IC694MDL940

The IC694MDL940 is a 2 Amp relay output module that provides 16 normally-open relay circuits for controlling output loads. Each output can switch up to 2 Amps, and the outputs are arranged in four groups of four points each. Each group has a common power terminal, providing flexibility for various control applications. The relay outputs can manage a wide range of devices such as motor starters, solenoids, and indicators. Power for the internal relay circuits is provided by the +24V DC bus on the backplane, while the user must supply AC or DC power to the field devices.

Each output point has an individual numbered LED to display its ON/OFF status. There are no fuses on this module, and the red bands on the label indicate that the MDL940 is a high-voltage module. This module can be installed in any I/O slot within an RX3i system.

Technical Specifications

    Rated Voltage: 24V DC, 120/240V AC (nominal, see table below for exceptions)
    Operating Voltage: 5 to 30V DC, 5 to 250V AC, 50/60 Hz
    Outputs per Module: 16 (four groups of four outputs each)
    Isolation:
        250 VAC continuous (Field to Backplane and Frame Ground)
        1500 VAC for 1 minute (Field to Backplane and Frame Ground)
        250 VAC continuous (Point to Point); 1500 VAC for 1 minute

Maximum Load:
        2 Amps pilot duty maximum per output
        4 Amps maximum per group common
    Minimum Load: 10 mA
    Maximum Inrush Current: 5 Amps
    On/Off Response Time: Maximum 15 ms
    Power Consumption:
        7 mA from the 5V bus on the backplane (all outputs ON)
        135 mA from the 24V relay bus on the backplane (all outputs ON)

Load Current Limitations

The following table shows the contact life for different load types and operating conditions:
Operating Voltage    Resistive Load    Lamp or Solenoid Load    Contact Life (Operations)
24 to 120 VAC    2 Amps    1 Amp    300,000
240 VAC    2 Amps    1 Amp    150,000
24 VDC    2 Amps    1 Amp    300,000

Note: Using appropriate suppression circuits for inductive loads can extend relay contact life. Common suppression methods include using diodes for DC loads and resistors and capacitors for AC loads.

Field Wiring

The terminal connections for the IC694MDL940 module are as follows:

    Terminal 1: Common return for Outputs 1-4
    Terminals 2-5: Outputs 1 to 4
    Terminal 6: Common return for Outputs 5-8
    Terminals 7-10: Outputs 5 to 8
    Terminal 11: Common return for Outputs 9-12
    Terminals 12-15: Outputs 9 to 12
    Terminal 16: Common return for Outputs 13-16
    Terminals 17-20: Outputs 13 to 16

Recommendations

The IC694MDL940 module is ideal for controlling moderate current loads in industrial applications. With its 2 Amp output capacity and isolation between each group of outputs, it provides flexibility for a range of devices like motor starters and solenoids. To prolong the relay contact life, especially when switching inductive loads, it is recommended to use appropriate suppression circuits. The module’s high-voltage capacity makes it a reliable choice for controlling field devices in high-voltage environments.

>> IC694MDL940 Output modules User manual (pdf)

++ Other 90-30 PLC modules

----------

+ Ge-Fanuc 2 Homepage

+ Ge-Fanuc Contact (for Automation Mall)

+ About Ge-Fanuc

Reminder: GE Fanuc IC694MDL940 Output modules and other Ge-Fanuc modules are available for sale at Otomasyon Mall. Please note that some of the devices are used products, so take this into consideration when purchasing. However, once products are out of stock, new ones will not be restocked. The information above is based on general knowledge and does not guarantee accuracy. For more detailed and precise information, it is recommended to refer to the relevant device’s user manual. 06.03.2013 

"Please note: The user manuals, commissioning suggestions, error codes, and solution recommendations provided on this page are not binding. The information and documents above are open to and even in need of improvement. As the Otomasyon Mall Community, we gladly welcome your suggestions and contributions. If you have field experience and insights on ease of use, please do not hesitate to share them with us."