IC697MDL341

120/240 Volt AC, 2 Amp Isolated 12-Point Output Module
    12 individually isolated output points
    2 Amp capacity per point
    High inrush capacity (10x rated current)

The 120/240 Volt AC, 2 Amp Isolated Output Module is designed for use with a Programmable Logic Controller (PLC) and provides 12 isolated output points. Each point can be used on different phases of the AC supply, and every output point is individually fused with a 3.15 Amp replaceable fuse.

The module is suitable for a wide range of inductive and incandescent loads due to its high inrush current capacity. It can operate most size 4 contactors.

LED indicators at the top of the module display the ON-OFF status of each point on the PLC side, and an additional LED shows the fuse status. If any fuse blows, the fuse status LED turns ON.

The module is mechanically keyed to ensure that it can only be replaced with the correct module type in the field. I/O references are user-configurable without using jumpers or DIP switches on the module.


Operation:

Configuration of the module is performed using MS-DOS or Windows programming software, which can run on Windows 95 or Windows NT. Configuration can be done over Ethernet TCP/IP or through the SNP port. The programming device can be an IBM PC or compatible computer.

Although the module is configured as a 16-point output, only outputs 1 through 12 are available for use in your program. For instance, if the starting reference is Q0017, then valid references will be Q0017 through Q0028.


Output Characteristics:

The 120/240 Volt AC, 2 Amp Isolated Output Module is compatible with a wide range of load devices, such as:

    Solenoids
    Motor starters
    Indicators

Each output point has a 2 Amp continuous current rating. The maximum current for the entire module is limited to 16 Amps due to heat dissipation.

Each output can handle transient surge currents that exceed its long-term current rating. The frequency at which these surges can be repeated depends on the current rating and duty cycle of the device.

For incandescent devices operating at a 50% duty cycle, the following repetition rates apply:
Steady-State Current (mA)    Repetition Rate (Hz)
0.5    5
1    1
2    0.1


Fault Mode Selection:

The module can be configured via the programmer so that output points respond to specific conditions by:

    Maintaining the current output state
    Turning outputs OFF

For more details, refer to the Programming Software User’s Manual.


Fusing:

Each output is protected by a 3.15 Amp fuse. Replace fuses with the following type:

    Metric 5 x 20 mm - 3.15 Amp, 250V, Slo-Blo

Mechanical Keying:

The module features mechanical keying to prevent the accidental installation of the wrong module type into a slot. The key fits into a uniquely shaped area on the circuit board below the connector. Each module includes a key for installation.

When the module is inserted, the key latches onto the backplane center rail. If the module is removed, the key remains on the rail, ensuring only identical module types can be installed in that slot. To change the module's location, the key can be removed by pushing it upwards and pulling it off the rail.


Field Wiring:

The module requires wiring as shown in Figure 2. Since each output is isolated, a wire must run from the power source to the power input terminal for each output (power input terminals are not connected internally in the module).

The detachable field wiring terminal board supports wire sizes from AWG #22 (0.36 mm²) to AWG #14 (2.10 mm²). Two wires of the same size may be connected to a single terminal. There is enough space for a bundle of forty AWG #14 wires to pass through the terminal board cavity.


Removing an I/O Module:

    Firmly grasp the top and bottom of the module cover.
    Press the rack clips on the back to disengage the module from the rack rail.
    Pull the module out of the backplane connector and slide it out of the rack.

Technical Specifications:
Parameter    Specification
Rated Voltage    120/240 volts AC
Outputs per Module    12 individually isolated outputs
Isolation    1500 volts (any output to backplane), 500 volts between points
Output Voltage Range    85 to 264 volts AC, 47-63 Hz
Output Current    2 amps per point, 16 amps per module
Inrush Current    20 amps maximum for one cycle (20 ms)
Voltage Drop    1.5 volts maximum
Response Time (On)    1 ms maximum
Response Time (Off)    1/2 cycle maximum
Leakage Current    3 mA max at 120V AC, 6 mA max at 240V AC
Current from 5V Bus    0.25 Amp

This module is designed for reliable control of AC outputs in industrial applications that require high current capacity and isolated outputs.

>> GE Fanuc IC697MDL341 User manual (pdf)

++ Other 90-30 PLC modules

----------

+ Ge-Fanuc 2 Homepage

+ Ge-Fanuc Contact (for Automation Mall)

+ About Ge-Fanuc

Reminder: GE Fanuc IC697MDL341 and other Ge-Fanuc modules are available for sale at Otomasyon Mall. Please note that some of the devices are used products, so take this into consideration when purchasing. However, once products are out of stock, new ones will not be restocked. The information above is based on general knowledge and does not guarantee accuracy. For more detailed and precise information, it is recommended to refer to the relevant device’s user manual. 06.03.2013 

"Please note: The user manuals, commissioning suggestions, error codes, and solution recommendations provided on this page are not binding. The information and documents above are open to and even in need of improvement. As the Otomasyon Mall Community, we gladly welcome your suggestions and contributions. If you have field experience and insights on ease of use, please do not hesitate to share them with us."