush current, making it suitable for a wide range of load types with such characteristics.
At the top of the module, there are LED indicators that display the ON/OFF status of each output point on the logic (PLC) side, as well as a separate LED to indicate the status of the fuse.
The module is mechanically keyed to prevent incorrect replacement with a different module type. I/O references can be configured by the user without the need for jumpers or DIP switches on the module.
Configuration is performed using the MS-DOS or Windows programming software that operates on Windows 95, Windows NT, and connects via Ethernet TCP/IP or through the SNP port. The configuration software is installed on the programming device, which can be an IBM XT, AT, PS/2, or compatible personal computer.
Output Characteristics:
The 24/48 Volt DC 2 Amp Output Module is compatible with various load devices, such as:
Solenoids
Motor starters
Indicators
The output current rating is 2 amps per point. Each group of four outputs has a total current capacity of 4 amps. Each output can handle a surge current greater than its long-term rating. The repetition rate for surge currents depends on the device's current rating and duty cycle (the percentage of time the device is ON). For typical incandescent devices operating at a 50% duty cycle, the following repetition rates apply:
Steady-State Current (mA) Repetition Rate (Hz)
0.5 5
1 1
2 0.1
Fault Mode Selection:
The output points can be configured to respond to certain operating or default conditions by assuming one of two states:
Maintain the existing output state
Turn outputs OFF
More detailed information can be found in the programming manual.
Fusing:
Each group of 4 outputs is protected by a 10-amp fuse. When replacing the fuse, use one of the following types:
3AG - 10 amp, 250V, Fast Acting
Metric 5 x 20 mm - 10 amp, 250V, Fast Acting
Mechanical Keying:
The module includes a mechanical key that prevents the inadvertent substitution of another module type in the same slot. The key fits into a specific area on the module and remains latched to the backplane when the module is removed, ensuring that only identical module types can be inserted into the slot.
Field Wiring:
The module is wired as shown. Each group of four outputs is isolated, and a wire from the power source to the power input terminals is required for each group (the power input terminals for each group are not connected inside the module). The terminal board supports wire sizes ranging from AWG #22 (0.36 mm²) to AWG #14 (2.1 mm²). Two wires of the same size can be terminated on one lug. There is enough room for a bundle of forty #14 wires to pass through the terminal board cavity. The wire bundle can be secured to the terminal board using a cable tie.
Technical Specifications:
Parameter Details
Rated Voltage 24 or 48 volts DC
Outputs per Module 16 (four groups of 4 outputs each)
Isolation 1500 volts (output to backplane), 500 volts (between groups)
Output Voltage Range 20 to 60 volts DC
Output Current 2 amps maximum per point, 4 amps maximum per group
Inrush Current 20 amps maximum for 20 ms
Output Voltage Drop Maximum 0.8 volts (0.4 ohms)
Response Time (On) 2 ms maximum
Response Time (Off) 2 ms maximum
Output Leakage Current 1 mA maximum
Current Required from 5V Bus 0.15 amps
The module is designed to support the VME system standard, VME standard C.1.