IC697MDL350
120 Volt AC 0.5 Amp, 32-Point Output Module IC697MDL350
32 output points in four isolated groups of 8 points each
0.5 amp capacity per point
High inrush current capacity (20x rated current)
Overview:
The 120 Volt AC 0.5 Amp Output Module provides 32 output points divided into four isolated groups of 8. This allows each group of 8 outputs to operate on a different AC phase. Each group is individually fused with a 5 amp fuse for protection.
The module is designed to handle high inrush currents, making it suitable for various inductive and incandescent loads. It is capable of switching larger contactors, such as size 2 contactors.
LED indicators are located at the top of the module to show the ON/OFF status of each output and the status of the fuses.
The module is mechanically keyed to ensure correct replacement with a similar module in the field. I/O references can be configured without the use of jumpers or DIP switches.
Operation:
This module supports configuration using MS-DOS or Windows programming software, either running on Windows 95 or Windows NT. The configuration can be completed via Ethernet TCP/IP or the SNP port. The programming device can be an IBM PC or a compatible device.
Output Characteristics:
The 120 Volt AC 0.5 Amp Output Module is compatible with a variety of load types, including:
Solenoids and motor starters
Indicators
The module’s 0.5 amp rating applies to the continuous current capacity for each point. However, at higher operating temperatures, the total current capacity per group may be limited (refer to specifications for detailed information).
Each output can handle surge currents significantly higher than its continuous rating. The repetition rate of these surges depends on the device's rated current and duty cycle. For typical incandescent loads operating at a 50% duty cycle, the following repetition rates apply:
Steady-state Current (mA) Repetition Rate (Hz)
100 5
250 1
500 0.1
Fault Mode Selection:
The module can be configured to define the behavior of output points during default or operating fault conditions:
Maintain the existing output state
Turn the outputs OFF
Fusing:
Each group of 8 outputs is protected by a 5-amp fuse. The fuses can be replaced with the following types:
3AG - 5 amp, 250V, Fast Acting
Metric 5 x 20 mm - 5 amp, 250V, Fast Acting
Mechanical Keying:
The module features mechanical keying to prevent incorrect module installation. The key fits into a uniquely shaped area on the board beneath the connector, ensuring proper module placement.
When the module is installed, the key locks onto the backplane’s center rail. If relocation is necessary, the key can be unlatched and moved along with the module to its new position.
Field Wiring:
Each group of 8 outputs is isolated from the others. A power wire must be connected to the input terminals for each group, as they are not internally connected within the module.
The detachable field wiring terminal board accepts wires sized from AWG #22 (0.36 mm²) to AWG #14 (2.10 mm²). Two wires of the same size may be terminated in a single lug. There is room for a bundle of forty AWG #14 wires to be routed out through the terminal board cavity, secured with a cable tie.
Recommended Field Wiring Procedures:
Power must be turned off before removing or installing terminal boards. The terminal board can be removed by disengaging the jackscrew.
To remove the terminal board, grasp it by the top and swing it outward. Do not use the hinged door for this operation.
The terminal board is designed to accept wire sizes from AWG #22 to AWG #14. Ensure that a maximum insulation diameter of 0.135 inches is not exceeded for proper closure of the hinged door.
After making all connections, the wire bundle should be securely fastened using cable ties, ensuring proper routing and ventilation.
Removing an I/O Module:
To remove the module:
Grasp the board firmly at the top and bottom.
Squeeze the rack clips to disengage the module from the rack rail.
Slide the module out along the card guide.
Specifications:
Parameter Value
Rated Voltage 120 Volts AC
Outputs per Module 32 (four groups of 8 outputs each)
Isolation 1500 volts (any output to backplane), 500 volts between groups
Output Voltage Range 85 to 132 volts AC, 47-63 Hz
Output Current 0.5 amps max per point, 2 amps max per group
Inrush Current 10 amps max per point for one cycle (20 ms)
Voltage Drop 3 volts max
Response Time On: 1 ms max, Off: 1/2 cycle
Leakage Current 1.5 mA max
Current from 5V Bus 0.5 amps
This module’s robust features and high inrush capacity make it suitable for demanding industrial applications requiring reliable AC output switching capabilities.