IC694ALG222

IC694ALG222 16-Channel Analog Voltage Input Module

The IC694ALG222 is a versatile 16-channel analog voltage input module that offers flexibility by allowing 16 single-ended or 8 differential input channels. Each channel can be configured using the RX3i system’s configuration software, with two input ranges available:

   0 to 10 V (unipolar), which is the default setting
   -10 to +10 V (bipolar)

You can set high and low alarm limits for both input ranges. This module can be installed in any I/O slot in an RX3i system, making it adaptable for a variety of applications.

Isolated +24 VDC Power

If the module is placed in an RX3i Universal Backplane, it requires an external source of isolated +24 VDC to power the module. This power source must be connected to the TB1 connector located on the left side of the backplane. However, if the module is installed in an Expansion Backplane, the backplane’s power supply will provide the required isolated +24 VDC power.

LED Indicators

The MODULE OK LED provides key status information on power-up:

   ON: Status is OK, module is properly configured.
   OFF: No backplane power or software is not running (watchdog timer timed out).
   Continuous rapid flashing: Configuration data was not received from the CPU.
   Slow flashing, then OFF: Power-up diagnostics failed or a code execution error occurred.

The Module P/S LED indicates that the module’s internally-generated +5 VDC supply is above a minimum threshold level.

Technical Specifications

   Number of Channels:
        1 to 16 (single-ended)
        1 to 8 (differential)

   Input Voltage Ranges:
        0 V to +10 V (unipolar)
        -10 V to +10 V (bipolar); selectable per channel

   Calibration: Factory-calibrated to:
        2.5 mV per count in the 0 V to +10 V range (unipolar)
        5 mV per count in the -10 V to +10 V range (bipolar)

   Update Rate:
        6 milliseconds for all 16 single-ended channels
        3 milliseconds for all 8 differential channels

   Resolution:
        2.5 mV for the 0 V to +10 V range
        5 mV for the -10 V to +10 V range

   Accuracy:
        +/-0.25% of full scale at 25°C (77°F)
        +/-0.5% of full scale across the entire operating temperature range

   Linearity: < 1 LSB

   Isolation (Field to Backplane and to Frame Ground):
        250 VAC continuous
        1500 VAC for 1 minute

   Common Mode Voltage (Differential Mode): +/-11 V (bipolar range)
   Cross-Channel Rejection: > 80dB from DC to 1 kHz

   Input Impedance:
        500K Ohms (single-ended mode)
        1 MegaOhm (differential mode)

   Input Filter Response:
        41 Hz (single-ended)
        82 Hz (differential)

   Power Consumption:
        112 mA (maximum) from the backplane’s +5 VDC bus
        41 mA (maximum) from the backplane’s isolated +24 VDC supply

Configuration Settings

The IC694ALG222 module’s configurable parameters allow for flexible operation:

   Active Channels: 1 to 16 (single-ended mode) or 1 to 8 (differential mode). Channels are scanned in sequential, contiguous order.
   Mode: Single-ended (default) or differential mode.
   Reference Address for Input Data: Specifies the memory location for input data from the module.
   Reference Address for Status Data: Specifies where status information starts in memory.
   Length: 8, 16, 24, 32, or 40 status bits reported to the PLC CPU. Includes diagnostics and alarm status.
   Range: 0 to 10 V (default) or -10 to 10 V. Selectable per channel.
   Alarm Low/High: Configurable low and high alarm limits for each channel.
   I/O Scan Set: Assigns the module to one of the I/O Scan Sets defined in the CPU configuration.

Data Format

The module stores 12-bit resolution analog input data in 16-bit 2’s complement format. In 0 to 10 V mode, input data is scaled so that 0 V corresponds to a count of 0 and 10 V corresponds to a count of +32,000. In bipolar mode (-10 V to +10 V), -10 V corresponds to -32,000, 0 V corresponds to 0, and +10 V corresponds to +32,000.

Factory calibration adjusts the analog value per bit (resolution) to a multiple of full scale:

   2.5 mV per bit in the unipolar range
   5 mV per bit in the bipolar range

Status Data

The module can return up to 40 status bits to the CPU, providing the following information:

   Module and power supply status
   High and low alarms for each channel

>> IC694ALG222 Analog modules User manual (pdf)

++ Other 90-30 PLC modules

----------

+ Ge-Fanuc 2 Homepage

+ Ge-Fanuc Contact (for Automation Mall)

+ About Ge-Fanuc

Reminder: GE Fanuc IC694ALG222 Analog modules and other Ge-Fanuc modules are available for sale at Otomasyon Mall. Please note that some of the devices are used products, so take this into consideration when purchasing. However, once products are out of stock, new ones will not be restocked. The information above is based on general knowledge and does not guarantee accuracy. For more detailed and precise information, it is recommended to refer to the relevant device’s user manual. 06.03.2013 

"Please note: The user manuals, commissioning suggestions, error codes, and solution recommendations provided on this page are not binding. The information and documents above are open to and even in need of improvement. As the Otomasyon Mall Community, we gladly welcome your suggestions and contributions. If you have field experience and insights on ease of use, please do not hesitate to share them with us."