IC694ALG442

Analog input and output Module: IC694ALG442

Analog Inputs: 4, differential

    Analog Current Input
        Input Ranges: 0-20 mA, 4-20 mA, 4-20 mA Enhanced
        Resolution: 5 µA (1 LSB = 5 µA)
        Absolute Accuracy: +/- 0.25% of full scale @ 25°C (77°F)
        Linearity: <1 LSB
        Common Mode Voltage: 200 VDC (maximum)
        Common Mode Rejection: >70 dB at DC; >70 dB at 60 Hz
        Cross-Channel Rejection: >80 dB from DC to 1 kHz
        Input Impedance: 250 Ω
        Input Filter Response: 29 Hz

Analog Voltage Input

    Input Ranges: 0 to +10 V (unipolar), -10 to +10 V (bipolar)
        Resolution:
            0 to +10 V: 2.5 mV (1 LSB = 2.5 mV)
            -10 to +10 V: 5 mV (1 LSB = 5 mV)
        Absolute Accuracy: +/- 0.25% of full scale @ 25°C (77°F)
        Linearity: <1 LSB
        Common Mode Voltage: 200 VDC (maximum)
        Common Mode Rejection: >70 dB at DC; >70 dB at 60 Hz
        Cross-Channel Rejection: >80 dB from DC to 1 kHz
        Input Impedance: 800 K Ohms (typical)
        Input Filter Response: 29 Hz

Note: In the presence of severe RF interference (IEC 801–3, 10V/m), accuracy may degrade to +/-2% FS.

Field Wiring: IC694ALG442

Each channel can be independently configured as a voltage or current input but not both simultaneously.

Terminal Definitions:

    1: User-supplied 24 VDC input
    2-13: Positive and negative connections for various channels
    14-19: Voltage and current outputs
    20: Frame ground connections

Input Scaling

The module scales each current and voltage input to a count value for the CPU. The resolution per bit depends on the configured input or output range.
Configured Range    Scaled Count Values
0 to 10 V (default)    0 to 32767
-10 to 10 V    -32768 to 32767
4 to 20 mA    0 to 32767
0 to 20 mA    0 to 32767
0 to 20 mA Enhanced    -8000 to 32767
Output Scaling

The module converts CPU-provided data to current or voltage values for each output.
Configured Range    Values Sent by CPU    Values Accepted by Module
0 to 10 V (default)    0 to 32767    0 to 32767
-10 to 10 V    -32768 to 32767    -32768 to 32767
4 to 20 mA    0 to 32767    0 to 32000
0 to 20 mA    0 to 32767    0 to 32767

I/O Data: IC694ALG442

The module uses two %AQ references and four %AI references, depending on configuration. Data in the %AI and %AQ registers is in 16-bit 2's complement format.

>> IC694ALG442 Analog modules User manual (pdf)

++ Other 90-30 PLC modules

----------

+ Ge-Fanuc 2 Homepage

+ Ge-Fanuc Contact (for Automation Mall)

+ About Ge-Fanuc

Reminder: GE Fanuc IC694ALG442 Analog modules and other Ge-Fanuc modules are available for sale at Otomasyon Mall. Please note that some of the devices are used products, so take this into consideration when purchasing. However, once products are out of stock, new ones will not be restocked. The information above is based on general knowledge and does not guarantee accuracy. For more detailed and precise information, it is recommended to refer to the relevant device’s user manual. 06.03.2013 

"Please note: The user manuals, commissioning suggestions, error codes, and solution recommendations provided on this page are not binding. The information and documents above are open to and even in need of improvement. As the Otomasyon Mall Community, we gladly welcome your suggestions and contributions. If you have field experience and insights on ease of use, please do not hesitate to share them with us."