IC694ALG390
IC694ALG390 2-Channel Analog Voltage Output Module
The IC694ALG390 2-Channel Analog Voltage Output module provides two output channels. Each channel is capable of converting 13 bits of binary (digital) data to an analog output signal for field devices. This module supports voltage output in the range of -10V to +10V. Both channels are updated on each CPU scan.
Default to 0V or Hold Last State
The module’s outputs can be configured to either:
Default to 0 volts or
Hold Last State when the CPU enters Stop mode or Reset.
This selection is made via a jumper on the module. If the jumper is not installed, the outputs will Hold Last State.
Installation
This module can be installed in any I/O slot in an RX3i system.
Power Supply
If installed in an RX3i Universal Backplane, an external source of Isolated +24 VDC is required to power the module. The external supply can be connected either via the TB1 connector on the left side of the backplane or directly on the module’s terminal block.
If installed in an Expansion Backplane, the primary power source can be either the Isolated +24 VDC from the backplane power supply or an external Isolated +24 VDC supply. External power should be used to maintain Hold Last State operation during a backplane power failure.
LED Status Indicator
Module OK LED: The ON state indicates that the module’s power supply is functioning properly.
Specifications: IC694ALG390
Voltage Range: -10 to +10 volts
Calibration: Factory calibrated to 2.5 mV per count
Supply Voltage (nominal): +24 VDC (from isolated +24 VDC backplane or user-supplied source) and +5 VDC from backplane
External Supply Voltage Range: 18 to 30 VDC
External Supply Ripple: 10% maximum
Update Rate: Approximately 5 milliseconds (both channels); application-dependent
Resolution: 2.5 mV (1 LSB = 2.5 mV)
Accuracy: +/-5 mV at 25°C (77°F)
Output Loading (maximum): 5 mA (minimum resistance of 2 kΩ)
Output Load Capacitance: 2000 pF maximum
Isolation (Field to Backplane): 250 VAC continuous, 1500 VAC for 1 minute
Internal Power Consumption:
32 mA from +5 VDC
120 mA from +24 VDC (isolated backplane or user supply)
Data Format: IC694ALG390
The module data is stored by the PLC CPU in a 16-bit 2’s complement format:
The resolution is 12 bits binary plus sign (13 bits total), with 1 part in 8192. The module scales the digital data to create an output voltage for the output.
Field Wiring: IC694ALG390
Terminal Connections:
Output 1: Terminal 3
Output 2: Terminal 4
Output 1 Common: Terminal 5
Output 2 Common: Terminal 6
Shield Termination (Output 1): Terminal 7
Shield Termination (Output 2): Terminal 8
External +24V Power Supply +: Terminal 17
External +24V Power Supply -: Terminal 19
DEF0 is the optional output default jumper that determines the behavior of the outputs in Stop or Reset modes. Install the jumper if outputs should default to 0V; leave it off to Hold Last State.
To minimize capacitive loading and noise, shielded instrumentation cable should be used, and shields should be connected to GND on the terminal block.
>> IC694ALG390 Analog modules User manual (pdf)
----------