IC694ALG391
Analog Output Module, Current, 2 Channel: IC694ALG391
IC694ALG391 2-Channel Analog Current Output module has two output channels, each capable of converting 12-bit binary (digital) data into an analog output signal for field devices. Each output can be set via a jumper on the module to generate signals in one of two ranges:
0 to 20 mA
4 to 20 mA
Each output can also be set as a less accurate voltage source. The selection of current or voltage output is made with a jumper or resistor on the module terminals. Both channels are updated on every scan.
Default Output or Hold-Last-State
The module’s outputs can be configured to either default to 0/4 mA or hold the Last State if the CPU goes into Stop mode or Reset. The output default state selection is made with a jumper on the module’s terminal board. See the Output Defaults section for more details.
LED
Module OK LED: Indicates the module's power supply is functioning properly when ON.
Isolated +24 VDC Power
If the module is installed in an RX3i Universal Backplane, an external source of Isolated +24 VDC is required to power the module. The external source can be connected via the TB1 connector on the left side of the backplane or directly on the module’s terminal block.
If the module is installed in an Expansion Backplane, the primary power source can either be the Isolated +24 VDC from the backplane power supply or an external Isolated +24 VDC power supply connected to the module’s terminal block. If the external source is set between 27.5-30 VDC, it will take over the module’s load from the system's Isolated 24 VDC power supply.
Specifications: IC694ALG391
Output Current Range: 4 to 20 mA and 0 to 20 mA
Output Voltage Range: 1 to 5 volts and 0 to 5 volts
Calibration: Factory calibrated (4 μA per count)
External Supply Voltage Range: 20 VDC to 30 VDC (dependent on current load and ambient temperature)
External Supply Voltage Ripple: Maximum 10%
Update Rate: Approximately 5 milliseconds (both channels, application-dependent)
Resolution:
4 to 20 mA: 4 μA (1 LSB = 4 μA)
0 to 20 mA: 5 μA (1 LSB = 5 μA)
1 to 5V: 1 mV (1 LSB = 1 mV)
0 to 5V: 1.25 mV (1 LSB = 1.25 mV)
Absolute Accuracy:
4 to 20 mA: +/-8 μA at 25°C (77°F)
0 to 20 mA: +/-10 μA at 25°C (77°F)
1 to 5V: +/-50 mV at 25°C (77°F)
0 to 5V: +/-50 mV at 25°C (77°F)
Maximum Compliance Voltage: 25 VDC
User Load (Current Mode): 0 to 850 Ohms
Output Load Capacitance (Current Mode): 2000 pF
Output Load Inductance (Current Mode): 1 H
Maximum Output Loading (Voltage Mode): 5 mA (minimum resistance 2 kΩ, maximum capacitance 2000 pF)
Isolation (Field to Backplane): 250 VAC continuous, 1500 VAC for 1 minute
Internal Power Consumption: 30 mA from +5 VDC supply, 215 mA from Isolated +24 VDC supply
Data Format: IC694ALG391
Module data is stored by the PLC CPU in 16-bit 2’s complement format as shown below:
X 11 10 9 8 7 6 5 4 3 2 1 0 X X X
The 13 most significant bits from the %AQ register are converted to sign magnitude by the PLC and sent to the module.
Wiring: IC694ALG391
To minimize capacitive loading and noise, all field connections to the module should be wired using a good grade of twisted, shielded instrumentation cable. The shields should be connected to GND on the user terminal block. The GND connection provides access to the backplane ground, which helps reject noise from shield drain currents.
If no jumper is installed, the module operates as a current source. If the jumper is installed, the module functions as a voltage source.
Field Wiring Example:
In this example, Output 1 is configured as a voltage output (jumper JMPV1 connected to IOUT1) in the 0 to 5V range (RANGE1 jumper installed). Output 2 is configured as a current output (jumper JMPV2 not connected) in the 4 to 20 mA mode (RANGE2 jumper not installed). Both outputs will hold their last state (no output default jumper installed, external +24 VDC power supply connected).
>> IC694ALG391 Analog modules User manual (pdf)
----------
+ Ge-Fanuc Contact (for Automation Mall)