IC697BEM733
Remote I/O Scanner (IC697BEM733/735) Overview
The IC697 Remote I/O Scanner (IC697BEM733/735) is an intelligent module designed for remote IC697 racks, allowing the interface of IC697 I/O modules with the IC66* bus. This enables remote I/O capabilities for various types of PLC systems.
- Long-distance installation: Can be located up to 7500 feet (2275 meters) from the controller.
- Supports various I/O modules: Works with standard IC697 discrete and analog I/O modules, PCM, ADS, and analog expander modules.
- Handles large input/output capacities: Manages up to 128 bytes of inputs and 128 bytes of outputs per remote drop.
- Easy configuration: Configurable using MS-DOS programming software or an IC66* Hand-held Monitor.
- Bus redundancy support: Works with both CPU and IC66* bus redundancy.
- Multiple racks: Supports up to eight racks per remote drop, with a Remote I/O Scanner located in rack 0.
- High scalability: Up to 30 remote drops can be connected on the same IC66* bus.
Module Description:
The Remote I/O Scanner is housed in a single slot with a faceplate that includes several connectors for communication. It does not require a battery for operation.
LED Indicators:
- Module OK: Lights up when the module passes its power-up diagnostic tests. If this LED flashes, a problem is detected.
- I/O Enabled: Lights up when the Remote I/O Scanner is receiving output data from the CPU. If it blinks, there is a conflict or forced I/O data.
- Bus B Active: In dual-bus (redundant) configurations, this LED indicates when Bus B is active.
Installation and Configuration:
- Rack installation: The Remote I/O Scanner should be installed in rack 0, slot 1 of a remote drop. For expansion, a Bus Transmitter can be placed in any slot of rack 0, and a Bus Receiver in slot 1 of each additional expansion rack.
- Bus connections: The module can be connected to a single or dual IC66* bus using appropriate terminals. In dual-bus configurations, bus termination resistors must be installed at the end of the bus.
- Configuration: The module can be configured using MS-DOS programming software or an IC66* Hand-held Monitor. Configuration includes assigning device numbers, setting baud rates, and specifying starting references for inputs and outputs.
Technical Specifications:
- Current Required from +5V Bus: 0.8 Amps
- Bus Type: Daisy-chained bus cable (twisted pair + shield or Twinax)
- Maximum Cable Length: 7500 feet (2275 meters) at 38.4 Kbaud
- Baud Rate: Configurable: 153.6 Kbaud, 76.8 Kbaud, 38.4 Kbaud
- Number of Devices per Bus: Up to 32 devices at 153.6 Kbaud
- Ports: One 15-pin RS-422/485 serial port, one 9-pin Hand-held Monitor port
Ordering Information:
- IC697BEM733/735: Remote I/O Scanner Module
- IC600WD Cable: Available in various lengths for connection